| Parameter | Value |
|---|---|
| GTIN | 4017918077464 |
| Orderkey | 2823625 |
| (General) | DIN VDE 0160 (in relevant parts) |
| (Coil side) | 1500 VA (for 250 V AC) |
| Catalog page | Page 87 (IF-2005) |
| Packing unit | 10 pc |
| Country of origin | DE (Germany) |
| Custom tariff number | 85364190 |
| Contact type (Coil side) | Single contact, 1 N/O contact |
| Depth (Key Commercial Data) | 66.5 mm |
| Width (Key Commercial Data) | 14.6 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Contact material (Coil side) | AgNi |
| Height (Key Commercial Data) | 33 mm |
| Operating mode (Contact side) | 100% operating factor |
| Net weight (SAP) (Contact side) | 31.6 g |
| Standards/regulations (General) | DIN VDE 0110b, Gr. C for 250 V DC |
| Maximum inrush current (Coil side) | 8 A |
| Type of switch contact (Coil side) | Single contact |
| Weight per Piece (excluding packing) | 31.600 g |
| Maximum switching voltage (Coil side) | 250 V AC/DC |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Mechanical service life (Contact side) | approx. 2x 107cycles |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Limiting continuous current (Coil side) | 6 A |
| Protective circuit (Ambient conditions) | Bridge rectifier, varistor |
| Typical release time (Ambient conditions) | 11 ms (with DC) |
| Typical response time (Ambient conditions) | 7 ms (with DC) |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 50 °C |
| Nominal input voltage UN (Ambient conditions) | 24 V AC/DC |
| Operating voltage display (Ambient conditions) | yes |
| Typical input current at UN (Ambient conditions) | 21 mA |
| Interrupting rating (ohmic load) max. (Coil side) | 95 W (at 24 V DC) |
| Ambient temperature (storage/transport) (Dimensions) | -20 °C ... 70 °C |
| Test voltage relay winding/relay contact (Contact side) | 2.5 kV AC (50 Hz, 1 min.) |
| Input voltage range in reference to UN (Ambient conditions) | 0.8 ... 1.1 |
| Power dissipation for nominal condition (Ambient conditions) | 0.5 W |
Technical specifications and performance data