| Parameter | Value |
|---|---|
| GTIN | 4055626356105 |
| Orderkey | 2904623 |
| (Drawings) | |
| (Standards) | CSA-C22.2 No. 107.1-01 |
| Catalog page | Page 237 (C-4-2019) |
| Packing unit | 1 pc |
| (Input data) | < 45 W (480 V AC) |
| (Output data) | > 236000 h (60 °C) |
| CSA (Standards) | CAN/CSA-C22.2 No. 60950-1-07 |
| SIQ (Standards) | BG (type approved) |
| Depth (Drawings) | 125 mm |
| Width (Drawings) | 120 mm |
| Country of origin | TH (Thailand) |
| ETIM 5.0 (eCl@ss) | EC002540 |
| ETIM 6.0 (eCl@ss) | EC002540 |
| ETIM 7.0 (eCl@ss) | EC002540 |
| Height (Drawings) | 130 mm |
| IECEx (Standards) | Ex nA nC IIC T4 Gc (IECEx EPS 16.0057X) |
| Diagram (Drawings) | |
| Custom tariff number | 85044030 |
| (Ambient conditions) | typ. 28 ms (3x 480 V AC) |
| REACh SVHC (EMC data) | Lead 7439-92-1 |
| (Conformance/approvals) | 4 kV (Test Level 4 - asymmetrical) |
| Block diagram (Drawings) | |
| Efficiency (Output data) | typ. 95.7 % (400 V AC) |
| Net weight (Output data) | 2.6 kg |
| UL approvals (Standards) | UL Listed UL 508 |
| Output power (Input data) | 960 W |
| Stripping length (General) | 8 mm |
| Climatic class (Dimensions) | 3K3 (in acc. with EN 60721) |
| Connection method (General) | Screw connection |
| Residual ripple (Input data) | < 50 mVPP(with nominal values) |
| eCl@ss 8.0 (Classifications) | 27049002 |
| eCl@ss 9.0 (Classifications) | 27040701 |
| I/O/S (Conformance/approvals) | asymmetrical |
| Input (Conformance/approvals) | 2 kV (Test Level 4 - symmetrical) |
| Control deviation (Input data) | < 0.5 % (Static load change 10 % ... 90 %) |
| Output (Conformance/approvals) | 1 kV (Test Level 3 - symmetrical) |
| Protection class (Output data) | I |
| Signal (Conformance/approvals) | 1 kV (Test Level 2 - asymmetrical) |
| Flicker (Conformance/approvals) | EN 61000-3-3 |
| Mounting position (Output data) | horizontal DIN rail NS 35, EN 60715 |
| Voltage (Conformance/approvals) | 2.5 kV |
| (Connection data for signaling) | IEC 62236-5 |
| Comments (Conformance/approvals) | Criterion A |
| Degree of pollution (Dimensions) | 2 |
| Installation height (Dimensions) | ≤ 5000 m (> 2000 m, observe derating) |
| Connection in series (Input data) | yes |
| Degree of protection (Dimensions) | IP20 |
| Frequency (Conformance/approvals) | 50 Hz |
| Shipbuilding approval (Standards) | DNV GL applied for |
| Degree of protection (Output data) | IP20 |
| Typical response time (Input data) | 300 ms (from SLEEP MODE) |
| Connection in parallel (Input data) | Yes, for redundancy and increased capacity |
| Criterion A (Conformance/approvals) | Normal operating behavior within the specified limits. |
| Criterion B (Conformance/approvals) | Temporary impairment to operational behavior that is corrected by the device itself. |
| Criterion C (Conformance/approvals) | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
| Inrush current (Ambient conditions) | typ. 1.5 A (at 25 °C) |
| Nominal output voltage (Input data) | 24 V DC |
| Voltage dip (Conformance/approvals) | 0 % |
| Test level 1 (Conformance/approvals) | 15 Hz 150 Hz (Test Level 4) |
| Test level 2 (Conformance/approvals) | 150 Hz 1.5 kHz (Test Level 4) |
| Test level 3 (Conformance/approvals) | 1.5 kHz 15 kHz (Test Level 4) |
| Test level 4 (Conformance/approvals) | 15 kHz 150 kHz (Test Level 4) |
| Test level 5 (Conformance/approvals) | 16.7 Hz 50 Hz 60 Hz (Test Level 4) |
| Test level 6 (Conformance/approvals) | 16.7 Hz 50 Hz 60 Hz (Test Level 4) |
| Voltage dips (Conformance/approvals) | EN 61000-4-11 |
| Weight per Piece (excluding packing) | 2,780.000 g |
| Noise emission (Conformance/approvals) | EN 55016 |
| Additional text (Conformance/approvals) | Test Level 2 |
| Dynamic Boost (IDyn.Boost) (Input data) | 60 A (5 s) |
| Frequency range (Conformance/approvals) | 0.15 MHz ... 80 MHz |
| Static Boost (IStat.Boost) (Input data) | 45 A |
| Type of protection (Ambient conditions) | Transient surge protection |
| Current consumption (Ambient conditions) | 3x 1.8 A (400 V AC) |
| Discharge in air (Conformance/approvals) | 15 kV (Test Level 4) |
| Feedback voltage resistance (Input data) | ≤ 35 V DC |
| Input voltage range (Ambient conditions) | 3x 400 V AC ... 500 V AC -20 % ... +10 % |
| MTBF (IEC 61709, SN 29500) (Output data) | > 849000 h (25 °C) |
| Nominal output current (IN) (Input data) | 40 A |
| Contact discharge (Conformance/approvals) | 8 kV (Test Level 4) |
| Frequency range (fN) (Ambient conditions) | 50 Hz ... 60 Hz -10 % ... +10 % |
| Harmonic currents (Conformance/approvals) | EN 61000-3-2 |
| Mains buffering time (Ambient conditions) | typ. 28 ms (3x 400 V AC) |
| Number of periods (Conformance/approvals) | 0,5 / 1 / 5 / 50 / 250 periods |
| Power loss nominal load max. (Input data) | < 45 W (400 V AC) |
| Stripping length (Connection data, input) | 10 mm |
| Conductor cross section AWG max. (General) | 10 |
| Conductor cross section AWG min. (General) | 24 |
| Connection method (Connection data, input) | Screw connection |
| Stripping length (Connection data, output) | 8 mm |
| Connection method (Connection data, output) | Push-in connection |
| Insulation voltage input / PE (Output data) | 3.5 kV AC (type test) |
| Power factor (cos phi) (Ambient conditions) | 0.91 |
| Selective Fuse Breaking (ISFB) (Input data) | 215 A (15 ms) |
| Test field strength (Conformance/approvals) | 110 A/m |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Conductor cross section solid max. (General) | 6 mm² |
| Conductor cross section solid min. (General) | 0.2 mm² |
| Discharge current to PE (Ambient conditions) | < 3.5 mA |
| Insulation voltage output / PE (Output data) | 0.5 kV DC (type test) |
| Insulation voltage input/output (Output data) | 4 kV AC (type test) |
| Low Voltage Directive (Conformance/approvals) | Conformance with Low Voltage Directive 2014/35/EC |
| Nominal power consumption (Ambient conditions) | 1217 VA |
| Conductor cross section flexible max. (General) | 4 mm² |
| Conductor cross section flexible min. (General) | 0.2 mm² |
| DNV GL noise radiation (Conformance/approvals) | Class B |
| Electrostatic discharge (Conformance/approvals) | EN 61000-4-2 |
| Fast transients (burst) (Conformance/approvals) | EN 61000-4-4 |
| Signals (test level 1) (Conformance/approvals) | 100 kHz 1 MHz (Test Level 3 - symmetrical) |
| Signals (test level 2) (Conformance/approvals) | 100 kHz 1 MHz (Test Level 3 - asymmetrical) |
| Conducted noise emission (Conformance/approvals) | EN 55016 |
| Electromagnetic HF field (Conformance/approvals) | EN 61000-4-3 |
| Nominal input voltage range (Ambient conditions) | 3x 400 V AC ... 500 V AC |
| Protective circuit/component (Ambient conditions) | Varistor, gas-filled surge arrester |
| Rail applications (Connection data for signaling) | EN 50121-5 |
| Pulse-shape magnetic field (Conformance/approvals) | EN 61000-4-9 |
| Surge voltage load (surge) (Conformance/approvals) | EN 61000-4-5 |
| Attenuated oscillating wave (Conformance/approvals) | EN 61000-4-18 |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Electromagnetic compatibility (Conformance/approvals) | Conformance with EMC Directive 2014/30/EU |
| Input, output (test level 1) (Conformance/approvals) | 100 kHz 1 MHz (Test Level 3 - asymmetrical) |
| Input, output (test level 2) (Conformance/approvals) | 10 MHz |
| DNV GL conducted interference (Conformance/approvals) | Class A |
| Ambient temperature (start-up type tested) (Dimensions) | -40 °C |
| Setting range of the output voltage (USet) (Input data) | 24 V DC ... 29.5 V DC (constant capacity) |
| Conductor cross section AWG max. (Connection data, input) | 6 |
| Conductor cross section AWG min. (Connection data, input) | 20 |
| Damped oscillating magnetic field (Conformance/approvals) | EN 61000-4-10 |
| Conductor cross section AWG max. (Connection data, output) | 16 |
| Conductor cross section AWG min. (Connection data, output) | 24 |
| Conductor cross section solid max. (Connection data, input) | 16 mm² |
| Conductor cross section solid min. (Connection data, input) | 0.5 mm² |
| Max. permissible relative humidity (operation) (Dimensions) | ≤ 95 % (at 25 °C, non-condensing) |
| Maximum power dissipation in no-load condition (Input data) | < 5 W (400 V AC) |
| Conductor cross section solid max. (Connection data, output) | 1 mm² |
| Conductor cross section solid min. (Connection data, output) | 0.2 mm² |
| Mains variation/undervoltage (Connection data for signaling) | SEMI F47-0706; EN 61000-4-11 |
| Standard - Electrical safety (Connection data for signaling) | IEC 60950-1/VDE 0805 (SELV) |
| EMC requirements, power plant (Connection data for signaling) | IEC 61850-3 |
| Recommended breaker for input protection (Ambient conditions) | 3x 4 A ... 20 A (Characteristic B, C, D, K or comparable) |
| Conductor cross section flexible max. (Connection data, input) | 16 mm² |
| Conductor cross section flexible min. (Connection data, input) | 0.5 mm² |
| Conductor cross section flexible max. (Connection data, output) | 1.5 mm² |
| Conductor cross section flexible min. (Connection data, output) | 0.2 mm² |
| Protection against overvoltage at the output (OVP) (Input data) | ≤ 32 V DC |
| Standard - Safety of transformers (Connection data for signaling) | EN 61558-2-16 |
| EMC requirements for noise immunity (Connection data for signaling) | EN 61000-6-1 |
| Asymmetrical conducted disturbance variables (Conformance/approvals) | EN 61000-4-16 |
| Standard – Safety extra-low voltage (Connection data for signaling) | IEC 60950-1 (SELV) |
| Attenuated sinusoidal oscillations (ring wave) (Conformance/approvals) | EN 61000-4-12 |
| Standard – Limitation of mains harmonic currents (Connection data for signaling) | EN 61000-3-2 |
| HART FSK Physical Layer Test Specification Compliance (Connection data for signaling) | Output voltage UOutcompliant |
| Standard - safety for equipment for measurement, control, and laboratory use (Connection data for signaling) | IEC 61010-1 |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations (Connection data for signaling) | EN 50178/VDE 0160 (PELV) |
Technical specifications and performance data