| Parameter | Value |
|---|---|
| GTIN | 4046356983518 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2905656 |
| Catalog page | Page 339 (C-5-2017) |
| Depth (Note) | 68 mm |
| Packing unit | 10 pc |
| Width (Note) | 6.2 mm |
| Height (Note) | 84 mm |
| (Output data) | 20 ... 14 (flexible) |
| Country of origin | JP (Japan) |
| (Connection data 1) | 20 ... 14 (flexible) |
| Custom tariff number | 85364110 |
| Insulation (General) | Basic insulation |
| Torque (Output data) | 0.5 Nm ... 0.6 Nm |
| Designation (General) | Air clearances and creepage distances between the power circuits |
| Surge current (Input data) | 30 A AC (tp = 20 ms, at 25°C) |
| Torque (Connection data 1) | 0.5 Nm ... 0.6 Nm |
| Output circuit (Input data) | 2-wire, zero voltage switch |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Leakage current (Input data) | 1 mA (in off state) |
| Max. load value (Input data) | 4.5 A2s (tp = 10 ms, at 25 °C) |
| Connection name (Output data) | Coil side |
| Degree of pollution (General) | 2 |
| Rated surge voltage (General) | 4 kV |
| Min. load current (Input data) | 10 mA |
| Overvoltage category (General) | III |
| Stripping length (Output data) | 7 mm |
| Connection method (Output data) | Screw connection |
| Designation (Connection data 2) | Air clearances and creepage distances between the power circuits |
| Standards/regulations (General) | DIN EN 50178 |
| Type of protection (Input data) | RCV circuit |
| Degree of protection (Dimensions) | IP20 |
| Output voltage range (Input data) | 24 V AC ... 253 V AC (50/60 Hz) |
| Operating mode (Connection data 2) | 100% operating factor |
| Rated insulation voltage (General) | 260 V AC |
| Connection name (Connection data 1) | Contact side |
| Maximum inrush current (Input data) | 30 A (10 ms) |
| Status display (Ambient conditions) | Yellow LED |
| Stripping length (Connection data 1) | 7 mm |
| Weight per Piece (excluding packing) | 27.990 g |
| Connection method (Connection data 1) | Screw connection |
| Mounting position (Connection data 2) | any |
| Surge voltage protection (Input data) | > 275 V |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Degree of pollution (Connection data 2) | 2 |
| Type of protection (Ambient conditions) | Free-wheeling diode |
| Input voltage range (Ambient conditions) | 19.2 V DC ... 28.8 V DC |
| Limiting continuous current (Input data) | 0.75 A (see derating curve) |
| Overvoltage category (Connection data 2) | III |
| Assembly instructions (Connection data 2) | In rows with zero spacing |
| Conductor cross section AWG (Output data) | 20 ... 12 (solid) |
| Standards/regulations (Connection data 2) | DIN EN 50178 |
| Typical response time (Ambient conditions) | 10 ms |
| Typical turn-off time (Ambient conditions) | 10 ms |
| Conductor cross section solid (Output data) | 0.5 mm² ... 4 mm² |
| Transmission frequency (Ambient conditions) | 10 Hz |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C |
| Test voltage input/output (Connection data 2) | 2.5 kVrms(50 Hz, 1 min.) |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Conductor cross section flexible (Output data) | 0.5 mm² ... 2.5 mm² |
| Conductor cross section AWG (Connection data 1) | 20 ... 12 (solid) |
| Rated actuating voltage UC (Ambient conditions) | 24 V DC |
| Flammability rating according to UL 94 (General) | V2 |
| Conductor cross section solid (Connection data 1) | 0.5 mm² ... 4 mm² |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Conductor cross section flexible (Connection data 1) | 0.5 mm² ... 2.5 mm² |
| Flammability rating according to UL 94 (Connection data 2) | V2 |
| Power dissipation for nominal condition (Ambient conditions) | 0.19 W |
| Voltage drop at max. limiting continuous current (Input data) | < 1 V |
| "0" signal switching threshold in reference to UC (Ambient conditions) | < 0.4 |
| "1" signal switching threshold in reference to UC (Ambient conditions) | > 0.8 |
| Conductor cross-section solid (2 conductors with same cross section) (Output data) | 0.5 mm² ... 1.5 mm² |
| Conductor cross section flexible (2 conductors with same cross section) (Output data) | 0.5 mm² ... 1.5 mm² |
| Conductor cross-section solid (2 conductors with same cross section) (Connection data 1) | 0.5 mm² ... 1.5 mm² |
| Conductor cross section flexible (2 conductors with same cross section) (Connection data 1) | 0.5 mm² ... 1.5 mm² |
Technical specifications and performance data
Installation and operation guide