| Parameter | Value |
|---|---|
| 25 min. (2 A) | |
| Depth | 61 mm |
| I/O/S | asymmetrical |
| Input | 2 kV (Test Level 3 - asymmetrical) |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Width | 108 mm |
| Height | 90 mm |
| Output | 2 kV (Test Level 3 - asymmetrical) |
| Signal | 2 kV (Test Level 4 - asymmetrical) |
| Voltage | 10 V (Test Level 3) |
| Comments | Criterion A |
| Derating | 35 °C ... 40 °C (5 %/K) |
| Efficiency | > 98 % (Mains operation, with charged energy storage) |
| Input fuse | 7 A (slow-blow, internal) |
| Criterion A | Normal operating behavior within the specified limits. |
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
| Output power | 72 W |
| Product type | DC UPS |
| Screw thread | M3 |
| UL approvals | UL Listed UL 508 |
| Assembly note | alignable: horizontally 0 mm, vertically 50 mm |
| Bridging time | 900 s |
| Buffer period | 50 min. (1 A) |
| IQ technology | no |
| Input voltage | 24 V DC |
| Memory medium | Lithium polymer |
| Mounting type | DIN rail mounting |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Status display | LED |
| Frequency range | 80 MHz ... 1 GHz |
| Type of housing | Plastic |
| Article revision | 03 |
| Charging current | 0.4 A |
| Discharge in air | 8 kV (Test Level 3) |
| Housing material | Polycarbonate |
| Nominal capacity | 1.4 Ah |
| Protection class | III |
| Stripping length | 6.5 mm |
| Connection method | Screw connection |
| Contact discharge | 6 kV (Test Level 3) |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Power dissipation | 0.6 W (Mains operation) |
| Battery technology | LIPO |
| Network management | No |
| Nominal voltage UN | 18.5 V DC |
| Output description | Transistor |
| Types of signaling | LED |
| Current consumption | 4.7 A |
| Degree of pollution | 2 |
| Foot latch material | POM (Polyoxymethylene) |
| Input voltage range | 22.5 V DC ... 29.5 V DC |
| Output current Imax | 4 A (0 °C ... 35 °C) |
| Test field strength | 10 V/m (Test Level 3) |
| Connection in series | no |
| Degree of protection | IP20 |
| Output current limit | In mains mode according to connected upstream current limiting device |
| Output voltage range | 22.5 V DC ... 29.5 V DC (UOut= UIn- 0.3 V DC) |
| POWER BOOST (IBoost) | 4 A (0 °C ... 35 °C) |
| End-of-charge voltage | 18.5 V DC ... 21 V DC |
| Standards/regulations | EN 61000-4-2 |
| Tightening torque max | 0.8 Nm |
| Typical response time | < 0.5 s |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| Fixed backup threshold | < 22.5 V |
| Nominal capacity range | 1.4 Ah |
| Nominal output voltage | 24 V DC |
| Note on status display | static on |
| Rotary selector switch | Service |
| Tightening torque, min | 0.6 Nm |
| Quality check of battery | yes, with each charge and cyclically once per month |
| Deep discharge protection | < 15 V DC |
| Signalization designation | Power In OK |
| MTBF (IEC 61709, SN 29500) | > 1401000 h (40 °C) |
| Variable connect threshold | 1 V / 1 s |
| Nominal input voltage range | 24 V DC |
| Nominal output current (IN) | 3 A (0 °C ... 40 °C) |
| Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Voltage type of supply voltage | DC |
| Ambient temperature (operation) | 0 °C ... 40 °C |
| Battery presence check (cyclic) | 60 s |
| Conductor cross section AWG max. | 12 |
| Conductor cross section AWG min. | 24 |
| Installation distance right/left | 0 mm / 0 mm |
| Installation distance top/bottom | 0 mm / 0 mm |
| Conductor cross section, rigid max. | 2.5 mm² |
| Conductor cross section, rigid min. | 0.2 mm² |
| EMC requirements for noise emission | EN 61000-6-3 |
| EMC requirements for noise immunity | EN 61000-6-1 |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Ambient temperature (storage/transport) | -20 °C ... 45 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
| Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Technical specifications and performance data
Installation and operation guide