Service time: Monday to Friday 9:00-18:00
QUINT-PS/12DC/24DC/ 5 - QUINT-PS/12DC/24DC/ 5 2320131 PHOENIX CONTACT DC/DC converters
In Stock Hot Product

QUINT-PS/12DC/24DC/ 5

QUINT-PS/12DC/24DC/ 5 2320131 PHOENIX CONTACT DC/DC converters

$0.00USD
4167 in stock
Key Specifications
:< 2 % (change in load, dynamic 10 % ... 90 %)
Color:green
Depth:125 mm
I/O/S:asymmetrical
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
< 2 % (change in load, dynamic 10 % ... 90 %)
Colorgreen
Depth125 mm
I/O/Sasymmetrical
Input2 kV (Test Level 3 - asymmetrical)
Shock18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Width32 mm
Height130 mm
Output2 kV (Test Level 3 - asymmetrical)
Signal1 kV (Test Level 4 - asymmetrical)
Voltage10 V (Test Level 3)
CommentsCriterion B
Derating60 °C ... 70 °C (2.5 %/K)
Rise time< 2 ms (UOUT(10 % ... 90 %))
Efficiency> 90 %
Input fuse25 A (internal (device protection))
Criterion ANormal operating behavior within the specified limits.
Criterion BTemporary impairment to operational behavior that is corrected by the device itself.
Hood versionGalvanized sheet steel, free from chrome (VI)
Output power120 W
Screw threadM3
UL approvalsUL/C-UL listed UL 508
Assembly notealignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
Mounting typeDIN rail mounting
Climatic class3K3 (in acc. with EN 60721)
Inrush current< 15 A (typical)
Product familyQUINT POWER
Status display"DC OK" LED green
Frequency range80 MHz ... 1 GHz
Residual ripple< 75 mVPP
Type of housingAluminum (AlMg3)
Article revision04
Discharge in air15 kV (Test Level 4)
Housing materialMetal
Number of phases1.00
Protection classIII
Stripping length8 mm
Wide-range inputno
Connection methodScrew connection
Contact discharge8 kV (Test Level 4)
Control deviation< 1 % (change in load, static 10 % ... 90 %)
Mounting positionhorizontal DIN rail NS 35, EN 60715
Rail applicationsEN 50121-4
Output descriptionUOUT> 0.9 x UN: High signal
Protective circuitTransient surge protection; Varistor
Types of signalingLED
Current consumption15 A (12 V, IBOOST)
Degree of pollution2
Input voltage range9 V DC ... 18 V DC
Test field strength20 V/m (Test Level 3)
Connection in seriesyes
Degree of protectionIP20
Mains buffering timetyp. 3 ms (12 V DC)
Max. capacitive loadunlimited
POWER BOOST (IBoost)6.25 A (-25 °C ... 40 °C permanent, UOUT= 24 V DC )
Output characteristicU/I
Standards/regulationsEN 61000-4-2
Tightening torque max0.6 Nm
Vibration (operation)< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Connection in parallelyes, for redundancy and increased capacity
Input voltage range DC9 V DC ... 18 V DC
Maximum inrush current< 20 mA (short-circuit-proof)
Nominal output voltage24 V DC ±1 %
Note on status displayLED on
Tightening torque, min0.5 Nm
Switching voltage range18 V DC ... 24 V DC
With protective coatingno
Active current limitationApproximately 6.9 A
Standard - Safe isolationDIN VDE 0100-410
MTBF (IEC 61709, SN 29500)> 1005000 h (40 °C)
Feedback voltage resistance35 V DC
Nominal input voltage range12 V DC
Nominal output current (IN)5 A (-25 °C ... 60 °C)
Reverse polarity protection≤ 30 V DC
Power loss nominal load max.13.5 W
Standard - Electrical safetyEN 60950-1/VDE 0805 (SELV)
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Inrush current integral (I2t)< 0.3 A2s
Selective Fuse Breaking (ISFB)30 A (12 ms)
Voltage type of supply voltageDC
Ambient temperature (operation)-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Insulation voltage input/output1.5 kV (type test)
Conductor cross section AWG max.12
Conductor cross section AWG min.18
Installation distance right/left0 mm / 0 mm (≤ 70 °C)
Installation distance top/bottom50 mm / 50 mm (≤ 70 °C)
Magnetic circuit breaker trippingB2 / B4 / C2
Maximum no-load power dissipation2 W
Conductor cross section, rigid max.2.5 mm²
Conductor cross section, rigid min.0.2 mm²
EMC requirements for noise emissionEN 61000-6-3
EMC requirements for noise immunityEN 61000-6-1
Peak switching voltages nominal load< 10 mVPP(20 MHz)
Conductor cross section flexible max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Standard – Safety extra-low voltageEN 60950-1 (SELV)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Installation distance right/left (active)15 mm / 15 mm (≤ 70 °C)
Installation distance top/bottom (active)50 mm / 50 mm (≤ 70 °C)
Ambient temperature (start-up type tested)-40 °C
Setting range of the output voltage (USet)18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Max. permissible relative humidity (operation)≤ 95 % (at 25 °C, non-condensing)
Emitted radio interference in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential
Radio interference voltage in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential
Protection against overvoltage at the output (OVP)< 35 V DC
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installationsEN 50178/VDE 0160 (PELV)

Product Description

Primary switched QUINT DC/DC transformer for rail mounting with SFB (Selective Fuse Breaking) technology, input: 12 V DC, output: 24 V DC/5 A
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top