Service time: Monday to Friday 9:00-18:00
TC-XC96-DO32-EX-HIMAX01 - TC-XC96-DO32-EX-HIMAX01 2908752 PHOENIX CONTACT Termination Carrier for connecting 32 MACX Analog Ex i solen..
In Stock Hot Product

TC-XC96-DO32-EX-HIMAX01

TC-XC96-DO32-EX-HIMAX01 2908752 PHOENIX CONTACT Termination Carrier for connecting 32 MACX Analog Ex i solen..

$0.00USD
4667 in stock
Key Specifications
:Class I, Div. 2, Groups A, B, C, D T4
Type:C
Depth:159.5 mm
Shock:15g, according to IEC 60068-2-27
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
Class I, Div. 2, Groups A, B, C, D T4
TypeC
Depth159.5 mm
Shock15g, according to IEC 60068-2-27
Width448 mm
Height170 mm
Altitude≤ 2000 m
EMC noteEMC: class A product, see manufacturer's declaration in the download area
InsulationFunctional insulation
CertificatePxCIF21UKEX2908752X
Product typeModule carrier
Assembly noteWith end bracket
Mounting typeDIN rail mounting
Identification II 3 G Ex ec IIC T4 Gc X
Article revision04
Pollution degree2
Connection methodPin strip
Mounting positionvertical, horizontal
Suitable I/O cardX-DO 32 01
Nominal voltage UN< 50 V DC (Per signal/channel)
Notes on operationFor proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met.
Number of positions96
Rated surge voltage0.5 kV
Degree of protectionIP20
Overvoltage categoryII
Number of connections1
Standards/regulationsEN 60664-1
Vibration (operation)2g, according to IEC 60068-2-6
Max. permissible current0.5 A (Signal/channel)
Rated insulation voltage30 V
Ambient temperature (operation)-20 °C ... 60 °C
Connection in acc. with standardIEC 60603-2
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Ambient temperature (storage/transport)-40 °C ... 80 °C

Product Description

Termination Carrier for the connection of 32 MACX Analog Ex-i valve control blocks to digital output cards of the HIMA-HIMax control system, via a 96-pole C96 connector. Suitable for HIMax X-DO 32 01
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top