| Parameter | Value |
|---|---|
| GTIN | 4046356731515 |
| Orderkey | 2320461 |
| Catalog page | Page 276 (C-4-2017) |
| Packing unit | 1 pc |
| Country of origin | CN (China) |
| Custom tariff number | 85371091 |
| Screw thread (General) | M4 |
| Stripping length (General) | 7 mm |
| Climatic class (Dimensions) | 3K3 (in acc. with EN 60721) |
| Connection method (General) | Pluggable screw connection |
| Depth (Key Commercial Data) | 125 mm |
| Width (Key Commercial Data) | 35 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 130 mm |
| (Connection data for signaling) | 15 Hz ... 150 Hz, 2.3g tv= 90 min. |
| Net weight (General output data) | 0.6 kg |
| Degree of protection (Dimensions) | IP20 |
| POWER BOOST (IBoost) (Input data) | 15 A (-25°C ... 40°C) |
| Input voltage (Ambient conditions) | 24 V DC |
| IQ technology (General output data) | Yes |
| Nominal output voltage (Input data) | 24 V DC |
| Weight per Piece (excluding packing) | 744.800 g |
| Screw thread (Connection data, input) | M4 |
| Shock (Connection data for signaling) | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 25; |
| Protection class (General output data) | III |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Screw thread (Connection data, output) | M4 |
| Mounting position (General output data) | horizontal DIN rail NS 35, EN 60715 |
| Voltage (Connection data for signaling) | 10 V (Test Level 3) |
| Comments (Connection data for signaling) | Criterion B |
| Input voltage range (Ambient conditions) | 18 V DC ... 30 V DC |
| Nominal output current (IN) (Input data) | 10 A (-25 °C ... 60 °C) |
| Stripping length (Connection data, input) | 7 mm |
| Conductor cross section AWG max. (General) | 12 |
| Conductor cross section AWG min. (General) | 16 |
| Connection method (Connection data, input) | Pluggable screw connection |
| Nominal input voltage (Ambient conditions) | 18 V DC ... 30 V DC |
| Stripping length (Connection data, output) | 7 mm |
| Assembly instructions (General output data) | alignable: horizontal 5 mm, vertical 50 mm |
| Connection method (Connection data, output) | Pluggable screw connection |
| Selective Fuse Breaking (ISFB) (Input data) | 60 A (-25 °C ... 60 °C) |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 70 °C |
| Conductor cross section solid max. (General) | 2.5 mm² |
| Conductor cross section solid min. (General) | 0.2 mm² |
| Fixed connect threshold (Ambient conditions) | ≤ 22 V DC |
| UL approvals (Connection data for signaling) | UL Listed UL 508 |
| Noise immunity (Connection data for signaling) | EN 61000-6-2:2005 |
| Conductor cross section flexible max. (General) | 2.5 mm² |
| Conductor cross section flexible min. (General) | 0.2 mm² |
| Frequency range (Connection data for signaling) | 0.15 MHz ... 80 MHz |
| Variable connect threshold (Ambient conditions) | 1 V/0.1 s |
| MTBF (IEC 61709, SN 29500) (General output data) | > 652000 h (40 °C) |
| Contact discharge (Connection data for signaling) | 4 kV (Test Level 2) |
| Rail applications (Connection data for signaling) | EN 50121-4 |
| Current consumption (maximum) (Ambient conditions) | 16 A (maximum, mains operation) |
| Test field strength (Connection data for signaling) | 3 V/m |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Depth with alternative assembly (Key Commercial Data) | 39 mm |
| Low Voltage Directive (Connection data for signaling) | Conformance with LV directive 2006/95/EC |
| Standards/regulations (Connection data for signaling) | EN 61000-6-3 |
| Vibration (operation) (Connection data for signaling) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| Width with alternative assembly (Key Commercial Data) | 123 mm |
| Height with alternative assembly (Key Commercial Data) | 130 mm |
| Conductor cross section AWG max. (Connection data, input) | 12 |
| Conductor cross section AWG min. (Connection data, input) | 16 |
| Conductor cross section AWG max. (Connection data, output) | 12 |
| Conductor cross section AWG min. (Connection data, output) | 24 |
| Conductor cross section solid max. (Connection data, input) | 2.5 mm² |
| Conductor cross section solid min. (Connection data, input) | 0.2 mm² |
| Current consumption (charging process) (Ambient conditions) | 4 A (Charging, mains operation) |
| Max. permissible relative humidity (operation) (Dimensions) | ≤ 95 % (25 °C, non-condensing) |
| Conductor cross section solid max. (Connection data, output) | 2.5 mm² |
| Conductor cross section solid min. (Connection data, output) | 0.2 mm² |
| Efficiency 12 V DC (Output data (12 V DC battery operation)) | > 93 % (Mains operation, with charged energy storage) |
| Efficiency 24 V DC (Output data (12 V DC battery operation)) | > 98 % (Mains operation, with charged energy storage) |
| POWER BOOST (IBoost) (Output data (12 V DC mains operation)) | 15 A (-25°C ... 40°C) |
| POWER BOOST (IBoost) (Output data (24 V DC mains operation)) | 7.5 A (-25°C ... 40°C) |
| Standard - Electrical safety (Connection data for signaling) | EN 60950-1/VDE 0805 (SELV) |
| Electromagnetic compatibility (Connection data for signaling) | Conformance with EMC Directive 2014/30/EU |
| Conductor cross section flexible max. (Connection data, input) | 2.5 mm² |
| Conductor cross section flexible min. (Connection data, input) | 0.2 mm² |
| Nominal output voltage (Output data (12 V DC mains operation)) | 24 V DC |
| Nominal output voltage (Output data (24 V DC mains operation)) | 12 V DC |
| POWER BOOST (IBoost) (Output data (24 V DC battery operation)) | 7.5 A (-25°C ... 40°C) |
| Conductor cross section flexible max. (Connection data, output) | 2.5 mm² |
| Conductor cross section flexible min. (Connection data, output) | 0.2 mm² |
| Connection in acc. with standard (Connection data for signaling) | CUL |
| Nominal output voltage (Output data (24 V DC battery operation)) | 12 V DC |
| Output voltage range (depends on the input voltage) (Input data) | 18 V DC ... 30 V DC (UOUT= UIN- 0.5 V DC) |
| Total power P12V+ P24V (Output data (12 V DC battery operation)) | max. 360 W |
| Nominal output current (IN) (Output data (12 V DC mains operation)) | 10 A (-25 °C ... 60 °C) |
| Nominal output current (IN) (Output data (24 V DC mains operation)) | 5 A (-25 °C ... 60 °C) |
| Nominal output current (IN) (Output data (24 V DC battery operation)) | 5 A (-25 °C ... 60 °C) |
| Selective Fuse Breaking (ISFB) (Output data (12 V DC mains operation)) | 65 A (-25 °C ... 60 °C) |
| Output voltage range (depends on the input voltage) (Output data (12 V DC mains operation)) | 19.2 V DC ... 27.6 V DC (UOUT= UBAT- 0.5 V DC) |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations (Connection data for signaling) | EN 50178/VDE 0160 (PELV) |
Technical specifications and performance data
Installation and operation guide