| Parameter | Value |
|---|---|
| GTIN | 4046356693646 |
| Orderkey | 2320555 |
| Catalog page | Page 254 (C-4-2017) |
| Packing unit | 1 pc |
| (Input data) | < 0.1 % (change in input voltage ±10 %) |
| (Output data) | |
| Country of origin | CN (China) |
| Custom tariff number | 85044030 |
| Derating (Input data) | 60 °C ... 70 °C (2.5%/K) |
| Screw thread (General) | M3 |
| Efficiency (Output data) | > 92 % |
| Net weight (Output data) | 0.9 kg |
| Stripping length (General) | 8 mm |
| Climatic class (Dimensions) | 3K3 (in acc. with EN 60721) |
| Connection method (General) | Pluggable screw connection |
| Depth (Key Commercial Data) | 125 mm |
| Width (Key Commercial Data) | 48 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 130 mm |
| Residual ripple (Input data) | < 20 mVPP |
| Control deviation (Input data) | < 1 % (change in load, static 10 % ... 90 %) |
| Protection class (Output data) | III |
| Input fuse (Ambient conditions) | 25 A (device protection) |
| Mounting position (Output data) | horizontal DIN rail NS 35, EN 60715 |
| (Connection data for signaling) | IECEx TUN 13.0007 X |
| Degree of pollution (Dimensions) | 2 |
| Feedback resistance (Input data) | 35 V DC |
| Connection in series (Input data) | yes |
| Degree of protection (Dimensions) | IP20 |
| Max. capacitive load (Input data) | unlimited |
| POWER BOOST (IBoost) (Input data) | 12.5 A (-25°C ... 40°C permanent, UOUT= 24 V DC ) |
| Degree of protection (Output data) | IP20 |
| Assembly instructions (Output data) | alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
| Connection in parallel (Input data) | Yes, for redundancy and increased capacity |
| Nominal output voltage (Input data) | 24 V DC ±1 % |
| ATEX (Connection data for signaling) | II 3 G Ex ec nC IIC T4 Gc |
| Mains buffering (Ambient conditions) | typ. 12 ms (24 V DC) |
| Weight per Piece (excluding packing) | 900.000 g |
| IECEx (Connection data for signaling) | Ex ec nC IIC T4 Gc |
| Screw thread (Connection data, input) | M3 |
| Shock (Connection data for signaling) | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Active current limitation (Input data) | Approx. 18 A |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 25; |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Screw thread (Connection data, output) | M3 |
| Type of protection (Ambient conditions) | Transient surge protection |
| Voltage (Connection data for signaling) | 10 V (Test Level 3) |
| Comments (Connection data for signaling) | Criterion B |
| Current consumption (Ambient conditions) | 14 A (24 V, IBOOST) |
| Input voltage range (Ambient conditions) | 18 V DC ... 32 V DC |
| MTBF (IEC 61709, SN 29500) (Output data) | |
| Nominal output current (IN) (Input data) | 10 A (-25 °C ... 60 °C) |
| Inrush surge current (Ambient conditions) | typ. 15 A |
| Power loss nominal load max. (Input data) | 24 W |
| Stripping length (Connection data, input) | 7 mm |
| Conductor cross section AWG max. (General) | 12 |
| Conductor cross section AWG min. (General) | 24 |
| Connection method (Connection data, input) | Pluggable screw connection |
| Selective Fuse Breaking (ISFB) (Input data) | 60 A (12 ms) |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 70 °C (> 60 °C derating, 2.5 %/K, startup at -40°C type-tested) |
| Conductor cross section solid max. (General) | 2.5 mm² |
| Conductor cross section solid min. (General) | 0.2 mm² |
| UL approvals (Connection data for signaling) | UL/C-UL listed UL 508 |
| Insulation voltage input/output (Output data) | 1.5 kV (type test) |
| Noise immunity (Connection data for signaling) | EN 61000-6-2:2005 |
| Conductor cross section flexible max. (General) | 2.5 mm² |
| Conductor cross section flexible min. (General) | 0.2 mm² |
| Frequency range (Connection data for signaling) | 0.15 MHz ... 80 MHz |
| Nominal input voltage range (Ambient conditions) | 24 V DC |
| Contact discharge (Connection data for signaling) | 4 kV (Test Level 2) |
| Peak switching voltages nominal load (Input data) | < 10 mVPP(20 MHz) |
| Protective circuit/component (Ambient conditions) | Varistor |
| Rail applications (Connection data for signaling) | EN 50121-4 |
| Test field strength (Connection data for signaling) | 3 V/m |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Depth with alternative assembly (Key Commercial Data) | 51 mm |
| Shipbuilding approval (Connection data for signaling) | DNV GL (EMC B) |
| Standards/regulations (Connection data for signaling) | EN 61000-6-3 |
| Vibration (operation) (Connection data for signaling) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| Width with alternative assembly (Key Commercial Data) | 122 mm |
| Height with alternative assembly (Key Commercial Data) | 130 mm |
| Ambient temperature (start-up type tested) (Dimensions) | -40 °C |
| Setting range of the output voltage (USet) (Input data) | 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted) |
| Choice of suitable circuit breakers (Ambient conditions) | 16 A ... 20 A (Characteristics B, C, D, K) |
| Conductor cross section AWG max. (Connection data, input) | 12 |
| Conductor cross section AWG min. (Connection data, input) | 24 |
| Standard - Safe isolation (Connection data for signaling) | DIN VDE 0100-410 |
| Conductor cross section AWG max. (Connection data, output) | 12 |
| Conductor cross section AWG min. (Connection data, output) | 24 |
| Conductor cross section solid max. (Connection data, input) | 2.5 mm² |
| Conductor cross section solid min. (Connection data, input) | 0.2 mm² |
| Max. permissible relative humidity (operation) (Dimensions) | 100 % (at 25 °C, non-condensing) |
| Maximum power dissipation in no-load condition (Input data) | 1.6 W |
| Protection against surge voltage on the output (Input data) | < 35 V DC |
| Conductor cross section solid max. (Connection data, output) | 2.5 mm² |
| Conductor cross section solid min. (Connection data, output) | 0.2 mm² |
| Standard - Electrical safety (Connection data for signaling) | EN 60950-1/VDE 0805 (SELV) |
| Electromagnetic compatibility (Connection data for signaling) | Conformance with EMC Directive 2014/30/EU |
| Conductor cross section flexible max. (Connection data, input) | 2.5 mm² |
| Conductor cross section flexible min. (Connection data, input) | 0.2 mm² |
| Conductor cross section flexible max. (Connection data, output) | 2.5 mm² |
| Conductor cross section flexible min. (Connection data, output) | 0.2 mm² |
| Connection in acc. with standard (Connection data for signaling) | CUL |
| Standard – Safety extra-low voltage (Connection data for signaling) | EN 60950-1 (SELV) |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations (Connection data for signaling) | EN 50178/VDE 0160 (PELV) |
Technical specifications and performance data
Installation and operation guide