| Parameter | Value |
|---|---|
| GTIN | 4055626607474 |
| Orderkey | 1043418 |
| (Drawings) | |
| (Standards) | UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
| Catalog page | Page 305 (C-4-2019) |
| Packing unit | 1 |
| (Input data) | 6 W (IOUT= 40 A) |
| (Output data) | > 3379000 h (60 °C) |
| Depth (Drawings) | 125 mm |
| Width (Drawings) | 32 mm |
| ETIM 5.0 (eCl@ss) | EC000683 |
| ETIM 6.0 (eCl@ss) | EC000683 |
| ETIM 7.0 (eCl@ss) | EC000683 |
| Height (Drawings) | 130 mm |
| Diagram (Drawings) | |
| Custom tariff number | 85049090 |
| Derating (Input data) | 60 °C ... 70 °C (2.5%/K) |
| REACh SVHC (EMC data) | Lead 7439-92-1 |
| Screw thread (General) | M4 |
| (Conformance/approvals) | 60 Hz |
| Block diagram (Drawings) | |
| Efficiency (Output data) | typ. 99 % (12 V DC) |
| Net weight (Output data) | 0.4 kg |
| UL approvals (Standards) | UL/C-UL listed UL 508 |
| Stripping length (General) | 10 mm |
| Climatic class (Dimensions) | 3K3 (in acc. with EN 60721) |
| Connection method (General) | Screw connection |
| eCl@ss 8.0 (Classifications) | 27371010 |
| eCl@ss 9.0 (Classifications) | 27371010 |
| I/O/S (Conformance/approvals) | asymmetrical |
| Input (Conformance/approvals) | 1 kV (Test Level 4 - symmetrical) |
| Output (Conformance/approvals) | 1 kV (Test Level 2 - symmetrical) |
| Protection class (Output data) | III |
| Signal (Conformance/approvals) | 1 kV (Test Level 2 - asymmetrical) |
| Mounting position (Output data) | horizontal DIN rail NS 35, EN 60715 |
| Voltage (Conformance/approvals) | 10 V (Test Level 3) |
| Comments (Conformance/approvals) | Criterion A |
| Degree of pollution (Dimensions) | 2 |
| Installation height (Dimensions) | ≤ 5000 m (> 2000 m, observe derating) |
| Connection in series (Input data) | No |
| Degree of protection (Dimensions) | IP20 |
| Frequency (Conformance/approvals) | 16.67 Hz |
| Output voltage range (Input data) | 8 V DC ... 27.5 V DC |
| Degree of protection (Output data) | IP20 |
| Assembly instructions (Output data) | alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
| Criterion A (Conformance/approvals) | Normal operating behavior within the specified limits. |
| Criterion B (Conformance/approvals) | Temporary impairment to operational behavior that is corrected by the device itself. |
| Screw thread (Connection data, input) | M4 |
| Noise emission (Conformance/approvals) | EN 55016 |
| Additional text (Conformance/approvals) | 60 s |
| Dynamic Boost (IDyn.Boost) (Input data) | 60 A (5 s) |
| Frequency range (Conformance/approvals) | 0.15 MHz ... 80 MHz |
| Static Boost (IStat.Boost) (Input data) | 45 A |
| Current consumption (Ambient conditions) | 40 A |
| Discharge in air (Conformance/approvals) | 15 kV (Test Level 4) |
| Input voltage range (Ambient conditions) | 8 V DC ... 27.5 V DC (SELV) |
| MTBF (IEC 61709, SN 29500) (Output data) | > 13486000 h (25 °C) |
| Nominal output current (IN) (Input data) | 40 A |
| Contact discharge (Conformance/approvals) | 8 kV (Test Level 4) |
| Power loss nominal load max. (Input data) | 6.5 W (IOUT= 40 A) |
| Stripping length (Connection data, input) | 10 mm |
| Conductor cross section AWG max. (General) | 6 |
| Conductor cross section AWG min. (General) | 20 |
| Connection method (Connection data, input) | Screw connection |
| Depth with alternative assembly (Drawings) | 35 mm |
| Nominal input current (Ambient conditions) | 40 A (-40 °C ... 60 °C) |
| Stripping length (Connection data, output) | 8 mm |
| Width with alternative assembly (Drawings) | 122 mm |
| Connection method (Connection data, output) | Push-in connection |
| Height with alternative assembly (Drawings) | 130 mm |
| Selective Fuse Breaking (ISFB) (Input data) | 215 A (15 ms) |
| Test field strength (Conformance/approvals) | 30 A/m |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Conductor cross section solid max. (General) | 16 mm² |
| Conductor cross section solid min. (General) | 0.5 mm² |
| Low Voltage Directive (Conformance/approvals) | Conformance with Low Voltage Directive 2014/35/EC |
| Conductor cross section flexible max. (General) | 16 mm² |
| Conductor cross section flexible min. (General) | 0.5 mm² |
| DNV GL noise radiation (Conformance/approvals) | Class B |
| Electrostatic discharge (Conformance/approvals) | EN 61000-4-2 |
| Fast transients (burst) (Conformance/approvals) | EN 61000-4-4 |
| Conducted noise emission (Conformance/approvals) | EN 55016 |
| Electromagnetic HF field (Conformance/approvals) | EN 61000-4-3 |
| Nominal input voltage range (Ambient conditions) | 12 V DC ... 24 V DC |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Electromagnetic compatibility (Conformance/approvals) | Conformance with EMC Directive 2014/30/EU |
| DNV GL conducted interference (Conformance/approvals) | Class A |
| Conductor cross section AWG max. (Connection data, input) | 6 |
| Conductor cross section AWG min. (Connection data, input) | 20 |
| Standard - Safe isolation (Connection data for signaling) | DIN VDE 0100-410 |
| Conductor cross section AWG max. (Connection data, output) | 16 |
| Conductor cross section AWG min. (Connection data, output) | 24 |
| Conductor cross section solid max. (Connection data, input) | 16 mm² |
| Conductor cross section solid min. (Connection data, input) | 0.5 mm² |
| Max. permissible relative humidity (operation) (Dimensions) | ≤ 100 % (at 25 °C, non-condensing) |
| Conductor cross section solid max. (Connection data, output) | 1.5 mm² |
| Conductor cross section solid min. (Connection data, output) | 0.2 mm² |
| Standard - Electrical safety (Connection data for signaling) | EN 60950-1/VDE 0805 (SELV) |
| Conductor cross section flexible max. (Connection data, input) | 16 mm² |
| Conductor cross section flexible min. (Connection data, input) | 0.5 mm² |
| Conductor cross section flexible max. (Connection data, output) | 1.5 mm² |
| Conductor cross section flexible min. (Connection data, output) | 0.2 mm² |
| Protection against overvoltage at the output (OVP) (Input data) | ≤ 30 V DC |
| Standard – Safety extra-low voltage (Connection data for signaling) | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
| Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment (Connection data for signaling) | EN 50178 |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations (Connection data for signaling) | EN 50178/VDE 0160 (PELV) |
Technical specifications and performance data