| Parameter | Value |
|---|---|
| GTIN | 4017918079062 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2903613 |
| (General) | DIN VDE 0110 |
| Catalog page | Page 92 (IF-2005) |
| Packing unit | 10 pc |
| (Input data) | Surge protection |
| (Output data) | DIN VDE 0110 |
| Country of origin | DE (Germany) |
| Custom tariff number | 85364900 |
| Surge current (Input data) | 5 A (t = 1 s) |
| Depth (Key Commercial Data) | 66.5 mm |
| Output circuit (Input data) | 2-wire, floating |
| Width (Key Commercial Data) | 20.8 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 33 mm |
| Mounting position (Output data) | any |
| Standards/regulations (General) | IEC 60664 |
| Type of protection (Input data) | Reverse polarity protection |
| Output voltage range (Input data) | 12 V DC ... 60 V DC |
| Peak offstate voltage (Input data) | 70 V DC (Collector-emitter reverse voltage) |
| Standards/regulations (Output data) | IEC 60664 |
| Weight per Piece (excluding packing) | 55.000 g |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Test voltage input/output (Output data) | 2.5 kV AC |
| Input voltage range (Ambient conditions) | 96 V AC ... 144 V AC |
| Limiting continuous current (Input data) | 3 A (see derating curve) |
| Protective circuit/component (Input data) | Polarity protection diode |
| Typical response time (Ambient conditions) | 3 ms |
| Typical turn-off time (Ambient conditions) | 13 ms |
| Transmission frequency (Ambient conditions) | 10 Hz |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 60 °C |
| Nominal input voltage UN (Ambient conditions) | 120 V AC |
| Typical input current at UN (Ambient conditions) | 4 mA |
| Ambient temperature (storage/transport) (Dimensions) | -20 °C ... 70 °C |
| Input voltage range in reference to UN (Ambient conditions) | 0.8 ... 1.2 |
| Voltage drop at max. limiting continuous current (Input data) | 1.2 V |
| Switching threshold "0" signal in reference to UN (Ambient conditions) | ≤ 0.4 |
| Switching threshold "1" signal in reference to UN (Ambient conditions) | ≥ 0.8 |
Technical specifications and performance data