| Parameter | Value |
|---|---|
| GTIN | 4046356013178 |
| Orderkey | 2938248 |
| (Signaling) | 15 Hz ... 150 Hz, 2.3g, 90 min. |
| Catalog page | Page 484 (IF-2007) |
| Packing unit | 1 pc |
| (Input data) | < 0.1 % (change in input voltage ±10 %) |
| (Output data) | 2 kV AC (routine test) |
| Country of origin | TH (Thailand) |
| Shock (Signaling) | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Voltage (Signaling) | 10 V |
| Comments (Signaling) | Criterion B |
| Custom tariff number | 85044030 |
| (Ambient conditions) | > 35 ms (230 V AC) |
| Derating (Input data) | 60 °C (2.5%/K) |
| Screw thread (General) | M3 |
| Efficiency (Output data) | > 90 % |
| Net weight (Output data) | 2.5 kg |
| UL approvals (Signaling) | UL/C-UL listed UL 508 |
| Output power (Input data) | 480 W |
| Noise immunity (Signaling) | EN 61000-6-2:2005 |
| Stripping length (General) | 7 mm |
| Climatic class (Dimensions) | 3K3 (in acc. with EN 60721) |
| Connection method (General) | Screw connection |
| Depth (Key Commercial Data) | 125 mm |
| Frequency range (Signaling) | 0.15 MHz ... 80 MHz |
| Width (Key Commercial Data) | 157 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 130 mm |
| Residual ripple (Input data) | < 20 mVPP(with nominal values) |
| Contact discharge (Signaling) | 8 kV |
| Control deviation (Input data) | < 1 % (change in load, static 10 % ... 90 %) |
| Protection class (Output data) | I (with PE connection) |
| Input fuse (Ambient conditions) | 12 A (slow-blow, internal) |
| Mounting position (Output data) | horizontal DIN rail NS 35, EN 60715 |
| Test field strength (Signaling) | 10 V/m |
| Degree of pollution (Dimensions) | 2 |
| Feedback resistance (Input data) | 60 V DC |
| Connection in series (Input data) | yes |
| Degree of protection (Dimensions) | IP20 |
| Max. capacitive load (Input data) | unlimited |
| POWER BOOST (IBoost) (Input data) | 13 A |
| Shipbuilding approval (Signaling) | DNV GL (EMC A), ABS |
| Standards/regulations (Signaling) | EN 61000-4-11 |
| Vibration (operation) (Signaling) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| Degree of protection (Output data) | IP20 |
| Typical response time (Input data) | < 1 s |
| Assembly instructions (Output data) | alignable: horizontally 0 mm, vertically 50 mm |
| Connection in parallel (Input data) | Yes, for redundancy and increased capacity |
| Nominal output voltage (Input data) | 48 V DC ±1 % |
| Mains buffering (Ambient conditions) | > 30 ms (120 V AC) |
| Weight per Piece (excluding packing) | 2,500.000 g |
| Output name (Connection data, output) | DC OK floating |
| Screw thread (Connection data, input) | M4 |
| Standard - Safe isolation (Signaling) | DIN VDE 0100-410 |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 25; |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Screw thread (Connection data, output) | M4 |
| AC frequency range (Ambient conditions) | 45 Hz ... 65 Hz |
| Frequency range DC (Ambient conditions) | 0 Hz |
| Standard - Equipment safety (Signaling) | GS (tested safety) |
| Type of protection (Ambient conditions) | Transient surge protection |
| Current consumption (Ambient conditions) | approx. 4.76 A (120 V AC) |
| Input voltage range (Ambient conditions) | 85 V AC ... 264 V AC |
| MTBF (IEC 61709, SN 29500) (Output data) | > 500000 h |
| Nominal output current (IN) (Input data) | 10 A (up to 60°C) |
| Output voltage (Connection data, output) | + 24 V DC |
| Standard - Electrical safety (Signaling) | EN 60950-1/VDE 0805 (SELV) |
| Status display (Connection data, output) | "DC OK" LED green |
| Electromagnetic compatibility (Signaling) | Conformance with EMC directive 89/336/EC |
| Inrush surge current (Ambient conditions) | < 15 A (3.2 A2s) |
| Power loss nominal load max. (Input data) | < 56 W |
| Stripping length (Connection data, input) | 7 mm |
| Conductor cross section AWG max. (General) | 10 |
| Conductor cross section AWG min. (General) | 24 |
| Connection method (Connection data, input) | Screw connection |
| Insulation voltage input / PE (Output data) | 3.5 kV AC (type test) |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Conductor cross section solid max. (General) | 6 mm² |
| Conductor cross section solid min. (General) | 0.2 mm² |
| Connection in acc. with standard (Signaling) | CUL |
| Discharge current to PE (Ambient conditions) | < 3.5 mA |
| Insulation voltage output / PE (Output data) | 500 V DC (routine test) |
| Output description (Connection data, output) | Relay contact, UOUT> 0.9 x UN: Contact closed |
| Insulation voltage input/output (Output data) | 4 kV AC (type test) |
| Overvoltage category (EN 62477-1) (Signaling) | III |
| Standard - Safety of transformers (Signaling) | EN 61558-2-17 |
| Nominal power consumption (Ambient conditions) | 524 W |
| Conductor cross section flexible max. (General) | 4 mm² |
| Conductor cross section flexible min. (General) | 0.2 mm² |
| Tightening torque max (Connection data, output) | 1.5 Nm |
| Maximum inrush current (Connection data, output) | ≤ 1 A |
| Nominal input voltage range (Ambient conditions) | 100 V AC ... 240 V AC |
| Note on status display (Connection data, output) | UOUT< 0.9 x UN: LED flashing |
| Tightening torque, min (Connection data, output) | 1.2 Nm |
| Continuous load current (Connection data, output) | ≤ 1 A |
| Peak switching voltages nominal load (Input data) | < 50 mVPP |
| Protective circuit/component (Ambient conditions) | Varistor |
| Standard – Safety extra-low voltage (Signaling) | EN 60950-1 (SELV) |
| Maximum switching voltage (Connection data, output) | ≤ 30 V AC/DC |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Depth with alternative assembly (Key Commercial Data) | 160 mm |
| Width with alternative assembly (Key Commercial Data) | 122 mm |
| Height with alternative assembly (Key Commercial Data) | 130 mm |
| Setting range of the output voltage (USet) (Input data) | 30 V DC ... 56 V DC |
| Choice of suitable circuit breakers (Ambient conditions) | 10 A ... 16 A (Characteristics B, C, D, K) |
| Conductor cross section AWG max. (Connection data, input) | 6 |
| Conductor cross section AWG min. (Connection data, input) | 20 |
| Conductor cross section AWG max. (Connection data, output) | 6 |
| Conductor cross section AWG min. (Connection data, output) | 20 |
| Conductor cross section solid max. (Connection data, input) | 16 mm² |
| Conductor cross section solid min. (Connection data, input) | 0.5 mm² |
| Max. permissible relative humidity (operation) (Dimensions) | 95 % (at 25 °C, non-condensing) |
| Maximum power dissipation in no-load condition (Input data) | < 5 W |
| Protection against surge voltage on the output (Input data) | ≤ 60 V DC |
| Conductor cross section solid max. (Connection data, output) | 16 mm² |
| Conductor cross section solid min. (Connection data, output) | 0.5 mm² |
| Conductor cross section flexible max. (Connection data, input) | 10 mm² |
| Conductor cross section flexible min. (Connection data, input) | 0.5 mm² |
| Standard – Limitation of mains harmonic currents (Signaling) | EN 61000-3-2 |
| Conductor cross section flexible max. (Connection data, output) | 10 mm² |
| Conductor cross section flexible min. (Connection data, output) | 0.5 mm² |
| Information technology equipment - safety (CB scheme) (Signaling) | CB Scheme |
| Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment (Signaling) | EN 50178 |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations (Signaling) | EN 50178/VDE 0160 (PELV) |
Technical specifications and performance data
Installation and operation guide