| Parameter | Value |
|---|---|
| 120 V DC | |
| LED | no |
| Width | 54 mm |
| Coding | A |
| Height | 42 mm |
| Length | 123 mm |
| General | When connecting the signal lines to the black PCB terminal blocks, please use a 0.4 x 2.0 mm screwdriver.The black PCB terminal blocks only require a minimal amount of operating force.Screwdriver: SZS 0,4X2,0 - 1205202Using larger screwdrivers or excessive force may damage the PCB terminal blocks.When using ferrules, the wires can be inserted straight into the PCB terminal blocks without opening the clamping area. |
| Application | Standard |
| Product type | Distributor box |
| Assembly note | NOTE:Observe the permissible bending radii when routing cables, since the degree of protection may be at risk if the bending forces are too high. Reduce mechanical loads upstream of the connector, e.g., by using cable ties. |
| Number of slots | 6 |
| Contact material | Cu alloy |
| Material Housing | PBT |
| Connection method | Spring-cage connection |
| Nominal voltage UN | 120 V AC |
| Dimensional drawing | |
| Note on application | Unused slots are to be sealed off prior to commissioning. Suitable sealing elements are to be found under "Accessories". |
| Number of positions | 4 |
| Degree of protection | IP65 |
| Rated current, total | 12 A |
| Seal material O-ring | NBR |
| Standard designation | M12 connector |
| Status display present | No |
| External cable diameter | 7 mm ... 12 mm |
| Contact carrier material | PA |
| Contact surface material | gold-plated |
| Material Threaded sleeve | PBT |
| Standards/specifications | IEC 61076-2-101 |
| Material Molding compound | PUR |
| Stripping length Signal line | 6 mm |
| Tightening torque, union nut | 2.5 Nm |
| Stripping length Power supply | 10 mm |
| Stripping length of the sheath | 50 mm (Master cable) |
| Tightening torque, cover screw | 1 Nm |
| Ambient temperature (operation) | -25 °C ... 80 °C |
| Sensor/actuator connection system | M12-SPEEDCON-socket |
| Current carrying capacity per slot | 4 A |
| Flammability rating according to UL 94 | V0 |
| Max. current carrying capacity per path | 2 A |
| Slot/position = Wire color or connection | 1 / 4 (A) = WH |
| Conductor cross section Flexible signal line | 0.2 mm² ... 0.5 mm² |
| Tightening torque slot sensor/actuator cable | 0.4 Nm |
| Conductor cross section Flexible power supply | 0.2 mm² ... 1.5 mm² |
| Connection cross section AWG Flexible signal line | 24 ... 20 |
| Connection cross section AWG Flexible power supply | 24 ... 16 |
| Tightening torque of mounting screw for fixing the housing | 0.5 Nm |