| Parameter | Value |
|---|---|
| 2x 400 V AC ... 500 V AC ±10 % | |
| Color | red, yellow, green (multicolor LED) |
| Depth | 167 mm |
| I/O/S | asymmetrical |
| Input | asymmetrical 2 kV (Test Level 3) |
| Width | 90 mm |
| rigid | 0.2 mm² ... 4 mm² |
| Height | 135 mm |
| Output | asymmetrical 2 kV (Test Level 3) |
| Signal | asymmetrical 1 kV (Test Level 3) |
| LED off | Supply voltage input AC not present (Off) |
| Voltage | 10 V (Test Level 3) |
| Comments | Criterion B |
| Derating | 60 °C ... 70 °C |
| Function | Visual operating state display |
| Position | 3.x |
| flexible | 0.2 mm² ... 2.5 mm² |
| Frequency | 50 Hz |
| Rise time | ≤ 1 s (UOut= 10 % ... 90 %) |
| EN 61010-1 | III (≤ 2000 m) |
| Efficiency | typ. 95.44 % (3x 400 V AC) |
| Criterion A | Normal operating behavior within the specified limits. |
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
| Criterion C | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
| Voltage dip | 70 % |
| rigid (AWG) | 24 ... 12 (Cu) |
| Crest factor | typ. 1.549 (3x 400 V AC) |
| Hood version | Polycarbonate |
| Product type | Power supply |
| Mounting type | DIN rail mounting |
| No-load proof | yes |
| Identification | UL/C-UL Listed UL 61010-1 |
| Inrush current | < 21 A (25 °C) |
| Noise emission | EN 55016 |
| Noise immunity | Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial) |
| Product family | TRIO POWER |
| Additional text | Class 3 |
| EN 61010-2-201 | III (≤ 2000 m) |
| Frequency range | 0 kHz ... 2 kHz |
| Residual ripple | typ. 13 mVPP(with nominal values) |
| State condition | UOut> 21 V DC and IOutN (Contact closed) |
| Discharge in air | 8 kV (Test Level 3) |
| Maximum altitude | ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) |
| Number of phases | 3.00 |
| Position marking | 3.1 (13), 3.2 (14) |
| Protection class | I |
| Stripping length | 10 mm (rigid/flexible) |
| Connection method | Push-in connection |
| Contact discharge | 6 kV (Test Level 3) |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| Device mains fuse | 6.3 A internal (device protection) |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Number of periods | 25 periods |
| Output power (PN) | 960 W |
| Shock (operation) | 18 ms, 30g, per spatial direction (IEC 60068-2-27) |
| Switching voltage | max. 30 V DC (SELV) |
| Protective circuit | Transient protection; Varistor |
| Types of signaling | LED DC OK – signal state operation (UN= 24 V DC, IOut= IN) |
| Current consumption | 3x 1.5 A (3x 400 V AC) |
| Degree of pollution | 2 |
| Input voltage range | 3x 400 V AC ... 500 V AC -20 % ... +10 % |
| Short-circuit-proof | yes |
| Test field strength | 10 V/m (Test Level 3) |
| Connection in series | yes, for increased output voltage (observe SELV limit) |
| Degree of protection | IP20 |
| Frequency range (fN) | 50 Hz ... 60 Hz ±10 % |
| LED on (red), ISHORT | UOutOut > 0.9 x IN(On (red), ISHORT) |
| Mains buffering time | typ. 21 ms (3x 400 V AC) |
| Side element version | Aluminum |
| Standard designation | Safety of power supply units up to 1100 V (insulation distances) |
| Assembly instructions | alignable: 0 mm horizontally, 30 mm vertically |
| Interference emission | Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial) |
| LED on (green), DC OK | UOut> 21 V DC and IOutN (On (green), DC OK) |
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| Standards/regulations | EN 61000-3-2 |
| Vibration (operation) | 10 Hz ... 50 Hz, amplitude ±0.2 mm (IEC 60068-2-6) |
| Connection in parallel | yes, for increasing power and redundancy with diode |
| Nominal output voltage | 24 V DC |
| Power factor (cos phi) | 0.94 (3x 480 V AC) |
| Discharge current to PE | < 3.5 mA |
| Conducted noise emission | EN 55016 |
| Standards/specifications | DIN EN 61558-2-16 |
| Current carrying capacity | max. 100 mA |
| LED on (flashing red) OVP | UOUT> OVP (Over voltage protection) (On (flashing red)) |
| Switch contact (floating) | OptoMOS |
| Dynamic Boost (IDyn.Boost) | max. 60 A (5 s) |
| Integrated fuse protection | no |
| MTBF (IEC 61709, SN 29500) | > 1200000 h (25 °C) |
| Output power (PDyn. Boost) | max. 1440 W (5 s) |
| Feedback voltage resistance | ≤ 35 V DC |
| LED on (yellow), IOut > 90% | UOut> 21 V DC and IOut> 0.9 x IN(On (yellow), IOut> 90% ) |
| Nominal input voltage range | 3x 400 V AC ... 500 V AC |
| Nominal output current (IN) | 40 A |
| Supply system configuration | Star network (TN, TT, IT (PE)) |
| Power loss nominal load max. | < 42.52 W (3x 480 V AC) |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Inrush current integral (I2t) | < 0.77 A2s |
| Typical national grid voltage | 3x 400 V AC |
| Voltage type of supply voltage | AC |
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
| Insulation voltage input/output | 4 kV AC (type test) |
| Installation distance right/left | 0 mm / 0 mm |
| Installation distance top/bottom | 50 mm / 50 mm |
| Maximum no-load power dissipation | < 0.77 W (3x 480 V AC) |
| Minimum no-load power dissipation | < 1.37 W (3x 400 V AC) |
| Environmental protection directive | RoHS Directive 2011/65/EU |
| Flammability rating according to UL 94 | V0 (Housing, terminal blocks) |
| Minimum nominal load power dissipation | < 45.75 W (3x 400 V AC) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Recommended breaker for input protection | 3x 6 A ... 16 A (Characteristic B, C, D, K or comparable) |
| flexible with ferrule with plastic sleeve | 0.25 mm² ... 1.5 mm² |
| Ambient temperature (start-up type tested) | -40 °C |
| Setting range of the output voltage (USet) | 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) |
| flexible with ferrule without plastic sleeve | 0.25 mm² ... 2.5 mm² |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Protection against overvoltage at the output (OVP) | ≤ 35 V DC |
Technical specifications and performance data
Installation and operation guide