| Parameter | Value |
|---|---|
| -40 °F ... 158 °F (>131°F derating) | |
| MTTF | 778 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) |
| Depth | 114.5 mm |
| IECEx | Ex nA nC IIC T4 Gc |
| Range | ± 5 km (The range may be considerably above or below that stated, and depends on the environment, antenna technology, and the product used) |
| Shock | 16g, 11 ms |
| Width | 17.5 mm |
| Height | 99 mm |
| Altitude | 2000 m |
| Security | 128-bit data encryption |
| Data rate | 16 kbps (adjustable) |
| Direction | Bi-directional |
| Frequency | 2400 MHz |
| Conformance | CE compliance (R&TTE directive 1999/5/EC) |
| Designation | Wireless module |
| Export note | *The range may be considerably above or below that stated. It is dependent on the environment, antenna technology, transmission power, and the product used. |
| Interface 1 | RS-232 |
| Interface 2 | RS-485 |
| Interface 3 | Configuration interface |
| Contact type | PDT |
| Screw thread | M3 |
| I/O data mode | ≤ 99 (I/O extension modules per wireless network, serial interfaces deactivated) |
| Operating mode | I/O data (Default setting, configuration via thumbwheel) |
| Status display | Green LED (supply voltage, PWR) |
| Frequency range | 2.4002 GHz ... 2.4785 GHz |
| Channel distance | 1.3 MHz |
| Contact material | PdRu, gold-plated |
| Housing material | PA 6.6-FR |
| Pollution degree | 2 |
| Serial data mode | 0 (no I/O extension modules can be used) |
| Stripping length | 7 mm |
| UL, USA / Canada | UL 508 Listed |
| Connection method | COMBICON plug-in screw terminal block |
| Number of outputs | 1 |
| Tightening torque | 0.6 Nm |
| Wireless licences | Australia |
| Antenna connection | RSMA (female) |
| Transmission speed | 0,3 ... 115,2 kbit/s |
| PLC/Modbus RTU mode | ≤ 99 (I/O extension modules per wireless network, access to extension modules via Modbus RTU protocol) |
| Transmission length | ≤ 15 m |
| Degree of protection | IP20 |
| Overvoltage category | II |
| Receiver sensitivity | -106 dBm (16 kbps) |
| Standard designation | Ex Directive (ATEX) |
| Supply voltage range | 19.2 V DC ... 30.5 V DC |
| Termination resistor | 390 Ω (switchable via DIP switches) |
| Assembly instructions | on standard DIN rail NS 35 in accordance with EN 60715 |
| Standards/regulations | EN 60079-0 |
| Vibration (operation) | in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz |
| Voltage output signal | 0 V ... 3 V |
| Max. switching current | 500 mA (30 V AC/DC) |
| Electrical service life | 5 x 105cycles with 0.5 A @ 30 V DC |
| Max. current consumption | ≤ 65 mA (@ 24 V DC, @ 25°C, stand-alone) |
| Number of channel groups | 8 |
| Maximum switching voltage | 30 V AC/DC |
| Transient surge protection | Yes |
| Transmit capacity, maximum | ≤ 20 dBm (Outside of Europe, adjustable via software) |
| Transmit capacity, minimum | 0 dBm |
| Number of supported devices | ≤ 250 (Addressing via PSI-CONF software) |
| Number of channels per group | 55 |
| Ambient temperature (operation) | -40 °C ... 70 °C (>55°C derating) |
| Conductor cross section AWG max. | 14 |
| Conductor cross section AWG min. | 24 |
| Permissible humidity (operation) | 20 % ... 85 % |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section solid min. | 0.2 mm² |
| Number of possible extension modules | ≤ 32 (per wireless module) |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Flammability rating according to UL 94 | V0 |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (storage/transport) | 20 % ... 85 % |
Technical specifications and performance data