| Parameter | Value |
|---|---|
| GTIN | 4046356989824 |
| Orderkey | 1413147 |
| Packing unit | 1 |
| (Dimensions) | -5 °C ... 75 °C (cable, flexible installation) |
| (PROFIBUS [910]) | -25 °C ... 80 °C (cable, flexible installation) |
| ETIM 5.0 (eCl@ss) | EC002062 |
| ETIM 6.0 (eCl@ss) | EC002925 |
| ETIM 7.0 (eCl@ss) | EC002925 |
| UNSPSC 13.2 (ETIM) | 31251501 |
| Custom tariff number | 85444290 |
| (Ambient conditions) | 60 V DC |
| Cable type (PROFIBUS [910]) | PUR halogen-free black |
| (Standards and Regulations) | ≤ 70 °C (cable, drag chain applications) |
| Wire colors (PROFIBUS [910]) | brown, blue, black |
| eCl@ss 5.1 (Classifications) | 27061800 |
| eCl@ss 6.0 (Classifications) | 27279200 |
| eCl@ss 7.0 (Classifications) | 27440104 |
| eCl@ss 8.0 (Classifications) | 27440104 |
| eCl@ss 9.0 (Classifications) | 27440106 |
| Acceleration (PROFIBUS [910]) | 10 m/s² |
| Cable weight (PROFIBUS [910]) | 23 kg/km |
| Halogen-free (PROFIBUS [910]) | in accordance with DIN VDE 0472 part 815 |
| UL AWM style (PROFIBUS [910]) | 20549 |
| Overall twist (PROFIBUS [910]) | 3 wires, twisted |
| (PUR halogen-free black [PUR]) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Bending radius (PROFIBUS [910]) | 44 mm |
| AWG signal line (PROFIBUS [910]) | 22 |
| Traversing path (PROFIBUS [910]) | 10 m |
| Traversing rate (PROFIBUS [910]) | 3 m/s |
| Flame resistance (PROFIBUS [910]) | in accordance with UL 758/1581 FT2 |
| Other resistance (PROFIBUS [910]) | Highly resistant to acids, alkaline solutions and solvents |
| Rated voltage (Ambient conditions) | 48 V AC |
| Resistance to oil (PROFIBUS [910]) | in accordance with DIN EN 60811-2-1 |
| Conductor material (PROFIBUS [910]) | Bare Cu litz wires |
| Special properties (PROFIBUS [910]) | Flexible cable conduit capable |
| Standard designation (General data) | M12 connector |
| Standards/regulations (General data) | IEC 61076-2-101 |
| Test voltage, cable (PROFIBUS [910]) | ≥ 3000 V |
| Conductor resistance (PROFIBUS [910]) | max. 58 Ω/km (at 20 °C) |
| Contact material (Ambient conditions) | CuSn |
| Length of cable (Key Commercial Data) | 0.5 m |
| Shielding (Standards and Regulations) | Plastic-coated aluminum foil, tinned copper braided shield |
| Cable type (Standards and Regulations) | PROFIBUS |
| Insulation resistance (PROFIBUS [910]) | ≥ 100 GΩ*km (at 20 °C) |
| Thickness, insulation (PROFIBUS [910]) | ≥ 0.21 mm (Core insulation) |
| Attenuation (Standards and Regulations) | ≤ 0.049 dB/m (at 16 MHz) |
| External sheath, color (PROFIBUS [910]) | black-gray RAL 7021 |
| Nominal voltage, cable (PROFIBUS [910]) | ≤ 300 V |
| Outer sheath, material (PROFIBUS [910]) | PUR |
| Wire colors (Standards and Regulations) | Red, green |
| Acceleration (Standards and Regulations) | 3 m/s² |
| Cable weight (Standards and Regulations) | 90 kg/km |
| Conductor cross section (PROFIBUS [910]) | 3x 0.34 mm² (Signal line) |
| Degree of pollution (Ambient conditions) | 3 |
| Halogen-free (Standards and Regulations) | in accordance with DIN VDE 0472 part 815 |
| Number of positions (Ambient conditions) | 4 |
| UL AWM style (Standards and Regulations) | 21198 (80°C/300 V) |
| China RoHS (PUR halogen-free black [PUR]) | Environmentally Friendly Use Period = 50 |
| Number of bending cycles (PROFIBUS [910]) | 10000000 |
| Overall twist (Standards and Regulations) | 2 cores with 2 fillers to the core |
| Overvoltage category (Ambient conditions) | II |
| REACh SVHC (PUR halogen-free black [PUR]) | Lead 7439-92-1 |
| Bending radius (Standards and Regulations) | 65 mm |
| Cable capacity (Standards and Regulations) | nom. 30 pF/m |
| Cable type (abbreviation) (PROFIBUS [910]) | PUR |
| External cable diameter D (PROFIBUS [910]) | 3.85 mm ±0.15 mm |
| Standards/regulations (Ambient conditions) | M12 connector IEC 61076-2-101 |
| Wave impedance (Standards and Regulations) | 150 Ω ±10 % (3 MHz ... 20 MHz) |
| AWG signal line (Standards and Regulations) | 24 |
| Cable structure (Standards and Regulations) | 1x2xAWG24/19 |
| Rated current at 40°C (Ambient conditions) | 4 A |
| Traversing path (Standards and Regulations) | 4.5 m |
| Traversing rate (Standards and Regulations) | 3 m/s |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 90 °C (Plug / socket) |
| Flame resistance (Standards and Regulations) | UL 1581, Sec. 1060 (FT-1) |
| Material, filler (Standards and Regulations) | PP |
| Other resistance (Standards and Regulations) | Low adhesion |
| Contact carrier material (Ambient conditions) | TPU GF |
| Contact surface material (Ambient conditions) | Ni/Au |
| Conductor material (Standards and Regulations) | Tin-plated Cu litz wires |
| Material conductor insulation (PROFIBUS [910]) | PP |
| Ambient temperature (operation) (PROFIBUS [910]) | -40 °C ... 80 °C (cable, fixed installation) |
| Conductor resistance (Standards and Regulations) | ≤ 78.6 Ω/km |
| Conductor structure signal line (PROFIBUS [910]) | 42x 0.10 mm |
| Signal type/category (Standards and Regulations) | PROFIBUS |
| Insulation resistance (Standards and Regulations) | ≥ 5 GΩ*km |
| External sheath, color (Standards and Regulations) | violet RAL 4001 |
| Nominal voltage, cable (Standards and Regulations) | 30 V |
| Outer sheath, material (Standards and Regulations) | PUR |
| Test voltage Core/Core (Standards and Regulations) | 1500 V (50 Hz, 1 min.) |
| Conductor cross section (Standards and Regulations) | 2x 0.25 mm² (Signal line) |
| Core diameter including insulation (PROFIBUS [910]) | 1.27 mm ±0.02 mm (Signal line) |
| Optical shield covering (Standards and Regulations) | 85 % |
| Number of bending cycles (Standards and Regulations) | 4000000 |
| Test voltage Core/Shield (Standards and Regulations) | 1500 V (50 Hz, 1 min.) |
| Cable type (abbreviation) (Standards and Regulations) | 910 |
| External cable diameter D (Standards and Regulations) | 7.8 mm ±0.2 mm |
| Flammability rating according to UL 94 (General data) | HB |
| Material conductor insulation (Standards and Regulations) | Foam-Skin PP |
| Ambient temperature (operation) (Standards and Regulations) | -40 °C ... 80 °C (cable, fixed installation) |
| Conductor structure signal line (Standards and Regulations) | 19x 0.13 mm |
| Smallest bending radius, fixed installation (PROFIBUS [910]) | 19 mm |
| Core diameter including insulation (Standards and Regulations) | 2.55 mm ±0.07 mm |
| Smallest bending radius, movable installation (PROFIBUS [910]) | 38 mm |
| Ambient temperature (storage/transport) (Standards and Regulations) | -40 °C ... 80 °C |
| Smallest bending radius, fixed installation (Standards and Regulations) | 40 mm |
| Smallest bending radius, movable installation (Standards and Regulations) | 65 mm |