| Parameter | Value |
|---|---|
| typ. 92 % (240 V AC) | |
| Depth | 160 mm |
| Input | 4 kV |
| Shock | 30g, 18 ms in accordance with IEC 60068-2-27 |
| Width | 88 mm |
| rigid | 1 mm² ... 4 mm² |
| Height | 130 mm |
| Output | 2 kV |
| Signal | 2 kV |
| Locking | Screw |
| Voltage | 10 V |
| Derating | > 60 °C (2.5%/K of POutnom.) |
| flexible | 1 mm² ... 2.5 mm² |
| Interface | USB (Modbus/RTU) |
| Rise time | < 34 ms |
| EN 61010-1 | II |
| Efficiency | typ. 88 % (100 V AC) |
| Input fuse | 10 A (slow-blow, internal) |
| Low signal | Connection to SGnd with < 2.7 kΩ |
| High signal | Open (> 200 kΩ between Bat.-Start and SGnd) |
| rigid (AWG) | 16 ... 12 |
| Crest factor | 1.57 (120 V AC) |
| Hood version | PC |
| Product type | DC UPS with integrated power supply |
| Mounting type | DIN rail mounting |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Identification | UL Listed UL 61010 |
| Inrush current | < 10 A |
| Noise emission | EN 61000-6-3 |
| Noise immunity | Immunity in accordance with EN 61000-6-2 (industrial) |
| Output voltage | 24 V DC |
| Product family | TRIO UPS |
| Switch-on time | typ. 200 ms |
| Frequency range | 80 MHz ... 6 GHz |
| Residual ripple | < 20 mV |
| Discharge in air | 8 kV (Test Level 3) |
| Maximum altitude | ≤ 4000 m (> 2000 m, observe derating) |
| Number of phases | 1.00 |
| Protection class | I |
| Stripping length | 10 mm |
| Switch-over time | < 3 ms |
| Switching output | Transistor output, active |
| Connection method | Push-in connection |
| Contact discharge | 6 kV (Test Level 3) |
| Control deviation | < 0.4 % (change in load, static 10 % ... 90 %) |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Output current IN | 20 A |
| Type of signaling | LED red |
| Battery technology | VRLA-AGM |
| Nominal voltage UN | 24 V DC |
| Charging current () | 3 A |
| Connection labeling | 3.6 |
| Degree of pollution | 2 |
| Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
| Test field strength | 10 V/m |
| Degree of protection | IP20 |
| Frequency range (fN) | 50 Hz ... 60 Hz (±10 %) |
| LED status indicator | red |
| Mains buffering time | ≥ 20 ms (120 V AC) |
| Number of interfaces | 1 |
| Output voltage range | 24 V DC ... 28 V DC (> 24 V constant capacity) |
| Side element version | Aluminum |
| Standard designation | Safety for equipment for measurement, control, and laboratory use |
| Assembly instructions | alignable: horizontally 0 mm, vertically 50 mm |
| End-of-charge voltage | max. 30 V DC |
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| Standards/regulations | EN 61000-3-2 |
| Vibration (operation) | in accordance with IEC 60068-2-6 |
| Nominal capacity range | 4 Ah ... 40 Ah |
| Continuous load current | 20 mA |
| Permissible backup fuse | B16 |
| Conducted noise emission | EN 61000-6-3 |
| Standards/specifications | IEC 61010-1 |
| UPS connection in series | no |
| Charging current (Preset) | 2.1 A (-25 °C ... 40 °C) |
| Signalization designation | Bat.-Start |
| Charging current (Reduced) | 3 A ... 0 A (40 °C ... 65 °C) |
| Dynamic Boost (IDyn.Boost) | 30 A |
| MTBF (IEC 61709, SN 29500) | 958219 h (25 °C) |
| UPS connection in parallel | yes, with diode module uncoupled |
| Charge characteristic curve | IU0U |
| Feedback voltage resistance | ≤ 35 V DC |
| Typical current consumption | 6.4 A (100 V AC) |
| Power loss nominal load max. | < 50 W (230 V AC) |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Inrush current integral (I2t) | < 0.4 A2s |
| Voltage type of supply voltage | AC |
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
| Charging current (Configurable) | 0.2 A ... 3 A (-25 °C ... 40 °C) |
| Installation distance right/left | 0 mm / 0 mm |
| Installation distance top/bottom | 50 mm / 50 mm |
| Maximum no-load power dissipation | < 4 W (230 V AC) |
| EMC requirements for noise emission | EN 61000-6-3 |
| EMC requirements for noise immunity | EN 61000-6-1 |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| flexible with ferrule with plastic sleeve | 1 mm² ... 1.5 mm² |
| Ambient temperature (start-up type tested) | -40 °C |
| Energy storage device connection in parallel | yes |
| flexible with ferrule without plastic sleeve | 1 mm² ... 2.5 mm² |
| Max. permissible relative humidity (operation) | ≤ 95 % (At +25°C, non-condensing) |
| Protection against overvoltage at the output (OVP) | < 30 V DC |
| Flammability rating according to UL 94 (housing / terminal blocks) | V0 |
Technical specifications and performance data