| Parameter | Value |
|---|---|
| 24 V DC | |
| LED | yes |
| Time | 186000 h |
| Depth | 125 mm |
| I/O/S | asymmetrical |
| Input | 2 kV (Test Level 4 - asymmetrical) |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Width | 32 mm |
| Height | 130 mm |
| Output | 2 kV (Test Level 4 - asymmetrical) |
| Signal | 2 kV (Test Level 4 - asymmetrical) |
| Current | 40 A |
| Default | open |
| Voltage | 10 V (Test Level 3) |
| Comments | Criterion B |
| Derating | 60 °C ... 70 °C (2.5 %/K) |
| Frequency | 16.67 Hz |
| Efficiency | typ. 99.1 % (12 V DC) |
| Criterion A | Normal operating behavior within the specified limits. |
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
| Temperature | 40 °C |
| UIn< 8 V DC | LED off, input voltage not present or short circuit at redundancy module output |
| UIn> 8 V DC | LED lights up green, input voltage present |
| Hood version | Galvanized sheet steel, free from chrome (VI) |
| Product type | Redundancy module |
| Screw thread | M4 |
| UL approvals | UL/C-UL listed UL 508 |
| Assembly note | alignable: PNâ¥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
| Mounting type | DIN rail mounting |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Noise emission | Additional basic standard EN 61000-6-5 (immunity in power station) |
| Product family | QUINT S-ORING |
| Additional text | UIN |
| Frequency range | 80 MHz ... 1 GHz |
| Type of housing | Aluminum (AlMg3) |
| Article revision | 03 |
| Discharge in air | 15 kV (Test Level 4) |
| Housing material | Metal |
| Maximum altitude | ⤠5000 m (> 2000 m, observe derating) |
| Protection class | III |
| Stripping length | 10 mm |
| Connection method | Screw connection |
| Contact discharge | 8 kV (Test Level 4) |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Input current ISFB | 215 A (15 ms) |
| Output description | Group contact |
| Types of signaling | Relay contact, floating, current limited |
| Current consumption | 40 A |
| Degree of pollution | 2 |
| Dimensional drawing | |
| Input voltage range | 8 V DC ... 30 V DC |
| Test field strength | 20 V/m (Test Level 3) |
| Connection in series | no |
| Degree of protection | IP20 |
| Input current IStatic | 45 A (40 °C) |
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| Shipbuilding approval | DNV GL |
| Standards/regulations | EN 61000-4-2 |
| Tightening torque max | 1.5 Nm |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| Input current IDynamic | 60 A (5 s) |
| Maximum inrush current | ⤠100 mA (short-circuit-proof) |
| Nominal output voltage | UIn- 0.1 V |
| Tightening torque, min | 1.2 Nm |
| DNV GL noise radiation | Class B |
| Redundancy modul faulty | LED lights up red, redundancy module needs to be factory tested |
| Conducted noise emission | EN 55016 |
| Maximum switching voltage | max. 30 V AC/DC |
| Standard - Safe isolation | DIN VDE 0100-410 |
| Dynamic Boost (IDyn.Boost) | 60 A (5 s) |
| MTBF (IEC 61709, SN 29500) | > 25297000 h (25 °C) |
| Nominal input current (IN) | 40 A (-40 °C ... 60 °C) |
| Static Boost (IStat.Boost) | 45 A |
| Transient surge protection | Varistor |
| Voltage drop, input/output | 0.1 V |
| Nominal input voltage range | 12 V DC ... 24 V DC |
| Nominal output current (IN) | 40 A |
| Reverse polarity protection | < yes60 V |
| Power loss nominal load max. | 6.5 W (IOUT= 40 A) |
| Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Typical national grid voltage | 12 V DC |
| DNV GL conducted interference | Class A |
| Selective Fuse Breaking (ISFB) | 215 A (15 ms) |
| Voltage type of supply voltage | DC |
| Ambient temperature (operation) | -40 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
| Conductor cross section AWG max. | 6 |
| Conductor cross section AWG min. | 20 |
| Installation distance right/left | 0 mm / 0 mm |
| Installation distance top/bottom | 40 mm / 20 mm |
| SIL in accordance with IEC 61508 | 0 |
| Conductor cross section, rigid max. | 16 mm² |
| Conductor cross section, rigid min. | 0.5 mm² |
| EMC requirements for noise emission | EN 61000-6-3 |
| EMC requirements for noise immunity | EN 61000-6-1 |
| Conductor cross section flexible max. | 16 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Standard â Safety extra-low voltage | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Insulation voltage input, output / housing | 500 V DC |
| Max. permissible relative humidity (operation) | ⤠95 % (at 25 °C, non-condensing) |
| Flammability rating according to UL 94 (housing / terminal blocks) | V0 |
| Single conductor/flexible terminal point with ferrule with plastic sleeve, max. | 16 mm² |
| Single conductor/flexible terminal point with ferrule with plastic sleeve, min. | 0.5 mm² |
| Single conductor/flexible terminal point with ferrule without plastic sleeve, max. | 16 mm² |
| Single conductor/flexible terminal point with ferrule without plastic sleeve, min. | 0.5 mm² |
| Standard â Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 50178 |
| Standard â Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Technical specifications and performance data