| Parameter | Value |
|---|---|
| GTIN | 4046356960854 |
| Orderkey | 2903149 |
| Catalog page | Page 220 (C-4-2017) |
| Packing unit | 1 pc |
| (Input data) | |
| (Output data) | > 480000 h (60 °C) |
| Country of origin | CN (China) |
| Custom tariff number | 85044030 |
| (Ambient conditions) | typ. 20 ms (230 V AC) |
| Derating (Input data) | > 60 °C ... 70 °C (2.5%/K) |
| Efficiency (Output data) | > 91 % (for 230 V AC and nominal values) |
| Net weight (Output data) | 1 kg |
| Output power (Input data) | 240 W |
| Stripping length (General) | 10 mm |
| Climatic class (Dimensions) | 3K3 (in acc. with EN 60721) |
| Connection method (General) | Push-in connection |
| Depth (Key Commercial Data) | 160 mm |
| Width (Key Commercial Data) | 42 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 130 mm |
| Residual ripple (Input data) | < 10 mVPP(with nominal values) |
| Control deviation (Input data) | < 1 % (change in load, static 10 % ... 90 %) |
| Protection class (Output data) | I (in closed control cabinet) |
| Input fuse (Ambient conditions) | 6.3 A (internal (device protection)) |
| Mounting position (Output data) | horizontal DIN rail NS 35, EN 60715 |
| (Connection data for signaling) | 15 Hz ... 150 Hz, 4g, 90 min. |
| Degree of pollution (Dimensions) | 2 |
| Feedback resistance (Input data) | ≤ 35 V DC |
| Installation height (Dimensions) | ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) |
| Connection in series (Input data) | yes |
| Degree of protection (Dimensions) | IP20 |
| Degree of protection (Output data) | IP20 |
| Typical response time (Input data) | < 1 s |
| Assembly instructions (Output data) | alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm |
| Connection in parallel (Input data) | Yes, for redundancy and increased capacity |
| Nominal output voltage (Input data) | 24 V DC ±1 % |
| Mains buffering (Ambient conditions) | typ. 15 ms (120 V AC) |
| Weight per Piece (excluding packing) | 1,199.200 g |
| Shock (Connection data for signaling) | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 25; |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| AC frequency range (Ambient conditions) | 50 Hz ... 60 Hz ±10 % |
| Dynamic Boost (IDyn.Boost) (Input data) | 15 A (5 s) |
| Type of protection (Ambient conditions) | Transient surge protection |
| Voltage (Connection data for signaling) | 10 V (Test Level 3) |
| Comments (Connection data for signaling) | Criterion B |
| Current consumption (Ambient conditions) | 3.1 A (100 V AC) |
| Input voltage range (Ambient conditions) | 100 V AC ... 240 V AC -15 % ... +10 % |
| MTBF (IEC 61709, SN 29500) (Output data) | > 1800000 h (25 °C) |
| Nominal output current (IN) (Input data) | 10 A |
| Inrush surge current (Ambient conditions) | ≤ 25 A |
| Power loss nominal load max. (Input data) | < 25 W |
| Stripping length (Connection data, input) | 8 mm |
| Conductor cross section AWG max. (General) | 12 |
| Conductor cross section AWG min. (General) | 24 |
| Connection method (Connection data, input) | Push-in connection |
| Output overvoltage protection (Input data) | ≤ 30 V DC |
| Stripping length (Connection data, output) | 8 mm |
| Connection method (Connection data, output) | Push-in connection |
| Power factor (cos phi) (Ambient conditions) | 0.93 |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Conductor cross section solid max. (General) | 4 mm² |
| Conductor cross section solid min. (General) | 0.2 mm² |
| Discharge current to PE (Ambient conditions) | < 3.5 mA |
| UL approvals (Connection data for signaling) | UL Listed UL 508 |
| Insulation voltage input/output (Output data) | 3 kV AC (type test) |
| Noise emission (Connection data for signaling) | EN 55011 (EN 55022) |
| Noise immunity (Connection data for signaling) | EN 61000-6-2:2005 |
| Nominal power consumption (Ambient conditions) | 285 VA |
| Conductor cross section flexible max. (General) | 2.5 mm² |
| Conductor cross section flexible min. (General) | 0.2 mm² |
| Frequency range (Connection data for signaling) | 0.15 MHz ... 80 MHz |
| Dielectric strength maximum (Ambient conditions) | 300 V AC 15 s |
| Nominal input voltage range (Ambient conditions) | 100 V AC ... 240 V AC |
| Contact discharge (Connection data for signaling) | 4 kV (Test Level 2) |
| Protective circuit/component (Ambient conditions) | Varistor |
| Rail applications (Connection data for signaling) | EN 50121-4 |
| Test field strength (Connection data for signaling) | 3 V/m (Test Level 2) |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Low Voltage Directive (Connection data for signaling) | Conformance with LV directive 2006/95/EC |
| Standards/regulations (Connection data for signaling) | EN 61000-6-3 |
| Vibration (operation) (Connection data for signaling) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| Ambient temperature (start-up type tested) (Dimensions) | -40 °C |
| Setting range of the output voltage (USet) (Input data) | 24 V DC ... 28 V DC (constant capacity) |
| Choice of suitable circuit breakers (Ambient conditions) | 6 A ... 16 A (Characteristics B, C, D, K) |
| Conductor cross section AWG max. (Connection data, input) | 12 |
| Conductor cross section AWG min. (Connection data, input) | 24 |
| Standard - Safe isolation (Connection data for signaling) | DIN VDE 0100-410 |
| Conductor cross section AWG max. (Connection data, output) | 16 |
| Conductor cross section AWG min. (Connection data, output) | 24 |
| Conductor cross section solid max. (Connection data, input) | 4 mm² |
| Conductor cross section solid min. (Connection data, input) | 0.2 mm² |
| Max. permissible relative humidity (operation) (Dimensions) | ≤ 95 % (at 25 °C, non-condensing) |
| Maximum power dissipation in no-load condition (Input data) | < 5.1 W (230 V) |
| Conductor cross section solid max. (Connection data, output) | 1.5 mm² |
| Conductor cross section solid min. (Connection data, output) | 0.2 mm² |
| Standard - Electrical safety (Connection data for signaling) | IEC 60950-1/VDE 0805 (SELV) |
| Electromagnetic compatibility (Connection data for signaling) | Conformance with EMC Directive 2014/30/EU |
| Conductor cross section flexible max. (Connection data, input) | 2.5 mm² |
| Conductor cross section flexible min. (Connection data, input) | 0.2 mm² |
| Conductor cross section flexible max. (Connection data, output) | 1.5 mm² |
| Conductor cross section flexible min. (Connection data, output) | 0.2 mm² |
| Standard - Safety of transformers (Connection data for signaling) | EN 61558-2-16 (air clearances and creepage distances only) |
| Standard – Safety extra-low voltage (Connection data for signaling) | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
| Standard – Limitation of mains harmonic currents (Connection data for signaling) | EN 61000-3-2 |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations (Connection data for signaling) | EN 50178/VDE 0160 (PELV) |
Technical specifications and performance data