| Parameter | Value |
|---|---|
| 230 V AC | |
| Exit | 2 kV (Test Severity 3, Asymmetric) |
| AC OK | AcIn> 0.45 x ACN(ACN= 108 V AC) |
| Crash | 18 ms, 30g, per direction in space (according to IEC 60068-2-27) |
| DC OK | UOUT> 0.9 x UN(UN= 24 V DC) |
| Depth | 53 mm |
| Width | 136 mm |
| Yield | Typ. 90% (120 V AC) |
| Colour | green |
| Height | 240 mm |
| Marked | UL/C-UL Listed UL 61010-1 |
| Signal | 2 kV (Test Severity 3, Asymmetric) |
| Default | closed |
| Digital | 30 V AC 30 V DC 100 mA |
| tension | 10 V (Test Severity 3) |
| Derating | > 40 °C ... 50 °C (1%/K) |
| Diameter | 5.6 mm |
| entrance | 4 kV (Test Severity 3, Asymmetric) |
| Lock Type | M12 Screw Lock |
| frequency | 50 Hz |
| EN 61010-1 | III (≤ 2000 m) |
| Inlet fuse | 6.3 A (internal (device protection)) |
| Ascent Time | ≤ 12 ms (UOUT(10 % ... 90 %)) |
| Criterion A | Normal service behavior within the specified limits. |
| Criterion B | Transient alteration of service behavior, which is corrected by the device itself. |
| Criterion C | Temporary adverse effects on performance that are automatically corrected by the equipment or that can be reset by operating the control elements. |
| Observation | Criterion A |
| Codification | s |
| Input/Output | asymmetric |
| Output power | 240 W |
| Product Type | Power supply |
| Fixing height | ≤ 4000 m (> 2000 m, Derating: 10%/1000 m) |
| Voltage Error | 70 % |
| Weather Class | 4K26 (EN 60721-3-4) |
| Product Family | TRIO POWER |
| Connection Time | < 1 sec |
| Connection type | M12 Cylindrical Connector |
| Frequency Range | 80 MHz ... 1 GHz |
| Number of poles | 3 |
| Residual ripple | ≤ 10 mVPP |
| Type of signage | LED |
| Housing Material | Metal |
| Number of phases | 1,00 |
| Protection Index | IP67 |
| Rules/Provisions | IEC 61010-1 |
| Type of mounting | Wall Mounting |
| Dimming deviation | < 1% (static load change 10% ... 90 %) |
| Network Structure | Star Network (TN, TT, IT (PE)) |
| Number of periods | 25 periods |
| Operating Voltage | > 85 V AC |
| Status Indication | 2 x Green LED |
| AC Frequency Range | 50 Hz ... 60 Hz ±10% |
| Current absorption | 2.3 A (120 V AC) |
| Disconnect voltage | < 85 V AC |
| Kind of protection | I |
| Protection Circuit | Protection against transient overvoltages; Varistor |
| Degree of pollution | 3 |
| Designation Signage | AC OK |
| Download contact us | 6 kV (Test Severity 3) |
| Input Voltage Range | 120 V AC ... 240 V AC ±10% |
| Nominal power input | 285 VA |
| Vibration (service) | < 15 Hz, width ±2.5 mm (according to IEC 60068-2-6) |
| Frequency range (fN) | 50 Hz ... 60 Hz ±10% |
| Test Field Intensity | 10 V/m (Test Severity 3) |
| Interference emission | Interference emission in accordance with EN 61000-6-3 (residential and commercial areas) and EN 61000-6-4 (industrial areas) |
| Low Voltage Directive | Compliance with the Low Voltage Directive 2014/35/EU |
| Static boost derating | > 40 °C ... 50 °C 1 %/K> 50 ... 60 °C 0.22 %/K (UN 230 V AC, PStat.Boost= PNx 1:25) |
| With protective paint | No |
| Extra-current shut-off | ≤ 25 A (typical) |
| Nominal Output Voltage | 24 V DC ±1% |
| Interference resistance | Immunity to interference according to EN 61000-6-1 (domestic use), EN 61000-6-2 (industrial use) |
| Short circuit resistant | Yes |
| Denomination of standard | Electrical Safety |
| Recirculation Resistance | ≤ 35 V DC |
| Standards/Specifications | EN 61000-3-2 |
| Execution of the housings | Aluminum (AlMg3) |
| Ground Shunt Current (PE) | < 3.5 mA |
| Installation instructions | Stackable: horizontal 20 mm, vertical up 50 mm, vertical down 100 mm |
| Mounting Distance Up/Down | 50 mm / 100 mm |
| Rated Output Current (IN) | 10 A |
| Dynamic Boost (IDyn.Boost) | 15 A (5 sec) |
| MTBF (IEC 61709, SN 29500) | > 850000 h (25 °C) |
| Static Boost (IBoost est.) | 12.5 A (UN 230 V AC) |
| Maximum dielectric strength | ≤ 300 V AC 15 sec |
| Nominal Input Voltage Range | 120 V AC ... 240 V AC |
| Radiated spurious emissions | EN 55016 |
| Supply Voltage Voltage Type | AC |
| Parallel connection possible | Yes, for redundancy and power boost |
| Right/Left Mounting Distance | 20 mm / 20 mm |
| Typical Country Grid Voltage | 120 V AC |
| Ambient Temperature (Service) | -25 °C ... 60 °C |
| Electromagnetic compatibility | Compliance with EMC Directive 2014/30/EU |
| Inrush current integral (I2t) | < 0.5 A2s |
| Network Failure Bridging Time | > 17 ms (120 V AC) |
| Output Surge Protection (OVP) | ≤ 30 V DC |
| Maximum Rated Load Dissipation | < 25 W (120 V AC) |
| Input/Output Insulation Voltage | 3 kV AC (type test) |
| Maximum Open Circuit Dissipation | < 2 W (120 V AC) |
| Possibility of series connection | Yes |
| Emission of Conducted Interference | EN 55016 |
| Permissible air humidity (service) | ≤ 100% (at 25°C, non-condensing) |
| Shut-off current voltage limitation | Typ. 25 A (after 1 ms) |
| Ambient Temperature (Storage/Transport) | -40 °C ... 85 °C |
| Max. permissible air humidity (service) | ≤ 100% (at 25°C, non-condensing) |
| Radio interference according to EN 55011 | EN 55011 (EN 55022) Class B Application in industry and residential |
| Ambient temperature (Start-Up tested model) | -40 °C |
| Selecting the Right Fuse for Ingress Protection | 6 A ... 16 A (US/CAN: branch circuit protection |
| Radio interference voltage according to EN 55011 | EN 55011 (EN 55022) Class B Application in industry and residential |
| Flammability class according to UL 94 (housing/terminals) | V0 |
Technical specifications and performance data
Installation and operation guide