| Parameter | Value |
|---|---|
| GTIN | 4055626246918 |
| Orderkey | 2320539 |
| (Signaling) | UL/C-UL Recognized UL 60950-1 |
| Catalog page | Page 296 (C-4-2017) |
| Packing unit | 1 pc |
| Country of origin | CN (China) |
| Voltage (Signaling) | 10 V |
| Custom tariff number | 85322900 |
| Efficiency (Output data) | > 97 % (with charged energy storage device) |
| Net weight (Output data) | 1.3 kg |
| UL approvals (Signaling) | UL Listed UL 508 |
| Stripping length (General) | 6.5 mm |
| Climatic class (Dimensions) | 3K3 (in acc. with EN 60721) |
| Connection method (General) | Screw connection |
| Depth (Key Commercial Data) | 125 mm |
| Frequency range (Signaling) | 0.15 MHz ... 80 MHz |
| IQ technology (Output data) | no |
| Memory medium (Output data) | Dual layer capacitor |
| Width (Key Commercial Data) | 94 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 130 mm |
| Contact discharge (Signaling) | 4 kV (Test Level 2) |
| Protection class (Output data) | Special application (SELV input voltage, hazardous voltages are generated in the device). |
| Mounting position (Output data) | horizontal DIN rail NS 35, EN 60715 |
| Test field strength (Signaling) | 10 V/m |
| Degree of pollution (Dimensions) | 2 |
| Installation height (Dimensions) | ≤ 4000 m |
| Connection in series (Input data) | No |
| Degree of protection (Dimensions) | IP20 |
| Low Voltage Directive (Signaling) | Conformance with Low Voltage Directive 2014/35/EC |
| Standards/regulations (Signaling) | EN 61000-4-6 |
| Degree of protection (Output data) | IP20 |
| Input voltage (Ambient conditions) | 24 V DC (SELV) |
| Assembly instructions (Output data) | alignable: horizontally 0 mm, vertically 50 mm |
| Connection in parallel (Input data) | no |
| Nominal output voltage (Input data) | 24 V DC |
| Weight per Piece (excluding packing) | 1,474.000 g |
| Output name (Connection data, output) | Transistor output, active |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 25; |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Static Boost (IStat.Boost) (Input data) | 6.25 A |
| Input voltage range (Ambient conditions) | 22.5 V DC ... 30 V DC |
| MTBF (IEC 61709, SN 29500) (Output data) | 1301923 h (40 °C) |
| Nominal output current (IN) (Input data) | 5 A |
| Output voltage (Connection data, output) | 24 V (UN- 1 V (typical)) |
| Standard - Electrical safety (Signaling) | IEC 60950-1/VDE 0805 (SELV) |
| Status display (Connection data, output) | LED |
| Electromagnetic compatibility (Signaling) | Conformance with EMC Directive 2014/30/EU |
| Power loss nominal load max. (Input data) | < 3 W |
| Stripping length (Connection data, input) | 6.5 mm |
| Conductor cross section AWG max. (General) | 12 |
| Conductor cross section AWG min. (General) | 30 |
| Connection method (Connection data, input) | Screw connection |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C (> 40 °C Derating: 1 %/K) |
| Conductor cross section solid max. (General) | 2.5 mm² |
| Conductor cross section solid min. (General) | 0.2 mm² |
| Fixed connect threshold (Ambient conditions) | < 22 V DC |
| Output description (Connection data, output) | floating 13/14 |
| Overvoltage category (EN 60950-1) (Signaling) | I |
| Conductor cross section flexible max. (General) | 2.5 mm² |
| Conductor cross section flexible min. (General) | 0.2 mm² |
| Current consumption (idle) (Ambient conditions) | 0.1 A (No-load) |
| Continuous load current (Connection data, output) | 20 mA |
| Current consumption (maximum) (Ambient conditions) | 7 A (max.) |
| Maximum switching voltage (Connection data, output) | 30 V DC |
| Signalization designation (Connection data, output) | Reference potential for Ready, alarm and remote |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 60 °C |
| Ambient temperature (start-up type tested) (Dimensions) | -40 °C |
| Conductor cross section AWG max. (Connection data, input) | 12 |
| Conductor cross section AWG min. (Connection data, input) | 30 |
| Conductor cross section AWG max. (Connection data, output) | 16 |
| Conductor cross section AWG min. (Connection data, output) | 24 |
| Conductor cross section solid max. (Connection data, input) | 2.5 mm² |
| Conductor cross section solid min. (Connection data, input) | 0.2 mm² |
| Current consumption (charging process) (Ambient conditions) | 0.8 A (charging process) |
| Max. permissible relative humidity (operation) (Dimensions) | ≤ 95 % |
| Conductor cross section solid max. (Connection data, output) | 1.5 mm² |
| Conductor cross section solid min. (Connection data, output) | 0.2 mm² |
| Conductor cross section flexible max. (Connection data, input) | 2.5 mm² |
| Conductor cross section flexible min. (Connection data, input) | 0.2 mm² |
| Conductor cross section flexible max. (Connection data, output) | 1.5 mm² |
| Conductor cross section flexible min. (Connection data, output) | 0.2 mm² |
Technical specifications and performance data