| Parameter | Value |
|---|---|
| GTIN | 4055626244563 |
| Orderkey | 2320283 |
| Catalog page | Page 281 (C-4-2017) |
| Packing unit | 1 pc |
| (Input data) | typ. 25 W (230 V AC) |
| (Output data) | > 94 % (230 V AC) |
| Country of origin | DE (Germany) |
| Custom tariff number | 85371091 |
| (Ambient conditions) | 240 V AC -20 % / +10 % |
| Derating (Input data) | > 50 °C ... 60 °C (2.5%/K) |
| Efficiency (Output data) | > 92 % (120 V AC) |
| Net weight (Output data) | 5 kg |
| Stripping length (General) | 8 mm |
| Climatic class (Dimensions) | 3K3 (EN 60721) |
| Connection method (General) | Screw connection |
| Depth (Key Commercial Data) | 125 mm |
| Width (Key Commercial Data) | 290 mm |
| Height (Key Commercial Data) | 130 mm |
| Protection class (Output data) | I |
| Degree of pollution (Dimensions) | 2 |
| Installation height (Dimensions) | ≤ 3000 m (> 2000 m, observe derating) |
| Connection in series (Input data) | No |
| Degree of protection (Dimensions) | IP20 |
| POWER BOOST (IBoost) (Input data) | 13 A (120 V AC) |
| Buffer period (Ambient conditions) | 1 h (38 AH) |
| Degree of protection (Output data) | IP20 |
| Connection in parallel (Input data) | Yes, 2 |
| Nominal output voltage (Input data) | 100 V AC |
| Weight per Piece (excluding packing) | 5,530.000 g |
| Shock (Connection data for signaling) | 15g in all directions (EN 60068-2-27) |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| AC frequency range (Ambient conditions) | 45 Hz ... 65 Hz |
| Voltage (Connection data for signaling) | 10 V |
| Comments (Connection data for signaling) | Criterion B |
| Input voltage range (Ambient conditions) | 90 V AC ... 264 V AC |
| MTBF (IEC 61709, SN 29500) (Output data) | 217546 h (230 V AC, at 40 °C) |
| Nominal output current (IN) (Input data) | 7.8 A (100 V AC) |
| Stripping length (Connection data, input) | 8 mm |
| Conductor cross section AWG max. (General) | 10 |
| Conductor cross section AWG min. (General) | 30 |
| Connection method (Connection data, input) | Screw connection |
| Nominal input voltage (Ambient conditions) | 100 V AC -10 % / +20 % |
| Stripping length (Connection data, output) | 8 mm |
| Connection method (Connection data, output) | Screw connection |
| Power factor (cos phi) (Ambient conditions) | 0.9 |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C (> 50 °C Derating: 2.5 %/K) |
| Conductor cross section solid max. (General) | 6 mm² |
| Conductor cross section solid min. (General) | 0.2 mm² |
| Permissible backup fuse (Ambient conditions) | B16 230 V AC |
| UL approvals (Connection data for signaling) | UL/C-UL Recognized UL 1778 |
| Noise immunity (Connection data for signaling) | Noise immunity according to EN 62040-2-2006 |
| Conductor cross section flexible max. (General) | 4 mm² |
| Conductor cross section flexible min. (General) | 0.2 mm² |
| Frequency range (Connection data for signaling) | 0.15 MHz ... 80 MHz |
| Contact discharge (Connection data for signaling) | 4 kV (Test Level 2) |
| Test field strength (Connection data for signaling) | 10 V/m |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C (with charged energy storage device) |
| Low Voltage Directive (Connection data for signaling) | Conformance with Low Voltage Directive 2014/35/EC |
| Standards/regulations (Connection data for signaling) | EN 61000-4-8 |
| Vibration (operation) (Connection data for signaling) | 5 Hz ... 100 Hz, 0.7g (EN 60068-2-6) |
| Conducted noise emission (Connection data for signaling) | EN 62040-02 (Class C2) |
| Conductor cross section AWG max. (Connection data, input) | 10 |
| Conductor cross section AWG min. (Connection data, input) | 30 |
| Conductor cross section AWG max. (Connection data, output) | 12 |
| Conductor cross section AWG min. (Connection data, output) | 30 |
| Conductor cross section solid max. (Connection data, input) | 6 mm² |
| Conductor cross section solid min. (Connection data, input) | 0.2 mm² |
| Max. permissible relative humidity (operation) (Dimensions) | ≤ 95 % |
| Maximum power dissipation in no-load condition (Input data) | typ. 17 W (120 V AC) |
| Conductor cross section solid max. (Connection data, output) | 2.5 mm² |
| Conductor cross section solid min. (Connection data, output) | 0.2 mm² |
| Electromagnetic compatibility (Connection data for signaling) | Conformance with EMC Directive 2014/30/EU |
| Conductor cross section flexible max. (Connection data, input) | 4 mm² |
| Conductor cross section flexible min. (Connection data, input) | 0.2 mm² |
| Conductor cross section flexible max. (Connection data, output) | 2.5 mm² |
| Conductor cross section flexible min. (Connection data, output) | 0.2 mm² |
| Overvoltage category (EN 60950-1) (Connection data for signaling) | II |
Technical specifications and performance data