| Parameter | Value |
|---|---|
| GTIN | 4046356781961 |
| Orderkey | 2904035 |
| Catalog page | Page 463 (C-6-2017) |
| Depth (Note) | 114.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 17.5 mm |
| (Dimensions) | -40 °F ... 185 °F |
| Height (Note) | 113 mm |
| Country of origin | DE (Germany) |
| (Connection data) | Red LED (periphery error, ERR) |
| Shock (Dimensions) | 16g, 11 ms |
| (Status indicator) | Class I, Zone 2, IIC T4 |
| Custom tariff number | 85177000 |
| (Ambient conditions) | 194 Years (Telcordia standard, temperature 40 °C, operating cycle 100 % (7 days a week, 24 hours a day)) |
| Altitude (Dimensions) | 2000 m |
| ATEX (Status indicator) | II 3 G Ex nA IIC T4 Gc |
| IECEx (Status indicator) | Ex nA IIC T4 Gc |
| Shock (Status indicator) | 16g, 11 ms |
| MTTF (Ambient conditions) | 1249 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) |
| Number of inputs (Supply) | 4 |
| Dimensional drawing (Note) | |
| Measuring accuracy (Supply) | 0.1% (From the measuring range final value) |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Screw thread (Analog inputs) | M3 |
| Process data channel (Supply) | 16 Bit (per channel) |
| Sensor input current (Supply) | 1 mA (constant) |
| Conformance (Status indicator) | CE-compliant |
| Connection technology (Supply) | 2, 3-wire |
| Supply voltage range (General) | 19.2 V DC ... 30.5 V DC (DIN rail connector) |
| Status display (Connection data) | Green LED (supply voltage, PWR) |
| Stripping length (Analog inputs) | 7 mm |
| Connection method (Analog inputs) | Screw connection |
| Degree of protection (Dimensions) | IP20 |
| Description of the input (Supply) | Pt 100 input |
| Noise emission (Status indicator) | EN 61000-6-4 |
| Noise immunity (Status indicator) | EN 61000-6-2 |
| Tightening torque (Analog inputs) | 0.6 Nm |
| UL, USA/Canada (Status indicator) | UL 508 Listed |
| Max. current consumption (General) | ≤ 38 mA (At 24 V DC, at 25°C) |
| Vibration (operation) (Dimensions) | in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz |
| Noxious gas test (Status indicator) | ISA-S71.04-1985 G3 Harsh Group A |
| Temperature measuring range (Supply) | -50 °C ... 250 °C |
| Transient surge protection (General) | Yes |
| Weight per Piece (excluding packing) | 217.800 g |
| Housing material (Ambient conditions) | PA 6.6-FR |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Mounting position (Ambient conditions) | any |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Standard designation (Status indicator) | Ex Directive (ATEX) |
| Degree of pollution (Ambient conditions) | 2 |
| Standards/regulations (Status indicator) | EN-60079-15 |
| Vibration (operation) (Status indicator) | in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz |
| Overvoltage category (Ambient conditions) | II |
| Assembly instructions (Ambient conditions) | on standard DIN rail NS 35 in accordance with EN 60715 |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 70 °C |
| Permissible humidity (operation) (Dimensions) | 20 % ... 85 % |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Conductor cross section AWG max. (Analog inputs) | 14 |
| Conductor cross section AWG min. (Analog inputs) | 24 |
| Electromagnetic compatibility (Status indicator) | Conformance with EMC Directive 2014/30/EU |
| Conductor cross section solid max. (Analog inputs) | 2.5 mm² |
| Conductor cross section solid min. (Analog inputs) | 0.2 mm² |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Conductor cross section flexible max. (Analog inputs) | 2.5 mm² |
| Conductor cross section flexible min. (Analog inputs) | 0.2 mm² |
| Permissible humidity (storage/transport) (Dimensions) | 20 % ... 85 % |
| Max. permissible overall conductor resistance (Supply) | 25 Ω |
| Flammability rating according to UL 94 (Status indicator) | V0 |
| Flammability rating according to UL 94 (Ambient conditions) | V0 |