| Parameter | Value |
|---|---|
| 250 V DC | |
| Color | gray (RAL 7042) |
| Depth | 91 mm |
| Width | 44 mm |
| Height | 96 mm |
| Insulation | Basic insulation |
| Application | Universal |
| Coil voltage | 230 V AC |
| Product type | Relay Module |
| Assembly note | in rows with zero spacing |
| Mounting type | DIN rail mounting |
| Identification | ISA-S71.04. G3 Harsh Group |
| Operating mode | 100% operating factor |
| Product family | RIFLINE complete |
| Mains frequency | 50/60 Hz |
| Article revision | 03 |
| Contact material | AgNi |
| Pollution degree | 2 |
| Stripping length | 8 mm |
| Connection method | Screw connection |
| Mounting position | any |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Drive and function | monostable |
| Protective circuit | Varistor |
| Input voltage range | 195.5 V AC ... 253 V AC (20 °C) |
| Rated surge voltage | 4 kV |
| Overvoltage category | III |
| Standards/regulations | DIN EN 50178 |
| Typical response time | 5 ms ... 25 ms |
| Contact switching type | 2 changeover contacts |
| Maximum inrush current | 50 A (20 ms, N/O contacts) |
| Min. switching current | 10 mA (24 V) |
| Type of switch contact | Single contact |
| Mechanical service life | approx. 107cycles |
| Single-phase motor load | 800 W |
| Nominal input voltage UN | 230 V AC |
| Rated insulation voltage | 250 V AC |
| Maximum switching voltage | 440 V AC |
| Minimum switching voltage | 10 V (24 mA) |
| Operating voltage display | Yellow LED |
| Typical release time range | 5 ms ... 20 ms |
| Conductor cross section AWG | 20 ... 10 (solid) |
| Limiting continuous current | 9 A (see diagram) |
| Typical input current at UN | 14 mA |
| Date of last data management | 10.06.2024 |
| Degree of protection (Relay) | RT I (Relay) |
| Conductor cross section rigid | 0.5 mm² ... 4 mm² |
| Motor load according to UL 508 | 1/3 HP, 120 V AC (single-phase AC motor) |
| Test voltage (Contact/contact) | 2.5 kVrms(50 Hz, 1 min., contact/contact) |
| Test voltage (Winding/contact) | 2.5 kVrms(50 Hz, 1 min., winding/contact) |
| Ambient temperature (operation) | -40 °C ... 40 °C |
| Conductor cross section flexible | 0.5 mm² ... 4 mm² |
| Degree of protection (Relay base) | IP20 (Relay base) |
| Interrupting rating (ohmic load) max. | 216 W (24 V DC) |
| Flammability rating according to UL 94 | V2 (Housing) |
| Input voltage range in reference to UN | see diagram |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Utilization category CB Scheme (IEC 60947-5-1) | AC15, 1.5 A/240 V (N/O contact) |
| Conductor cross-section rigid (2 conductors with same cross section) | 0.5 mm² ... 2.5 mm² |
| Conductor cross section flexible (2 conductors with same cross section) | 0.5 mm² ... 2.5 mm² |
Technical specifications and performance data