| Parameter | Value |
|---|---|
| GTIN | 4046356484046 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2900174 |
| Catalog page | Page 523 (C-5-2017) |
| Depth (Note) | 80 mm |
| Packing unit | 1 pc |
| Width (Note) | 162 mm |
| Height (Note) | 112 mm |
| Country of origin | DE (Germany) |
| Custom tariff number | 85369010 |
| Connection name (General) | Field level |
| Connection method (General) | Screw connection |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Insulation (Supported controller) | Functional insulation |
| Designation (Supported controller) | Air clearances and creepage distances |
| Status display (Ambient conditions) | Green LED (supply), yellow LED (channel) |
| Weight per Piece (excluding packing) | 612.000 g |
| Conductor cross section AWG (General) | 24 ... 12 |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Mounting position (Ambient conditions) | any |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Conductor cross section solid (General) | 0.2 mm² ... 4 mm² |
| Number of positions (Ambient conditions) | 50 |
| Degree of protection (Ambient conditions) | IP00 |
| Torque (Connection data for connection 1) | 0.5 Nm |
| Conductor cross section flexible (General) | 0.2 mm² ... 2.5 mm² |
| Degree of pollution (Supported controller) | 2 |
| Rated surge voltage (Supported controller) | 0.5 kV (1.2/50 μs) |
| Overvoltage category (Supported controller) | II |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 70 °C |
| Standards/regulations (Supported controller) | DIN EN 50178: 1998-04 |
| Controller (Connection data for connection 3) | Yokogawa ProSafe-RS |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Rated insulation voltage (Supported controller) | 50 V |
| Max. perm. operating voltage (Ambient conditions) | 24 V DC ±5 % |
| Connection name (Connection data for connection 1) | Controller level |
| Connection name (Connection data for connection 2) | Supply |
| Connection method (Connection data for connection 1) | Yokogawa KS-compatible |
| Connection method (Connection data for connection 2) | pluggable |
| Max. perm. current (per branch) (Ambient conditions) | 100 mA |
| - suitable I/O card (Connection data for connection 3) | SDV531/-L |
| Number of positions (Connection data for connection 1) | 50 |
| Number of positions (Connection data for connection 2) | 6 |
| Number of connections (Connection data for connection 1) | 2 |
| Number of connections (Connection data for connection 2) | 1 |
| Max. permissible current (separate power supply) (Ambient conditions) | 6.3 AT (F17, F18) pluggable fuse (5x20, 6.3 A), DIN 41662 |
Technical specifications and performance data
Installation and operation guide