| Parameter | Value |
|---|---|
| GTIN | 4055626231211 |
| Orderkey | 2907719 |
| Catalog page | Page 264 (C-4-2017) |
| Packing unit | 1 pc |
| (Input data) | 20 A (Redundancy) |
| (Output data) | |
| Country of origin | CN (China) |
| Custom tariff number | 85049091 |
| (Ambient conditions) | 1x 60 A (-25°C ... 40°C) |
| Derating (Input data) | 60 °C ... 70 °C (2.5%/K) |
| Screw thread (General) | M4 |
| Efficiency (Output data) | > 97 % |
| Net weight (Output data) | 0.75 kg |
| (Connection data, output) | IECEx KEM 10.0091 |
| Stripping length (General) | 10 mm |
| Climatic class (Dimensions) | 3K3 (in acc. with EN 60721) |
| Connection method (General) | Screw connection |
| Depth (Key Commercial Data) | 125 mm |
| Width (Key Commercial Data) | 50 mm |
| Height (Key Commercial Data) | 130 mm |
| ATEX (Connection data, output) | II 3G Ex nA IIC T4 Gc |
| Protection class (Output data) | III |
| IECEx (Connection data, output) | Ex nA IIC T4 Gc |
| Mounting position (Output data) | horizontal DIN rail NS 35, EN 60715 |
| Shock (Connection data, output) | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Degree of pollution (Dimensions) | 2 |
| Installation height (Dimensions) | ≤ 2000 m |
| Connection in series (Input data) | No |
| Degree of protection (Dimensions) | IP20 |
| Output voltage range (Input data) | 12 V DC ... 24 V DC |
| Degree of protection (Output data) | IP20 |
| Assembly instructions (Output data) | alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
| Weight per Piece (excluding packing) | 953.000 g |
| Screw thread (Connection data, input) | M4 |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| UL approvals (Connection data, output) | UL/C-UL listed UL 508 |
| Input voltage range (Ambient conditions) | 10 V DC ... 30 V DC |
| MTBF (IEC 61709, SN 29500) (Output data) | |
| Nominal output current (IN) (Input data) | 40 A (Increasing power) |
| Power loss nominal load max. (Input data) | 10 W (IOUT= 20 A) |
| Stripping length (Connection data, input) | 10 mm |
| Conductor cross section AWG max. (General) | 6 |
| Conductor cross section AWG min. (General) | 10 |
| Connection method (Connection data, input) | Screw connection |
| Maximum input current (Ambient conditions) | 2x 30 A (-25°C ... 40°C) |
| Nominal input current (Ambient conditions) | 2x 20 A (-25 °C ... 60 °C) |
| Insulation voltage input / PE (Output data) | type test |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Conductor cross section solid max. (General) | 16 mm² |
| Conductor cross section solid min. (General) | 0.5 mm² |
| Insulation voltage input/output (Output data) | type test |
| Conductor cross section flexible max. (General) | 16 mm² |
| Conductor cross section flexible min. (General) | 0.5 mm² |
| Low Voltage Directive (Connection data, output) | Conformance with LV directive 2006/95/EC |
| Vibration (operation) (Connection data, output) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| Nominal input voltage range (Ambient conditions) | 12 V DC ... 24 V DC |
| Standard - Safe isolation (Connection data, output) | DIN VDE 0100-410 |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Standard - Electrical safety (Connection data, output) | EN 60950-1/VDE 0805 (SELV) |
| Electromagnetic compatibility (Connection data, output) | Conformance with EMC Directive 2014/30/EU |
| Conductor cross section AWG max. (Connection data, input) | 6 |
| Conductor cross section AWG min. (Connection data, input) | 10 |
| Conductor cross section solid max. (Connection data, input) | 16 mm² |
| Conductor cross section solid min. (Connection data, input) | 0.5 mm² |
| Max. permissible relative humidity (operation) (Dimensions) | ≤ 95 % (at 25 °C, non-condensing) |
| Conductor cross section flexible max. (Connection data, input) | 16 mm² |
| Conductor cross section flexible min. (Connection data, input) | 0.5 mm² |
| Standard – Safety extra-low voltage (Connection data, output) | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
| Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment (Connection data, output) | EN 50178 |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations (Connection data, output) | EN 50178/VDE 0160 (PELV) |
Technical specifications and performance data
Installation and operation guide