Service time: Monday to Friday 9:00-18:00
QUINT-UPS/ 24DC/ 24DC/10 - QUINT-UPS/ 24DC/ 24DC/10 2320225 PHOENIX CONTACT Uninterruptible power supply
In Stock Hot Product

QUINT-UPS/ 24DC/ 24DC/10

QUINT-UPS/ 24DC/ 24DC/10 2320225 PHOENIX CONTACT Uninterruptible power supply

$0.00USD
4620 in stock
Key Specifications
:10.4 mA (No load, mains operation)
Time:295585 h
Color:red
Depth:125 mm
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
10.4 mA (No load, mains operation)
Time295585 h
Colorred
Depth125 mm
I/O/Sasymmetrical
Input2 kV (Test Level 3 - asymmetrical)
Shock18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Width35 mm
Height130 mm
Output2 kV (Test Level 3 - asymmetrical)
Signal2 kV (Test Level 4 - asymmetrical)
Voltage10 V (Test Level 3)
CommentsCriterion A
Derating60 °C ... 70 °C (2.5 %/K)
Duration12 ms (SFB technology)
InterfaceIFS (Interface system data port)
Efficiency> 98 % (Mains operation, with charged energy storage)
Criterion ANormal operating behavior within the specified limits.
Criterion BTemporary impairment to operational behavior that is corrected by the device itself.
Hood versionGalvanized sheet steel, free from chrome (VI)
Output power240 W
Product typeDC UPS
Screw threadM4
UL approvalsUL Listed UL 508
Assembly notealignable: horizontal 5 mm, vertical 50 mm
Bridging time10800 s
Buffer period3 h (With battery module 38 AH)
IQ technologyYes
Input voltage24 V DC
Mounting typeDIN rail mounting
Climatic class3K3 (in acc. with EN 60721)
Output voltage24 V
Product familyQUINT USV
Status displayLED
Frequency range80 MHz ... 1 GHz
Type of housingAluminum (AlMg3)
Article revision12
Charging current0.2 A ... 2.88 A
Discharge in air15 kV (Test Level 4)
Housing materialMetal
Protection classIII
Stripping length7 mm
Connection methodPluggable screw connection
Contact discharge8 kV (Test Level 4)
Mounting positionhorizontal DIN rail NS 35, EN 60715
Power dissipation2.6 W (Mains operation)
Rail applicationsEN 50121-4
Network managementYes
Nominal voltage UN24 V DC
Output descriptionRelay (floating)
Types of signalingLED
Current consumption19 A (maximum, mains operation)
Input voltage range18 V DC ... 30 V DC
Test field strength20 V/m
Connection in seriesno
Degree of protectionIP20
Output current limitIn mains mode according to connected upstream current limiting device
Output voltage range18 V DC ... 30 V DC
POWER BOOST (IBoost)15 A (-25 °C ... 40 °C)
End-of-charge voltage24 V DC ... 29 V DC (temperature compensated)
Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
Standards/regulationsEN 61000-4-2
Tightening torque max0.6 Nm
Vibration (operation)< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Connection in parallelyes, up to 2 modules with redundancy module
Fixed backup threshold≤ 22 V DC
Input voltage range DC18 V DC ... 30 V DC
Nominal capacity range1.3 Ah ... 140 Ah
Nominal output voltage24 V DC
Note on status displaystatic on
Tightening torque, min0.5 Nm
Continuous load current≤ 100 mA
Temperature compensation42 mV/K (preset)
Maximum switching voltage≤ 30 V AC/DC
Signalization designationPower In OK
MTBF (IEC 61709, SN 29500)> 500000 h (40 °C)
Variable connect threshold1 V/0.1 s
Nominal input voltage range24 V DC
Nominal output current (IN)10 A (-25 °C ... 50 °C)
Standard - Electrical safetyEN 60950-1/VDE 0805 (SELV)
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Selective Fuse Breaking (ISFB)60 A (-25 °C ... 60 °C)
Voltage type of supply voltageDC
Ambient temperature (operation)-25 °C ... 70 °C
Battery presence check (cyclic)60 s
Insulation voltage input/output500 V DC
Conductor cross section AWG max.12
Conductor cross section AWG min.16
Installation distance right/left5 mm / 5 mm
Installation distance top/bottom50 mm / 50 mm
Temperature compensation (preset)42 mV/K
Conductor cross section, rigid max.2.5 mm²
Conductor cross section, rigid min.0.2 mm²
EMC requirements for noise emissionEN 61000-6-3
EMC requirements for noise immunityEN 61000-6-1
Battery presence check/time interval1 min.
Conductor cross section flexible max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Ambient temperature (storage/transport)-40 °C ... 85 °C
Insulation voltage input, output / housing750 V DC
Max. permissible relative humidity (operation)≥ 95 % (25 °C, non-condensing)
Emitted radio interference in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential
Radio interference voltage in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installationsEN 50178/VDE 0160 (PELV)

Product Description

Uninterruptible power supply with IQ technology for rail mounting, input: 24 V DC, output: 24 V DC/10 A, including universal adapter for UTA 107/30 rail mounted
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top