| Parameter | Value |
|---|---|
| GTIN | 4017918079079 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2903639 |
| Catalog page | Page 92 (IF-2005) |
| Packing unit | 10 pc |
| Country of origin | DE (Germany) |
| Custom tariff number | 85364190 |
| Surge current (Input data) | 35 A (t = 10 ms) |
| Depth (Key Commercial Data) | 66.5 mm |
| Output circuit (Input data) | 2-wire, floating |
| Width (Key Commercial Data) | 20.8 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 33 mm |
| Leakage current (Input data) | 5 mA (in off state - components with low minimum load and leakage currents on request.) |
| Max. load value (Input data) | 6 A2s (I2x t at t = 8.3 ms) |
| Min. load current (Input data) | 50 mA |
| Mounting position (Output data) | any |
| Standards/regulations (General) | DIN VDE 0110 |
| Output voltage range (Input data) | 24 V AC ... 280 V AC |
| Peak offstate voltage (Input data) | 600 V |
| Standards/regulations (Output data) | DIN VDE 0110 |
| Weight per Piece (excluding packing) | 53.900 g |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Test voltage input/output (Output data) | 2.5 kV AC |
| Type of protection (Ambient conditions) | Reverse polarity protection |
| Input voltage range (Ambient conditions) | 4 V DC ... 6 V DC |
| Limiting continuous current (Input data) | 3 A (see derating curve) |
| Protective circuit/component (Input data) | RC element |
| Typical response time (Ambient conditions) | switch-on time: Max. one half cycle - zero-voltage crossing |
| Typical turn-off time (Ambient conditions) | switch-off time Max. one half cycle - zero-current crossing |
| Transmission frequency (Ambient conditions) | 25 Hz |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 60 °C |
| Nominal input voltage UN (Ambient conditions) | 5 V DC |
| Operating voltage display (Ambient conditions) | Yellow LED |
| Typical input current at UN (Ambient conditions) | 10 mA |
| Protective circuit/component (Ambient conditions) | Polarity protection diode |
| Ambient temperature (storage/transport) (Dimensions) | -20 °C ... 70 °C |
| Input voltage range in reference to UN (Ambient conditions) | 0.8 ... 1.2 |
| Voltage drop at max. limiting continuous current (Input data) | 1.5 V |
| Switching threshold "0" signal in reference to UN (Ambient conditions) | ≤ 0.4 |
| Switching threshold "1" signal in reference to UN (Ambient conditions) | ≥ 0.8 |
Technical specifications and performance data
Installation and operation guide