| Parameter | Value |
|---|---|
| > 85 ms (230 V AC) | |
| CSA | CAN/CSA-C22.2 No. 60950-1-07 |
| Depth | 84 mm |
| Input | 4 kV (Test Level 4 - asymmetrical) |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Width | 35 mm |
| Height | 90 mm |
| Output | 2 kV (Test Level 3 - asymmetrical) |
| Voltage | 10 V (Test Level 3) |
| Comments | Criterion B |
| Derating | 55 °C ... 70 °C (2.5 %/K) |
| Frequency | 50 Hz |
| Rise time | < 0.5 s (UOUT(10 % ... 90 %)) |
| Efficiency | typ. 88 % (120 V AC) |
| Input fuse | 2.5 A (slow-blow, internal) |
| Criterion A | Normal operating behavior within the specified limits. |
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
| Voltage dip | 70 % |
| Input/Output | asymmetrical |
| Output power | 60 W |
| Product type | Power supply |
| Screw thread | M3 |
| UL approvals | UL/C-UL listed UL 508 |
| Assembly note | alignable: 0 mm horizontally, 30 mm vertically |
| Mounting type | DIN rail mounting |
| Response time | < 2 ms |
| Climatic class | 3K22 (in accordance with EN 60721-3-3) |
| Inrush current | < 30 A (typ.) |
| Product family | UNO POWER |
| Additional text | Class 3 |
| Frequency range | 80 MHz ... 1 GHz |
| Residual ripple | < 30 mVPP(with nominal values) |
| Type of housing | Polycarbonate |
| Article revision | 04 |
| Discharge in air | 8 kV (Test Level 3) |
| Housing material | Plastic |
| Number of phases | 1.00 |
| Protection class | II (in closed control cabinet) |
| Stripping length | 8 mm |
| Connection method | Screw connection |
| Contact discharge | 6 kV (Test Level 3) |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Number of periods | 25 periods |
| AC frequency range | 50 Hz ... 60 Hz |
| Protective circuit | Transient surge protection; Varistor |
| Types of signaling | LED |
| Current consumption | typ. 1.3 A (100 V AC) |
| Degree of pollution | 2 |
| Foot latch material | POM (Polyoxymethylene) |
| Input voltage range | 85 V AC ... 264 V AC |
| Short-circuit-proof | yes |
| Test field strength | 10 V/m (Test Level 3) |
| Connection in series | yes |
| Degree of protection | IP20 |
| Frequency range (fN) | 50 Hz ... 60 Hz ±10 % |
| Mains buffering time | > 20 ms (120 V AC) |
| Standard designation | Requirement of the semiconductor industry with regard to mains voltage dips |
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| Output characteristic | HICCUP |
| Standards/regulations | EN 61000-4-2 |
| Tightening torque max | 0.6 Nm |
| Typical response time | < 1 s |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| Connection in parallel | yes, for redundancy and increased capacity |
| Input voltage range AC | 85 V AC ... 264 V AC |
| Nominal output voltage | 24 V DC |
| Power factor (cos phi) | 0.49 |
| Tightening torque, min | 0.5 Nm |
| With protective coating | no |
| Standards/specifications | SEMI F47 - 0706 (180 V AC) |
| Nominal power consumption | 135.5 VA |
| Standard - Safe isolation | DIN VDE 0100-410 |
| MTBF (IEC 61709, SN 29500) | > 785000 h (40 °C) |
| Feedback voltage resistance | < 35 V DC |
| Nominal input voltage range | 100 V AC ... 240 V AC |
| Nominal output current (IN) | 2.5 A (-25 °C ... 55 °C) |
| Power loss nominal load max. | < 7 W |
| Standard - Electrical safety | IEC 62368-1 (SELV) |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Inrush current integral (I2t) | < 0.5 A2s (typ.) |
| Voltage type of supply voltage | AC |
| Ambient temperature (operation) | -25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K) |
| Insulation voltage input/output | 4 kV AC (type test) |
| Conductor cross section AWG max. | 14 |
| Conductor cross section AWG min. | 24 |
| Installation distance right/left | 0 mm / 0 mm |
| Installation distance top/bottom | 30 mm / 30 mm |
| SIL in accordance with IEC 61508 | 0 |
| Maximum no-load power dissipation | < 0.3 W |
| Standard - Safety of transformers | EN 61558-2-16 |
| Conductor cross section, rigid max. | 2.5 mm² |
| Conductor cross section, rigid min. | 0.2 mm² |
| EMC requirements for noise emission | EN 61000-6-3 |
| EMC requirements for noise immunity | EN 61000-6-1 |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Standard – Safety extra-low voltage | IEC 62368-1 (SELV) und EN 60204-1 (PELV) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Recommended breaker for input protection | 6 A ... 16 A (Characteristics B, C, D, K) |
| Ambient temperature (start-up type tested) | -40 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
| Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
| Protection against overvoltage at the output (OVP) | ≤ 35 V DC |
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
| Flammability rating according to UL 94 (housing / terminal blocks) | V0 |
| Single conductor/flexible terminal point with ferrule with plastic sleeve, max. | 2.5 mm² |
| Single conductor/flexible terminal point with ferrule with plastic sleeve, min. | 0.2 mm² |
| Single conductor/flexible terminal point with ferrule without plastic sleeve, max. | 2.5 mm² |
| Single conductor/flexible terminal point with ferrule without plastic sleeve, min. | 0.2 mm² |
| Approval - requirement of the semiconductor industry with regard to mains voltage dips | EN 61000-4-11 |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Technical specifications and performance data
Installation and operation guide