| Parameter | Value |
|---|---|
| 10.5 mA (No load, mains operation) | |
| Time | 195013 h |
| Color | red |
| Depth | 125 mm |
| I/O/S | asymmetrical |
| Input | 2 kV (Test Level 3 - asymmetrical) |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Width | 40 mm |
| Height | 130 mm |
| Output | 2 kV (Test Level 3 - asymmetrical) |
| Signal | 2 kV (Test Level 4 - asymmetrical) |
| Voltage | 10 V (Test Level 3) |
| Comments | Criterion A |
| Derating | 60 °C ... 70 °C (2.5 %/K) |
| Duration | 12 ms (SFB technology) |
| Interface | IFS (Interface system data port) |
| Efficiency | > 98 % (Mains operation, with charged energy storage) |
| Criterion A | Normal operating behavior within the specified limits. |
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
| Hood version | Galvanized sheet steel, free from chrome (VI) |
| Output power | 480 W |
| Product type | DC UPS |
| Screw thread | M4 |
| UL approvals | UL Listed UL 508 |
| Assembly note | alignable: horizontal 5 mm, vertical 50 mm |
| Bridging time | 7200 s |
| Buffer period | 1 h (With battery module 38 AH) |
| IQ technology | Yes |
| Input voltage | 24 V DC |
| Mounting type | DIN rail mounting |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Output voltage | 24 V |
| Product family | QUINT USV |
| Status display | LED |
| Frequency range | 80 MHz ... 1 GHz |
| Type of housing | Aluminum (AlMg3) |
| Article revision | 12 |
| Charging current | 0.2 A ... 5 A |
| Discharge in air | 15 kV (Test Level 4) |
| Housing material | Metal |
| Protection class | III |
| Stripping length | 8 mm |
| Connection method | Screw connection |
| Contact discharge | 8 kV (Test Level 4) |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Power dissipation | 2.7 W (Mains operation) |
| Rail applications | EN 50121-4 |
| Network management | Yes |
| Nominal voltage UN | 24 V DC |
| Output description | Relay (floating) |
| Types of signaling | LED |
| Current consumption | 32.9 A (maximum, mains operation) |
| Input voltage range | 18 V DC ... 30 V DC |
| Test field strength | 20 V/m |
| Connection in series | no |
| Degree of protection | IP20 |
| Output current limit | In mains mode according to connected upstream current limiting device |
| Output voltage range | 18 V DC ... 30 V DC |
| POWER BOOST (IBoost) | 26 A (-25 °C ... 40 °C) |
| End-of-charge voltage | 24 V DC ... 29 V DC (temperature compensated) |
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| Standards/regulations | EN 61000-4-2 |
| Tightening torque max | 0.6 Nm |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| Connection in parallel | yes, up to 2 modules with redundancy module |
| Fixed backup threshold | ≤ 22 V DC |
| Input voltage range DC | 18 V DC ... 30 V DC |
| Nominal capacity range | 3 Ah ... 200 Ah |
| Nominal output voltage | 24 V DC |
| Note on status display | static on |
| Tightening torque, min | 0.5 Nm |
| Continuous load current | ≤ 100 mA |
| Temperature compensation | 42 mV/K (preset) |
| Maximum switching voltage | ≤ 30 V AC/DC |
| Signalization designation | Power In OK |
| MTBF (IEC 61709, SN 29500) | > 500000 h (40 °C) |
| Variable connect threshold | 1 V/0.1 s |
| Nominal input voltage range | 24 V DC |
| Nominal output current (IN) | 20 A (-25 °C ... 50 °C) |
| Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Selective Fuse Breaking (ISFB) | 120 A (-25 °C ... 60 °C) |
| Voltage type of supply voltage | DC |
| Ambient temperature (operation) | -25 °C ... 70 °C |
| Battery presence check (cyclic) | 60 s |
| Insulation voltage input/output | 500 V DC |
| Conductor cross section AWG max. | 10 |
| Conductor cross section AWG min. | 12 |
| Installation distance right/left | 5 mm / 5 mm |
| Installation distance top/bottom | 50 mm / 50 mm |
| Temperature compensation (preset) | 42 mV/K |
| Conductor cross section, rigid max. | 6 mm² |
| Conductor cross section, rigid min. | 0.2 mm² |
| EMC requirements for noise emission | EN 61000-6-3 |
| EMC requirements for noise immunity | EN 61000-6-1 |
| Battery presence check/time interval | 1 min. |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Insulation voltage input, output / housing | 750 V DC |
| Max. permissible relative humidity (operation) | ≤ 95 % (25 °C, non-condensing) |
| Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
| Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Technical specifications and performance data
Installation and operation guide