| Parameter | Value |
|---|---|
| Note | Screws with hexagonal socket |
| Color | gray/black-yellow |
| Width | 124 mm |
| Height | 110.9 mm |
| Length | 100 mm |
| Height NS 32 | 116 mm |
| Screw thread | M10 |
| Height NS 35/15 | 118.5 mm |
| Open side panel | nein |
| Number of levels | 1 |
| Pollution degree | 3 |
| Stripping length | 40 mm |
| Connection method | Screw connection |
| Nominal current IN | 309 A |
| Nominal voltage UN | 1000 V |
| Insulating material | PA |
| Number of positions | 4 |
| Rated surge voltage | 8 kV |
| Maximum load current | 309 A (with 150 mm² conductor cross section) |
| Overvoltage category | III |
| Nominal cross section | 150 mm² |
| Number of connections | 8 |
| Tightening torque max | 30 Nm |
| Tightening torque, min | 25 Nm |
| Insulating material group | I |
| Conductor cross section AWG max. | 300 kcmil |
| Conductor cross section AWG min. | 2 |
| Connection in acc. with standard | IEC 60947-7-1 |
| Conductor cross section solid max. | 150 mm² |
| Conductor cross section solid min. | 35 mm² |
| Conductor cross section flexible max. | 150 mm² |
| Conductor cross section flexible min. | 50 mm² |
| Flammability rating according to UL 94 | V0 |
| Max. AWG conductor cross section, flexible | 300 kcmil |
| Min. AWG conductor cross section, flexible | 1/0 |
| Cross section with insertion bridge, solid max. | 150 mm² |
| 2 conductors with same cross section, solid max. | 50 mm² |
| 2 conductors with same cross section, solid min. | 25 mm² |
| Cross section with insertion bridge, stranded max. | 120 mm² |
| 2 conductors with same cross section, stranded max. | 50 mm² |
| 2 conductors with same cross section, stranded min. | 35 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 150 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 50 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 150 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 50 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. | 50 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. | 25 mm² |
Technical specifications and performance data