| Parameter | Value |
|---|---|
| GTIN | 4055626358789 |
| Orderkey | 2909055 |
| (Drawings) | Do not use to separate SELV / PELV circuits from other circuits, because safe isolation is not guaranteed. |
| (Coil side) | 1/2 HP, 240 V AC (three-phase induction motor) |
| Catalog page | Page 312 (C-5-2019) |
| Depth (Note) | 45.5 mm |
| Packing unit | 1 |
| Width (Note) | 38.6 mm |
| (Dimensions) | ≥ IP54 (Installation location) |
| Height (Note) | 36.1 mm |
| Note (Drawings) | The outputs are not suitable for switching different outer conductors. |
| ETIM 2.0 (eCl@ss) | EC001437 |
| ETIM 3.0 (eCl@ss) | EC001437 |
| ETIM 4.0 (eCl@ss) | EC001437 |
| ETIM 5.0 (eCl@ss) | EC001437 |
| ETIM 6.0 (eCl@ss) | EC001437 |
| ETIM 7.0 (eCl@ss) | EC001437 |
| (Connection data) | IEC 61810 |
| UNSPSC 13.2 (ETIM) | 39122334 |
| UNSPSC 18.0 (ETIM) | 39122334 |
| UNSPSC 19.0 (ETIM) | 39122334 |
| UNSPSC 20.0 (ETIM) | 39122334 |
| UNSPSC 21.0 (ETIM) | 39122334 |
| Custom tariff number | 85364900 |
| Contact type (Coil side) | 3 PDTs |
| Connection method (General) | Plug connection |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Contact material (Coil side) | AgNi |
| Insulation (Connection data) | Basic insulation |
| eCl@ss 5.0 (Classifications) | 27371601 |
| eCl@ss 5.1 (Classifications) | 27371601 |
| eCl@ss 6.0 (Classifications) | 27371601 |
| eCl@ss 7.0 (Classifications) | 27371601 |
| eCl@ss 8.0 (Classifications) | 27371601 |
| eCl@ss 9.0 (Classifications) | 27371601 |
| Maximum altitude (Dimensions) | ≤ 2000 m |
| Operating mode (Contact side) | 100% operating factor |
| 3-phase motor load (Coil side) | 1500 W (at 400 V, AC3) |
| Mounting position (Contact side) | any |
| Degree of protection (Dimensions) | RT I |
| Maximum inrush current (Coil side) | 50 A (20 ms, N/O contacts) |
| Min. switching current (Coil side) | 10 mA (at 24 V) |
| Pollution degree (Connection data) | 3 |
| Type of switch contact (Coil side) | Single contact |
| Test voltage PDT/PDT (Contact side) | 2.5 kVrms(50 Hz, 1 min.) |
| Coil resistance (Ambient conditions) | 37000 Ω ±10 % |
| Maximum switching voltage (Coil side) | 440 V AC |
| Minimum switching voltage (Coil side) | 10 V (At 24 mA) |
| Rated surge voltage (Connection data) | 4 kV |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Mechanical service life (Contact side) | approx. 107cycles |
| Overvoltage category (Connection data) | III |
| Limiting continuous current (Coil side) | 16 A |
| Service life, electrical (Contact side) | see diagram |
| Standards/regulations (Connection data) | IEC 60664 |
| Non-operate voltage (Ambient conditions) | < 132 V DC |
| DiagramElectrical service life (Drawings) | |
| DiagramOperating voltage range (Drawings) | |
| Safe operate voltage (Ambient conditions) | > 176 V DC |
| Typical release time (Ambient conditions) | 15 ms |
| Motor load according to UL 508 (Coil side) | 1/3 HP, 120 V AC (single-phase AC motor) |
| Rated insulation voltage (Connection data) | 250 V AC |
| Typical response time (Ambient conditions) | 20 ms |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 70 °C |
| Nominal input voltage UN (Ambient conditions) | 220 V DC |
| Typical input current at UN (Ambient conditions) | 6 mA |
| Interrupting rating (ohmic load) max. (Coil side) | 384 W (at 24 V DC) |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Test voltage relay winding/relay contact (Contact side) | 2.5 kVrms(50 Hz, 1 min.) |
| Power dissipation for nominal condition (Ambient conditions) | 1.34 W |
Technical specifications and performance data
Installation and operation guide