| Parameter | Value |
|---|---|
| GTIN | 4055626685182 |
| Orderkey | 1053596 |
| Packing unit | 1 |
| ETIM 4.0 (eCl@ss) | EC000816 |
| ETIM 5.0 (eCl@ss) | EC000268 |
| ETIM 6.0 (eCl@ss) | EC000268 |
| ETIM 7.0 (eCl@ss) | EC000268 |
| Custom tariff number | 85363090 |
| Weight (Cable entry) | 17.8 kg |
| eCl@ss 5.1 (Classifications) | 27371890 |
| eCl@ss 7.0 (Classifications) | 27142422 |
| eCl@ss 8.0 (Classifications) | 27142422 |
| eCl@ss 9.0 (Classifications) | 27142422 |
| Impact strength (Cable entry) | IK10 |
| Protection class (Cable entry) | II |
| String fuse (System parameter) | 10:3 x 38 mm in scope of delivery |
| eCl@ss 10.0.1 (Classifications) | 27142422 |
| Degree of protection (Cable entry) | IP65 |
| Installation location (Cable entry) | Outdoor installation, roofed area, no direct sunlight |
| System voltage (Key Commercial Data) | 1000 V DC (Umax) |
| Protection level Up (System parameter) | ≤ 3.7 kV |
| Sealing area output (Safety equipment) | 16 mm ... 28 mm |
| Type of cable entry (Safety equipment) | Cable gland |
| Number of outputs (Key Commercial Data) | 1 (per MPP tracker) |
| Switching capacity (Key Commercial Data) | 250 A |
| Sealing area grounding (Safety equipment) | 6 mm ... 13 mm |
| IEC test classification (System parameter) | PV II |
| Surge protective device (System parameter) | T2 |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 45 °C |
| Sealing area string input (Safety equipment) | 5 mm ... 7 mm |
| Cable cross section output (Safety equipment) | 120 mm² |
| Number of string inputs (Key Commercial Data) | 16 |
| Standards/specifications (Ambient conditions) | IEC 61439-2 |
| Current per string (max.) (Key Commercial Data) | 12.5 A (Imax, with limited temperature range) |
| Cable cross section grounding (Safety equipment) | 6 mm² |
| Current per string (typical) (Key Commercial Data) | 9 A (Inc) |
| Bolt diameter output (cable lug) (Safety equipment) | 10 mm |
| Cable cross section string input (Safety equipment) | 4 mm² ... 6 mm² |
| Outer dimensions: width, height, depth (General data) | 500 mm x 600 mm x 230 mm (Housing dimensions) |
| Number of supported MPP trackers (Key Commercial Data) | (not relevant) |
| Total discharge current Itotal(8/20) µs (System parameter) | 40 kA |
Technical specifications and performance data