| Parameter | Value |
|---|---|
| GTIN | 4046356046657 |
| Orderkey | 2866323 |
| (Signaling) | 15 Hz ... 150 Hz, 2.3g, 90 min. |
| Catalog page | Page 175 (C-6-2013) |
| Packing unit | 1 pc |
| (Input data) | < 0.1 % (change in input voltage ±10 %) |
| (Output data) | 2 kV AC (routine test) |
| Country of origin | CN (China) |
| Shock (Signaling) | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Voltage (Signaling) | 10 V (Test Level 3) |
| Comments (Signaling) | Criterion B |
| Custom tariff number | 85044030 |
| (Ambient conditions) | > 24 ms (230 V AC) |
| Derating (Input data) | 55 °C ... 70 °C (2.5%/K) |
| Screw thread (General) | M2,5 |
| Efficiency (Output data) | 89 % (for 230 V AC and nominal values) |
| Net weight (Output data) | 1.4 kg |
| UL approvals (Signaling) | UL/C-UL listed UL 508 |
| Output power (Input data) | 240 W |
| Noise immunity (Signaling) | EN 61000-6-2:2005 |
| Stripping length (General) | 9 mm |
| Climatic class (Dimensions) | 3K3 (in acc. with EN 60721) |
| Connection method (General) | Screw connection |
| Depth (Key Commercial Data) | 152.5 mm |
| Frequency range (Signaling) | 0.15 MHz ... 80 MHz |
| Width (Key Commercial Data) | 60 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 130 mm |
| Residual ripple (Input data) | < 10 mVPP |
| Contact discharge (Signaling) | 4 kV (Test Level 2) |
| Control deviation (Input data) | < 1 % (change in load, static 10 % ... 90 %) |
| Protection class (Output data) | I (with PE connection) |
| Input fuse (Ambient conditions) | 6.3 A (slow-blow, internal) |
| Mounting position (Output data) | horizontal DIN rail NS 35, EN 60715 |
| Test field strength (Signaling) | 3 V/m |
| Degree of pollution (Dimensions) | 2 |
| Feedback resistance (Input data) | 35 V DC |
| Connection in series (Input data) | yes |
| Degree of protection (Dimensions) | IP20 |
| Low Voltage Directive (Signaling) | Conformance with LV directive 2006/95/EC |
| Max. capacitive load (Input data) | unlimited |
| Standards/regulations (Signaling) | EN 61000-4-11 |
| Vibration (operation) (Signaling) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| Degree of protection (Output data) | IP20 |
| Typical response time (Input data) | < 1 s |
| Assembly instructions (Output data) | alignable: horizontally 0 mm, vertically 50 mm |
| Connection in parallel (Input data) | Yes, for redundancy and increased capacity |
| Nominal output voltage (Input data) | 24 V DC ±1 % |
| Mains buffering (Ambient conditions) | > 24 ms (120 V AC) |
| Weight per Piece (excluding packing) | 1,400.000 g |
| Screw thread (Connection data, input) | M2,5 |
| Standard - Safe isolation (Signaling) | DIN VDE 0100-410 |
| Active current limitation (Input data) | Approx. 14 A (for short-circuit) |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 25; |
| AC frequency range (Ambient conditions) | 45 Hz ... 65 Hz |
| Operating voltage display (Output data) | Green LED |
| Type of protection (Ambient conditions) | Transient surge protection |
| Current consumption (Ambient conditions) | 3 A (100 V AC) |
| Input voltage range (Ambient conditions) | 85 V AC ... 264 V AC (Derating < 90 V AC: 2,5 %/V) |
| MTBF (IEC 61709, SN 29500) (Output data) | > 981000 h (40 °C) |
| Nominal output current (IN) (Input data) | 10 A (UOUT= 24 V DC) |
| Standard - Electrical safety (Signaling) | EN 60950-1/VDE 0805 (SELV) |
| Status display (Connection data, output) | "DC OK" LED green |
| Electromagnetic compatibility (Signaling) | Conformance with EMC Directive 2014/30/EU |
| Inrush surge current (Ambient conditions) | < 15 A |
| Power loss nominal load max. (Input data) | 30 W |
| Stripping length (Connection data, input) | 9 mm |
| Conductor cross section AWG max. (General) | 14 |
| Conductor cross section AWG min. (General) | 24 |
| Connection method (Connection data, input) | Screw connection |
| Output overvoltage protection (Input data) | < 35 V DC |
| Insulation voltage input / PE (Output data) | 2 kV AC (type test) |
| Power factor (cos phi) (Ambient conditions) | 0.99 |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 70 °C (> 55° C derating : 2.5%/K) |
| Conductor cross section solid max. (General) | 2.5 mm² |
| Conductor cross section solid min. (General) | 0.2 mm² |
| Connection in acc. with standard (Signaling) | CUL |
| Discharge current to PE (Ambient conditions) | < 3.5 mA |
| Insulation voltage output / PE (Output data) | 500 V DC (type test) |
| Insulation voltage input/output (Output data) | 4 kV AC (type test) |
| Nominal power consumption (Ambient conditions) | 272 VA |
| Conductor cross section flexible max. (General) | 2.5 mm² |
| Conductor cross section flexible min. (General) | 0.2 mm² |
| Dielectric strength maximum (Ambient conditions) | 300 V AC |
| Nominal input voltage range (Ambient conditions) | 100 V AC ... 240 V AC |
| Note on status display (Connection data, output) | UOUT< 0.9 x UN: LED flashing |
| Peak switching voltages nominal load (Input data) | < 50 mVPP |
| Protective circuit/component (Ambient conditions) | Varistor |
| Standard – Safety extra-low voltage (Signaling) | EN 60950-1 (SELV) |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Setting range of the output voltage (USet) (Input data) | 22.5 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted) |
| Choice of suitable circuit breakers (Ambient conditions) | 10 A ... 16 A (Characteristics B, C, D, K) |
| Conductor cross section AWG max. (Connection data, input) | 14 |
| Conductor cross section AWG min. (Connection data, input) | 24 |
| Conductor cross section solid max. (Connection data, input) | 2.5 mm² |
| Conductor cross section solid min. (Connection data, input) | 0.2 mm² |
| Max. permissible relative humidity (operation) (Dimensions) | ≤ 95 % (at 25 °C, non-condensing) |
| Maximum power dissipation in no-load condition (Input data) | 6.7 W |
| Conductor cross section flexible max. (Connection data, input) | 2.5 mm² |
| Conductor cross section flexible min. (Connection data, input) | 0.2 mm² |
| Standard – Limitation of mains harmonic currents (Signaling) | EN 61000-3-2 |
| Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment (Signaling) | EN 50178 |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations (Signaling) | EN 50178/VDE 0160 (PELV) |