| Parameter | Value |
|---|---|
| 3024481 ATP-ST 6 | |
| Color | red (RAL 3001) |
| Width | 6.2 mm |
| Height | 64.5 mm |
| output | (Permanent) |
| Potentials | 1 |
| Bridge data | 27 A / 4 mm² |
| Product type | Multi-conductor terminal block |
| Mounting type | NS 35/7,5 |
| Rated current | 30 A |
| Rated voltage | 550 V |
| Identification | II 2 G Ex eb IIC Gb |
| Number of rows | 1 |
| End cover width | 2.2 mm |
| List of bridges | Plug-in bridge / FBS 2-6 / 3030336 |
| Nominal current | 32 A (with 6 mm² conductor cross section) |
| Nominal voltage | 800 V |
| Open side panel | Yes |
| Article revision | 07 |
| Stripping length | 10 mm |
| Cross section AWG | 28 ... 10 (converted acc. to IEC) |
| Contact resistance | 0.75 mΩ |
| Depth on NS 35/15 | 50.5 mm |
| Depth on NS 35/7,5 | 43 mm |
| Insulating material | PA |
| Rated surge voltage | 8 kV |
| Maximum load current | 38 A (In the case of a 6 mm² conductor cross section, the maximum load current must not be exceeded by the total current of all connected conductors) |
| Overvoltage category | III |
| Nominal cross section | 4 mm² |
| Number of connections | 3 |
| Connection capacity AWG | 28 ... 10 |
| Ex temperature increase | 40 K (30 A / 4 mm²) |
| Rated cross section AWG | 12 |
| Ex-certified accessories | 3031704 D-STS 4 |
| Rated insulation voltage | 500 V |
| for bridging with bridge | 550 V |
| Connection capacity rigid | 0.08 mm² ... 6 mm² |
| Insulating material group | I |
| Internal cylindrical gage | A4 |
| - At cut-to-length bridging | 352 V |
| Operating temperature range | -60 °C ... 110 °C |
| Connection capacity flexible | 0.08 mm² ... 4 mm² |
| Conductor cross section rigid | 0.08 mm² ... 6 mm² |
| Ambient temperature (assembly) | -5 °C ... 70 °C |
| Ambient temperature (actuation) | -5 °C ... 70 °C () |
| Ambient temperature (operation) | -60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) |
| Number of connections per level | 3 |
| Conductor cross section flexible | 0.08 mm² ... 4 mm² |
| Connection in acc. with standard | IEC 60947-7-1 |
| Permissible humidity (operation) | 20 % ... 90 % |
| - At cut-to-length bridging with cover | 352 V |
| Flammability rating according to UL 94 | V0 |
| Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, no longer than 24 h, -60°C to +70°C) |
| Conductor cross section, flexible [AWG] | 28 ... 12 (converted acc. to IEC) |
| Permissible humidity (storage/transport) | 30 % ... 70 % |
| Maximum power dissipation for nominal condition | 1.02 W |
| - At cut-to-length bridging with partition plate | 550 V |
| - At bridging between non-adjacent terminal blocks | 352 V |
| Flexible conductor cross section (ferrule with plastic sleeve) | 0.14 mm² ... 4 mm² |
| Conductor cross-section flexible (ferrule without plastic sleeve) | 0.14 mm² ... 4 mm² |