| Parameter | Value |
|---|---|
| GTIN | 4055626456652 |
| Orderkey | 2910105 |
| (General) | IEC 61010-2-201 |
| (Drawings) | |
| (EMC data) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| (Standards) | 2 kV (Test Level 3 - asymmetrical) |
| Catalog page | Page 268 (C-4-2019) |
| Packing unit | 1 pc |
| Depth (Drawings) | 125 mm |
| Width (Drawings) | 59 mm |
| Country of origin | TH (Thailand) |
| ETIM 5.0 (eCl@ss) | EC002540 |
| ETIM 6.0 (eCl@ss) | EC002540 |
| ETIM 7.0 (eCl@ss) | EC002540 |
| Height (Drawings) | 130 mm |
| Input (Standards) | 2 kV (Test Level 3 - symmetrical) |
| Diagram (Drawings) | |
| Output (Standards) | 1 kV (Test Level 2 - symmetrical) |
| Voltage (Standards) | 230 V AC |
| Comments (Standards) | Criterion B |
| Custom tariff number | 85044030 |
| (Ambient conditions) | 2.4 kV AC (routine test) |
| China RoHS (EMC data) | Environmentally Friendly Use Period = 25; |
| Frequency (Standards) | 50 Hz |
| REACh SVHC (EMC data) | Lead 7439-92-1 |
| Criterion A (Standards) | Normal operating behavior within the specified limits. |
| Criterion B (Standards) | Temporary impairment to operational behavior that is corrected by the device itself. |
| Voltage dip (Standards) | 0 % |
| Block diagram (Drawings) | |
| Voltage dips (Standards) | EN 61000-4-11 |
| Noise emission (Standards) | EN 55016 |
| Additional text (Standards) | Test Level 2 |
| Climatic class (Dimensions) | 3K3 (in acc. with EN 60721) |
| Frequency range (Standards) | 0.15 MHz ... 80 MHz |
| Discharge in air (Standards) | 8 kV (Test Level 3) |
| eCl@ss 8.0 (Classifications) | 27049002 |
| eCl@ss 9.0 (Classifications) | 27040701 |
| Contact discharge (Standards) | 6 kV (Test Level 3) |
| Harmonic currents (Standards) | EN 61000-3-2 |
| Number of periods (Standards) | 1 period |
| eCl@ss 11.0 (Classifications) | 27040701 |
| Dimensional drawing (Drawings) | |
| Standard designation (General) | Requirement of the semiconductor industry with regard to mains voltage dips |
| Efficiency (Ambient conditions) | typ. 93 % (120 V AC) |
| Net weight (Ambient conditions) | 1 kg |
| Standards/regulations (General) | SEMI F47 - 0706 (185 V AC) |
| Test field strength (Standards) | 10 V/m (Test Level 3) |
| eCl@ss 10.0.1 (Classifications) | 27040701 |
| Degree of pollution (Dimensions) | 2 |
| Installation height (Dimensions) | ≤ 3000 m (> 2000 m, Derating: 10 %/1000 m) |
| Degree of protection (Dimensions) | IP20 |
| Low Voltage Directive (Standards) | Conformance with Low Voltage Directive 2014/35/EC |
| Conducted interference (Standards) | EN 61000-4-6 |
| Electrostatic discharge (Standards) | EN 61000-4-2 |
| Fast transients (burst) (Standards) | EN 61000-4-4 |
| Conducted noise emission (Standards) | EN 55016 |
| Electromagnetic HF field (Standards) | EN 61000-4-3 |
| Weight per Piece (excluding packing) | 1,240.000 g |
| Housing material (Ambient conditions) | Aluminum (AlMg3) / sheet steel, zinc-plated |
| Protection class (Ambient conditions) | I |
| Mounting position (Ambient conditions) | horizontal DIN rail NS 35, EN 60715 |
| Surge voltage load (surge) (Standards) | EN 61000-4-5 |
| Foot latch material (Ambient conditions) | Sheet steel, zinc-plated |
| Degree of protection (Ambient conditions) | IP20 |
| Electromagnetic compatibility (Standards) | Conformance with EMC Directive 2014/30/EU |
| Assembly instructions (Ambient conditions) | alignable: 0 mm horizontally, 30 mm vertically |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K) |
| EMC requirements for noise immunity (General) | EN 61000-6-2 |
| MTBF (IEC 61709, SN 29500) (Ambient conditions) | > 900000 h (25 °C) |
| Insulation voltage input / PE (Ambient conditions) | 3.5 kV AC (type test) |
| Flammability rating according to UL 94 (Dimensions) | V0 () |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Insulation voltage input/output (Ambient conditions) | 4 kV AC (type test) |
| Ambient temperature (start-up type tested) (Dimensions) | -40 °C |
| Environmental protection directive (Ambient conditions) | RoHS Directive 2011/65/EU |
| Max. permissible relative humidity (operation) (Dimensions) | ≤ 95 % (at 25 °C, non-condensing) |
| Installation distance right/left (active, passive) (Drawings) | 0 mm / 0 mm (POut≥50% ) |
| Installation distance top/bottom (active, passive) (Drawings) | 30 mm / 30 mm (POut≥50% ) |
Technical specifications and performance data