| Parameter | Value |
|---|---|
| 6 mm² / 1.4 kg | |
| Color | gray (RAL 7042) |
| Width | 8.2 mm |
| Height | 113 mm |
| Result | Test passed |
| Spectrum | Service life test category 2, bogie-mounted |
| ASD level | 6.12 (m/s²)²/Hz |
| Frequency | f1= 5 Hz to f2= 250 Hz |
| Potentials | 1 |
| Pulse shape | Half-sine |
| Revolutions | 135 |
| Acceleration | 3.12g |
| Product type | Test disconnect terminal block |
| Mounting type | NS 35/7,5 |
| Specification | DIN EN 50155 (VDE 0115-200):2018-05 |
| Number of rows | 1 |
| Rotation speed | 10 (+/- 2) rpm |
| Shock duration | 18 ms |
| End cover width | 2 mm |
| Nominal current | 41 A |
| Nominal voltage | 400 V |
| Open side panel | Yes |
| Test directions | X-, Y- and Z-axis |
| Article revision | 01 |
| Stripping length | 12 mm |
| Time of exposure | 30 s |
| Cross section AWG | 24 ... 8 (converted acc. to IEC) |
| Depth on NS 35/15 | 56.5 mm |
| Test socket torque | 0.6 |
| Degree of pollution | 3 |
| Depth on NS 35/7,5 | 49 mm |
| Insulating material | PA |
| Rated surge voltage | 6 kV |
| Test force setpoint | 5 N |
| Maximum load current | 45 A (with 10 mm² conductor cross section) |
| Overvoltage category | III |
| Nominal cross section | 6 mm² |
| Number of connections | 2 |
| Test voltage setpoint | 7.3 kV |
| Test duration per axis | 5 h |
| DIN rail/fixing support | NS 32/NS 35 |
| Insulating material group | I |
| Internal cylindrical gage | A5 |
| Conductor cross section rigid | 0.2 mm² ... 10 mm² |
| Ambient temperature (assembly) | -5 °C ... 70 °C |
| Conductor cross section/weight | 1 mm² / 0.4 kg |
| Number of shocks per direction | 3 |
| Ambient temperature (actuation) | -5 °C ... 70 °C |
| Ambient temperature (operation) | -60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) |
| Number of connections per level | 2 |
| Conductor cross section flexible | 0.2 mm² ... 6 mm² |
| Connection in acc. with standard | IEC 60947-7-1 |
| Permissible humidity (operation) | 20 % ... 90 % |
| Requirement temperature-rise test | Increase in temperature ≤ 45 K |
| Short-time withstand current 6 mm² | 0.72 kA |
| Flammability rating according to UL 94 | V0 |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
| Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
| Conductor cross section, flexible [AWG] | 24 ... 10 (converted acc. to IEC) |
| Permissible humidity (storage/transport) | 30 % ... 70 % |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| Static insulating material application in cold | -60 °C |
| Maximum power dissipation for nominal condition | 1.31 W |
| Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Flexible conductor cross section (ferrule with plastic sleeve) | 0.25 mm² ... 6 mm² |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Conductor cross-section flexible (ferrule without plastic sleeve) | 0.25 mm² ... 6 mm² |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
| 2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve | 0.5 mm² ... 1.5 mm² |
Technical specifications and performance data
Installation and operation guide