| Parameter | Value |
|---|---|
| GTIN | 4055626598703 |
| Orderkey | 1039830 |
| (Drawings) | |
| (Standards) | 2 kV (Test Level 1 - asymmetrical) |
| Catalog page | Page 264 (C-4-2019) |
| Packing unit | 1 |
| (Input data) | < 36 W (230 V AC) |
| (Output data) | > 400000 h (60 °C) |
| Coding (General) | S-coded |
| Depth (Drawings) | 120 mm |
| Width (Drawings) | 151 mm |
| ETIM 5.0 (eCl@ss) | EC002540 |
| ETIM 6.0 (eCl@ss) | EC002540 |
| ETIM 7.0 (eCl@ss) | EC002540 |
| Height (Drawings) | 304 mm |
| Input (Standards) | 3 kV (Test Level 3 - symmetrical) |
| Output (Standards) | 1 kV (Test Level 2 - symmetrical) |
| Signal (Standards) | 1 kV (Test Level 2 - asymmetrical) |
| Flicker (Standards) | EN 61000-3-3 |
| Voltage (Standards) | 230 V AC |
| Comments (Standards) | Criterion B |
| Custom tariff number | 85044030 |
| (Ambient conditions) | typ. 15 ms (230 V AC) |
| Derating (Input data) | > 60 °C ... 70 °C (2.5%/K) |
| Frequency (Standards) | 50 Hz |
| REACh SVHC (EMC data) | Lead 7439-92-1 |
| Criterion A (Standards) | Normal operating behavior within the specified limits. |
| Criterion B (Standards) | Temporary impairment to operational behavior that is corrected by the device itself. |
| Criterion C (Standards) | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
| Voltage dip (Standards) | 0 % |
| Efficiency (Output data) | 91 % (100 V AC) |
| Net weight (Output data) | 3.7 kg |
| Voltage dips (Standards) | EN 61000-4-11 |
| Output power (Input data) | 480 W |
| Type of locking (General) | M12 screw locking |
| Noise emission (Standards) | EN 55016 |
| Additional text (Standards) | Test Level 2 |
| Climatic class (Dimensions) | 3K3 (in acc. with EN 60721) |
| Connection method (General) | Circular connector |
| Frequency range (Standards) | 0.15 MHz ... 80 MHz |
| Discharge in air (Standards) | 8 kV (Test Level 4) |
| Residual ripple (Input data) | ≤ 30 mVPP |
| eCl@ss 8.0 (Classifications) | 27049002 |
| eCl@ss 9.0 (Classifications) | 27040701 |
| Contact discharge (Standards) | 6 kV (Test Level 4) |
| Number of periods (Standards) | 1 period |
| Number of positions (General) | 3 |
| Control deviation (Input data) | < 1 % (change in load, static 10 % ... 90 %) |
| Protection class (Output data) | I |
| Coding (Connection data, input) | N-coded |
| Input fuse (Ambient conditions) | 10 A (internal (device protection)) |
| Test field strength (Standards) | 10 V/m (Test Level 3) |
| Coding (Connection data, output) | A-coded |
| Degree of pollution (Dimensions) | 4 |
| Installation height (Dimensions) | ≤ 4000 m (> 2000 m, Derating: 10 %/1000 m) |
| Degree of protection (Dimensions) | IP67 |
| Low Voltage Directive (Standards) | Conformance with Low Voltage Directive 2014/35/EC |
| Conducted interference (Standards) | EN 61000-4-6 |
| Degree of protection (Output data) | IP67 |
| Typical response time (Input data) | < 1 s |
| Assembly instructions (Output data) | Alignable: 20 mm horizontally, 50 mm vertically above, 100 mm vertically below |
| Electrostatic discharge (Standards) | EN 61000-4-2 |
| Fast transients (burst) (Standards) | EN 61000-4-4 |
| Inrush current (Ambient conditions) | typ. 20 A (at 25 °C) |
| Nominal output voltage (Input data) | 24 V DC ±1 % |
| Conducted noise emission (Standards) | EN 55016 |
| Electromagnetic HF field (Standards) | EN 61000-4-3 |
| Surge voltage load (surge) (Standards) | EN 61000-4-5 |
| AC frequency range (Ambient conditions) | 50 Hz ... 60 Hz |
| Dynamic Boost (IDyn.Boost) (Input data) | 30 A (5 s) |
| Type of protection (Ambient conditions) | Transient surge protection |
| Current consumption (Ambient conditions) | 5.6 A (100 V AC) |
| Input voltage range (Ambient conditions) | 100 V AC ... 240 V AC 10 % |
| MTBF (IEC 61709, SN 29500) (Output data) | > 1400000 h (25 °C) |
| Nominal output current (IN) (Input data) | 20 A |
| Type of locking (Connection data, input) | M17 standard and SPEEDCON locking |
| Electromagnetic compatibility (Standards) | Conformance with EMC Directive 2014/30/EU |
| Mains buffering time (Ambient conditions) | typ. 10 ms (120 V AC) |
| Power loss nominal load max. (Input data) | < 48 W (120 V AC) |
| Type of locking (Connection data, output) | SPEEDCON M12 |
| Connection method (Connection data, input) | Circular connector |
| Connection method (Connection data, output) | Circular connector |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 85 °C (Derating >60°C: 2.5 %/K) |
| Discharge current to PE (Ambient conditions) | < 3.5 mA |
| Number of positions (Connection data, input) | 4 |
| Insulation voltage input/output (Output data) | 4 kV AC (type test) |
| Number of positions (Connection data, output) | 5 |
| Nominal power consumption (Ambient conditions) | 36.8 W |
| Dielectric strength maximum (Ambient conditions) | ≤ 300 V AC 15 s |
| Nominal input voltage range (Ambient conditions) | 100 V AC ... 240 V AC |
| Protective circuit/component (Ambient conditions) | Varistor |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Ambient temperature (start-up type tested) (Dimensions) | -40 °C |
| Standard - Safe isolation (Connection data for signaling) | DIN VDE 0100-410 |
| Max. permissible relative humidity (operation) (Dimensions) | ≤ 95 % (at 25 °C, non-condensing) |
| Maximum power dissipation in no-load condition (Input data) | < 3 W (120 V AC) |
| Standard - Electrical safety (Connection data for signaling) | IEC 61010-2-201 (SELV) |
| Recommended breaker for input protection (Ambient conditions) | 10 A ... 16 A (Characteristics B, C, D, K) |
| Protection against overvoltage at the output (OVP) (Input data) | ≤ 30 V DC |
| Standard – Safety extra-low voltage (Connection data for signaling) | EN 60204-1 (PELV) |
| Standard – Limitation of mains harmonic currents (Connection data for signaling) | EN 61000-3-2 |
Technical specifications and performance data
Installation and operation guide