| Parameter | Value |
|---|---|
| GTIN | 4055626513997 |
| Note | Made to Order (non-returnable) |
| Orderkey | 1021766 |
| (General) | IEC 62103 |
| (Coil side) | 1 A (230 V, AC15) |
| Depth (Note) | 70 mm |
| Packing unit | 10 pc |
| Width (Note) | 31 mm |
| Height (Note) | 96 mm |
| (Contact side) | 1500 VA (250 V AC) |
| Country of origin | PL (Poland) |
| Custom tariff number | 85364900 |
| Insulation (General) | Basic insulation |
| Minimum order quantity | 10 pc |
| Contact type (Coil side) | 4 PDTs |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Contact material (Coil side) | AgNi, hard gold-plated |
| (Connection data input side) | 26 ... 16 (flexible) |
| Degree of pollution (General) | 2 |
| Rated surge voltage (General) | 2.5 kV |
| (Connection data output side) | RT I (Relay) |
| Overvoltage category (General) | II |
| Switching capacity (Coil side) | 2 A (24 V, DC13) |
| Contact material (Contact side) | AgNi |
| Standards/regulations (General) | DIN EN 50178 |
| Coil voltage (Ambient conditions) | 230 V AC |
| Maximum inrush current (Coil side) | 50 mA |
| Min. switching current (Coil side) | 2 mA (24 V DC) |
| Rated insulation voltage (General) | 250 V AC |
| Type of switch contact (Coil side) | Single contact |
| Switching capacity min. (Coil side) | 48 mW |
| Mains frequency (Ambient conditions) | 50/60 Hz |
| Weight per Piece (excluding packing) | 102.000 g |
| Maximum switching voltage (Coil side) | 30 V AC |
| Min. switching current (Contact side) | 5 mA (24 V) |
| Minimum switching voltage (Coil side) | 2 V (At 24 mA) |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Limiting continuous current (Coil side) | 50 mA |
| Maximum switching voltage (Contact side) | 250 V AC/DC |
| Minimum switching voltage (Contact side) | 5 V (24 mA) |
| Limiting continuous current (Contact side) | see diagram |
| Typical response time (Ambient conditions) | 5 ms ... 15 ms |
| (Contact side (with destroyed gold layer)) | 26 ... 16 (flexible) |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 50 °C |
| Connection name (Connection data input side) | Contact side |
| Operating mode (Connection data output side) | 100% operating factor |
| Nominal input voltage UN (Ambient conditions) | 230 V AC |
| Stripping length (Connection data input side) | 8 mm |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Connection method (Connection data input side) | Push-in connection |
| Net weight (SAP) (Connection data output side) | 102 g |
| Operating voltage display (Ambient conditions) | Yellow LED |
| Mounting position (Connection data output side) | any |
| Typical release time range (Ambient conditions) | 5 ms ... 20 ms |
| Flammability rating according to UL 94 (General) | V2 |
| Typical input current at UN (Ambient conditions) | 6.5 mA |
| Interrupting rating (ohmic load) max. (Coil side) | 1.2 W (24 V DC) |
| Degree of protection (Connection data output side) | IP20 (Relay base) |
| Test voltage PDT/PDT (Connection data output side) | 2 kVrms(50 Hz, 1 min.) |
| Assembly instructions (Connection data output side) | In rows with zero spacing |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Interrupting rating (ohmic load) max. (Contact side) | 144 W (24 V DC) |
| Mechanical service life (Connection data output side) | approx. 2x 107cycles |
| Service life, electrical (Connection data output side) | see diagram |
| Conductor cross section AWG (Connection data input side) | 26 ... 16 (solid) |
| Conductor cross section solid (Connection data input side) | 0.14 mm² ... 1.5 mm² |
| Connection name (Contact side (with destroyed gold layer)) | Coil side |
| Input voltage range in reference to UN (Ambient conditions) | see diagram |
| Stripping length (Contact side (with destroyed gold layer)) | 8 mm |
| Connection method (Contact side (with destroyed gold layer)) | Push-in connection |
| Conductor cross section flexible (Connection data input side) | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG (Contact side (with destroyed gold layer)) | 26 ... 16 (solid) |
| Test voltage relay winding/relay contact (Connection data output side) | 2.5 kVrms(50 Hz, 1 min.) |
| Conductor cross section solid (Contact side (with destroyed gold layer)) | 0.14 mm² ... 1.5 mm² |
| Conductor cross section flexible (Contact side (with destroyed gold layer)) | 0.14 mm² ... 1.5 mm² |
Technical specifications and performance data
Installation and operation guide