| Parameter | Value |
|---|---|
| 450 V DC ... 800 V DC | |
| Depth | 130 mm |
| Width | 240 mm |
| Height | 130 mm |
| Efficiency | > 92 % |
| Input fuse | Externally via 3 circuit breakers 6 A, 10 A or 16 A, characteristic B |
| Output power | 720 W |
| Product type | Power supply |
| Screw thread | M3 |
| Assembly note | alignable: vertical with spacing = 5 cm |
| Inrush current | < 15 A (typical) |
| Noise emission | EN 55011 (EN 55022) |
| Output voltage | + 24 V DC (Signal) |
| Product family | QUINT POWER |
| Status display | Green LED (Uout< 0.9 x UN: LED flashes) |
| Residual ripple | < 100 mVPP |
| Type of housing | AluNox (AlMg1) |
| Housing material | Metal |
| Number of phases | 3.00 |
| Protection class | I (with PE connection) |
| Stripping length | 8 mm |
| Connection method | Screw connection |
| Mounting position | On horizontal DIN rail NS 35 in acc. with EN 60715 |
| AC frequency range | 45 Hz ... 65 Hz |
| Frequency range DC | 0 Hz |
| Output description | UOUT> 0.9 x UN: High signal |
| Current consumption | approx. 3x 2.1 A (400 V AC) |
| Input voltage range | 3x 320 V AC ... 575 V AC (for all three phases) |
| Connection in series | yes |
| Degree of protection | IP20 |
| Mains buffering time | > 20 ms (at 3 x 400 V AC) |
| POWER BOOST (IBoost) | 35 A |
| Typical response time | < 1 s |
| Connection in parallel | yes, for assembling redundant systems and increasing efficiency |
| Input voltage range AC | 3x 320 V AC ... 575 V AC (for all three phases) |
| Input voltage range DC | 450 V DC ... 800 V DC |
| Maximum inrush current | ≤ 1 A |
| Nominal output voltage | 24 V DC ±1 % |
| Continuous load current | max. 40 mA |
| Maximum switching voltage | ≤ 30 V AC/DC |
| Nominal power consumption | 720 W |
| Operating voltage display | Green LED |
| Standard - Safe isolation | DIN VDE 0100-410 |
| MTBF (IEC 61709, SN 29500) | > 500000 h |
| Nominal input voltage range | 3x 400 V AC ... 500 V AC |
| Nominal output current (IN) | 30 A (up to 60 °C) |
| Power loss nominal load max. | < 62 W |
| Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
| Electromagnetic compatibility | Conformance with EMC directive 89/336/EC |
| Voltage type of supply voltage | AC/DC |
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
| Insulation voltage input/output | 2 kV (routine test) |
| Conductor cross section AWG max. | 10 |
| Conductor cross section AWG min. | 24 |
| Maximum no-load power dissipation | < 14 W |
| Conductor cross section, rigid max. | 6 mm² |
| Conductor cross section, rigid min. | 0.2 mm² |
| EMC requirements for noise immunity | EN 61000-6-2 |
| Peak switching voltages nominal load | < 100 mVPP(20 MHz) |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Setting range of the output voltage (USet) | 22.5 V ... 28.5 V |
| Max. permissible relative humidity (operation) | 95 % (at 25 °C, non-condensing) |
Technical specifications and performance data