| Parameter | Value |
|---|---|
| GTIN | 4055626939568 |
| (Cable) | No hazardous substances above threshold values |
| Orderkey | 1097612 |
| (General) | -5 °C ... 80 °C (for flexible installation) |
| (Drawings) | Unused slots are to be sealed off prior to commissioning. Suitable sealing elements are to be found under "Accessories". |
| Packing unit | 1 pc |
| Note (Drawings) | NOTE: Observe the permissible bending radii when laying conductors, since the degree of protection may be put in jeopardy if the bending forces are too high. Alleviate mechanical loads upstream of the connector, e.g. by using cable ties. |
| Country of origin | DE (Germany) |
| ETIM 6.0 (eCl@ss) | EC002585 |
| ETIM 7.0 (eCl@ss) | EC002585 |
| China RoHS (Cable) | Environmentally friendly use period: unlimited = EFUP-e |
| Custom tariff number | 85444290 |
| (Ambient conditions) | Status display I/O Yellow LED |
| (Insulation material) | 1-8 / 5 (PE) = GN/YE |
| Minimum order quantity | 25 pc |
| Rated voltage (Drawings) | 24 V DC |
| Number of slots (Drawings) | 8 |
| (Standards and Regulations) | -5 °C ... 80 °C (cable, flexible installation) |
| eCl@ss 9.0 (Classifications) | 27440108 |
| Degree of protection (General) | IP65 |
| Dimensional drawing (Drawings) | |
| Number of positions (Drawings) | 5 |
| Total rated current (Drawings) | 12 A |
| Weight per Piece (excluding packing) | 0.000 g |
| Cable type (Standards and Regulations) | PUR/PVC black |
| Local diagnostics (Ambient conditions) | Supply voltage Green LED |
| Max. operating voltage Umax (Drawings) | 30 V DC |
| Wire colors (Standards and Regulations) | brown, blue, green/yellow, white, green, yellow, gray, pink, red, black, violet, gray/pink, red/blue, white/green, brown/green, white/yellow, yellow/brown, white/gray, gray/brown |
| Cable weight (Standards and Regulations) | 183.7 kg/km |
| UL AWM style (Standards and Regulations) | 20549 (80°C/300 V) |
| Ambient temperature (operation) (General) | -25 °C ... 80 °C |
| Overall twist (Standards and Regulations) | Wires twisted in layers |
| Standards/specifications (Pin assignment) | M12 connector IEC 61076-2-101 |
| AWG signal line (Standards and Regulations) | 20 |
| Traversing path (Standards and Regulations) | 2 m |
| Traversing rate (Standards and Regulations) | 2 m/s |
| AWG power supply (Standards and Regulations) | 17 |
| Flame resistance (Standards and Regulations) | according to DIN EN 50265 |
| Length of cable (Local diagnostics function) | 1.5 m |
| Other resistance (Standards and Regulations) | Highly resistant to acids, alkaline solutions and solvents |
| Sensor/actuator connection system (Drawings) | M12-SPEEDCON-socket |
| Current carrying capacity per slot (Drawings) | 4 A |
| Resistance to oil (Standards and Regulations) | according to VDE 0472 Part 803 |
| Cable abbreviation (Standards and Regulations) | LiYY11Y-HF |
| Conductor material (Standards and Regulations) | Bare Cu litz wires |
| Connection method (Local diagnostics function) | Fixed connection |
| O-ring material (Master cable connection data) | NBR |
| Special properties (Standards and Regulations) | Silicone-free |
| Contact material (Master cable connection data) | Cu alloy |
| Housing material (Master cable connection data) | PBT |
| Test voltage, cable (Standards and Regulations) | 2000 V |
| Flammability rating according to UL 94 (Drawings) | V0 |
| External sheath, color (Standards and Regulations) | black RAL 9005 |
| Inner sheath thickness (Standards and Regulations) | ≥ 0.15 mm |
| Material, inner sheath (Standards and Regulations) | PVC |
| Nominal voltage, cable (Standards and Regulations) | 300 V |
| Outer sheath thickness (Standards and Regulations) | ≥ 0.76 mm |
| Outer sheath, material (Standards and Regulations) | PUR |
| Conductor cross section (Standards and Regulations) | 16x 0.5 mm² (Signal line) |
| Current carrying capacity per I/O signal (Drawings) | 2 A |
| Number of bending cycles (Standards and Regulations) | 1500000 |
| Schematic diagramM12 slot, socket, 5-pos. (Drawings) | |
| Cable type (abbreviation) (Standards and Regulations) | PUR |
| External cable diameter D (Standards and Regulations) | 10.5 mm ±0.2 mm |
| Contact carrier material (Master cable connection data) | PA |
| Contact surface material (Master cable connection data) | gold-plated |
| Flammability rating according to UL 94 (Pin assignment) | V0 |
| Material conductor insulation (Standards and Regulations) | PVC |
| Material of threaded sleeve (Master cable connection data) | PBT |
| Ambient temperature (operation) (Standards and Regulations) | -40 °C ... 90 °C (cable, fixed installation) |
| Conductor structure signal line (Standards and Regulations) | 28x 0.15 mm |
| Material of the moulding mass (Master cable connection data) | PUR |
| Core diameter including insulation (Standards and Regulations) | 1.5 mm ±0.1 mm (Signal line) |
| Slot/position = Wire color or connection (Insulation material) | 1 / 4 (A) = WH |
| Conductor structure, voltage supply (Standards and Regulations) | 56x 0.15 mm |
| Minimum bending radius, fixed installation (Standards and Regulations) | 7.5 x D |
| Minimum bending radius, flexible installation (Standards and Regulations) | 10 x D |
| Tightening torque slot sensor/actuator cable (Local diagnostics function) | 0.4 Nm |
| Minimum bending radius, drag chain applications (Standards and Regulations) | 10 x D |
| Tightening torque of mounting screw for fixing the housing (Local diagnostics function) | 0.5 Nm |
Technical specifications and performance data