| Parameter | Value |
|---|---|
| 1x 20 A (-25 °C ... 60 °C) | |
| LED | no |
| Depth | 115 mm |
| I/O/S | asymmetrical |
| Input | 2 kV (Test Level 3 - asymmetrical) |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Width | 35 mm |
| Height | 130 mm |
| Output | 2 kV (Test Level 3 - asymmetrical) |
| Voltage | 10 V (Test Level 3) |
| Comments | Criterion B |
| Derating | 60 °C ... 70 °C (2.5 %/K) |
| Efficiency | > 97 % |
| Criterion A | Normal operating behavior within the specified limits. |
| Product type | Redundancy module |
| Screw thread | M3 |
| UL approvals | UL/C-UL listed UL 508 |
| Assembly note | alignable: horizontally 0 mm, vertically 50 mm |
| Mounting type | DIN rail mounting |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Product family | TRIO DIODE |
| Frequency range | 80 MHz ... 1 GHz |
| Type of housing | Steel sheet, zinc-plated |
| Article revision | 04 |
| Discharge in air | 8 kV (Test Level 3) |
| Housing material | Metal |
| Protection class | III |
| Stripping length | 10 mm |
| Connection method | Push-in connection |
| Contact discharge | 4 kV (Test Level 3) |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Degree of pollution | 2 |
| Input voltage range | 10 V DC ... 30 V DC |
| Test field strength | 10 V/m |
| Connection in series | no |
| Degree of protection | IP20 |
| Maximum current Imax | 2x 15 A (-25 °C ... 40 °C) |
| Side element version | Aluminum |
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| Standards/regulations | EN 61000-4-2 |
| Tightening torque max | 0.6 Nm |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| Nominal output voltage | UIn- 0,5 V |
| Tightening torque, min | 0.5 Nm |
| MTBF (IEC 61709, SN 29500) | 66425178 h (25 °C) |
| Nominal input current (IN) | 2x 10 A (-25 °C ... 60 °C) |
| Transient surge protection | Varistor |
| Voltage drop, input/output | 0.5 V |
| Nominal input voltage range | 12 V DC ... 24 V DC |
| Nominal output current (IN) | 20 A |
| Reverse polarity protection | < yes60 V |
| Power loss nominal load max. | 5 W (IOUT= 10 A) |
| Standard - Electrical safety | IEC 62368-1 (SELV) |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Voltage type of supply voltage | DC |
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
| Conductor cross section AWG max. | 12 |
| Conductor cross section AWG min. | 16 |
| Installation distance right/left | 0 mm / 0 mm |
| Installation distance top/bottom | 50 mm / 50 mm |
| Conductor cross section, rigid max. | 4 mm² |
| Conductor cross section, rigid min. | 0.2 mm² |
| EMC requirements for noise emission | EN 61000-6-3 |
| EMC requirements for noise immunity | EN 61000-6-1 |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Standard – Safety extra-low voltage | IEC 62368-1 (SELV) und EN 60204-1 (PELV) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Insulation voltage input, output / housing | 500 V |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
| Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
| Flammability rating according to UL 94 (housing / terminal blocks) | V0 |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Technical specifications and performance data