| Parameter | Value |
|---|---|
| Note | Connection bolts |
| Color | gray/blue/black-yellow |
| Width | 245 mm |
| Length | 164 mm |
| Screw thread | M12 |
| Bolt diameter | 12 mm |
| Hole diameter | 13 mm |
| Height NS 35/15 | 90.8 mm |
| Open side panel | nein |
| Height NS 35/7,5 | 83.3 mm |
| Number of levels | 1 |
| Pollution degree | 3 |
| Connection method | Bolt connection |
| Nominal current IN | 415 A |
| Nominal voltage UN | 1000 V |
| Insulating material | PA |
| Number of positions | 5 |
| Rated surge voltage | 8 kV |
| Maximum load current | 415 A (At 240 mm² conductor cross section) |
| Overvoltage category | III |
| Nominal cross section | 240 mm² |
| Number of connections | 10 |
| Tightening torque max | 30 Nm |
| Tightening torque, min | 14 Nm |
| Insulating material group | I |
| Conductor cross section AWG max. | 500 |
| Conductor cross section AWG min. | 8 |
| Connection in acc. with standard | IEC 60947-7-1 |
| Conductor cross section solid max. | 240 mm² |
| Conductor cross section solid min. | 10 mm² |
| Conductor cross section flexible max. | 240 mm² |
| Conductor cross section flexible min. | 10 mm² |
| Flammability rating according to UL 94 | V0 |
| Cable lug connection according to standard | DIN 46 234 |
| Max. AWG conductor cross section, flexible | 500 |
| Min. AWG conductor cross section, flexible | 8 |
| Max. cross section for cable lug connection | 240 mm² |
| Min. cross section for cable lug connection | 10 mm² |
Technical specifications and performance data