| Parameter | Value |
|---|---|
| IEC 60947-7-3 | |
| Fuse | G / 5 x 20 / 5 x 25 / 5 x 30 |
| Color | black (RAL 9005) |
| Width | 8.2 mm |
| Height | 72.5 mm |
| Result | Test passed |
| Spectrum | Service life test category 1, class B, body mounted |
| ASD level | 1.857 (m/s²)²/Hz |
| Frequency | f1= 5 Hz to f2= 150 Hz |
| Fuse type | Glass / ceramics / ... |
| Potentials | 1 |
| Pulse shape | Half-sine |
| Acceleration | 0.8g |
| Product type | Fuse terminal block |
| Screw thread | M3 |
| Mounting type | NS 35/7,5 |
| Specification | DIN EN 50155 (VDE 0115-200):2008-03 |
| Number of rows | 1 |
| Shock duration | 30 ms |
| Depth on NS 32 | 61.5 mm |
| Nominal current | 6.3 A |
| Nominal voltage | 24 V |
| Open side panel | No |
| Test directions | X-, Y- and Z-axis |
| Article revision | 12 |
| Stripping length | 8 mm |
| Cross section AWG | 24 ... 12 (converted acc. to IEC) |
| LED current range | 3.5 mA ... 8.1 mA |
| LED voltage range | 15 V AC/DC ... 30 V AC/DC |
| Tightening torque | 0.6 ... 0.8 Nm |
| Depth on NS 35/15 | 64 mm |
| Notes on operation | The current is determined by the fuse used, the voltage by the selected LED.If the fuse is faulty, the downstream circuit will not be disconnected. |
| Degree of pollution | 3 |
| Depth on NS 35/7,5 | 56.5 mm |
| Insulating material | PA |
| Number of positions | 1 |
| Rated surge voltage | 8 kV |
| Maximum load current | 6.3 A (the current is determined by the fuse used) |
| Overvoltage category | III |
| Nominal cross section | 4 mm² |
| Number of connections | 2 |
| Note regarding marking | For terminal marking, please use marking material with 8.2 mm pitch. |
| Test duration per axis | 5 h |
| Insulating material group | I |
| Internal cylindrical gage | A4 |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Ambient temperature (assembly) | -5 °C ... 70 °C |
| Number of shocks per direction | 3 |
| Ambient temperature (actuation) | -5 °C ... 70 °C |
| Ambient temperature (operation) | -60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) |
| Number of connections per level | 2 |
| Conductor cross section flexible | 0.2 mm² ... 4 mm² |
| Connection in acc. with standard | IEC 60947-7-3 |
| Permissible humidity (operation) | 20 % ... 90 % |
| Flammability rating according to UL 94 | V0 |
| Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
| Conductor cross section, flexible [AWG] | 24 ... 12 (converted acc. to IEC) |
| Permissible humidity (storage/transport) | 30 % ... 70 % |
| Cross-section with insertion bridge, rigid | 4 mm² |
| 2 conductors with same cross section, solid | 0.2 mm² ... 1.5 mm² |
| Cross-section with insertion bridge, flexible | 4 mm² |
| 2 conductors with same cross section, flexible | 0.2 mm² ... 1.5 mm² |
| Maximum power dissipation for nominal condition | 1.02 W |
| Flexible conductor cross section (ferrule with plastic sleeve) | 0.25 mm² ... 4 mm² |
| Relative insulation material temperature index (Elec., UL 746 B) | 125 °C |
| Conductor cross-section flexible (ferrule without plastic sleeve) | 0.25 mm² ... 4 mm² |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
| 2 conductors with same cross section, flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² |
| 2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve | 0.5 mm² ... 1.5 mm² |
Technical specifications and performance data
Installation and operation guide