| Parameter | Value |
|---|---|
| 90 V DC ... 350 V DC (Derating < 110 V DC: 2.5%/V) | |
| Depth | 125 mm |
| I/O/S | Level 3 - asymmetrical |
| Input | 4 kV (level 4 - asymmetrical) |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Width | 240 mm |
| Height | 130 mm |
| Output | 2 kV (Level 3 - asymmetrical) |
| Signal | 1 kV (Level 2 - asymmetrical) |
| Housing | Level 4 |
| Voltage | 10 V |
| Comments | Criterion B |
| Derating | 60 °C ... 70 °C (2.5 %/K) |
| Rise time | < 2 ms (UOUT(10 % ... 90 %)) |
| EN 62477-1 | III |
| Efficiency | > 92 % (for 230 V AC and nominal values) |
| Input fuse | 20 A (fast blow, internal) |
| Output power | 960 W |
| Product type | Power supply |
| Screw thread | M3 |
| UL approvals | UL/C-UL listed UL 508 |
| Assembly note | alignable: horizontally 0 mm, vertically 50 mm |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Inrush current | < 15 A (typical) |
| Noise emission | EN 55011 (EN 55022) |
| Output voltage | + 24 V DC (Signal) |
| Product family | QUINT POWER |
| Status display | "DC OK" LED green |
| Frequency range | 80 MHz ... 1 GHz |
| Residual ripple | < 30 mVPP(with nominal values) |
| Type of housing | AluNox (AlMg1) |
| Article revision | 05 |
| Discharge in air | 15 kV |
| Housing material | Metal |
| Number of phases | 1.00 |
| Protection class | I (with PE connection) |
| Stripping length | 7 mm |
| Connection method | Screw connection |
| Contact discharge | 8 kV |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Power dissipation | 80 W (Maximum, nominal load) |
| AC frequency range | 45 Hz ... 65 Hz |
| Frequency range DC | 0 Hz |
| Output description | UOUT> 0.9 x UN: High signal |
| Protective circuit | Transient surge protection; Varistor |
| Types of signaling | LED |
| Current consumption | approx. 12.5 A (120 V AC) |
| Degree of pollution | 2 |
| Input voltage range | 85 V AC ... 264 V AC (Derating < 100 V DC: 2.5%/V) |
| Test field strength | 10 V/m |
| Connection in series | yes |
| Degree of protection | IP20 |
| Mains buffering time | > 20 ms (120 V AC) |
| Max. capacitive load | unlimited |
| POWER BOOST (IBoost) | 45 A (-25 °C ... 40 °C permanent) |
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| Shipbuilding approval | DNV GL (EMC A) |
| Standards/regulations | EN 61000-4-2 |
| Tightening torque max | 0.6 Nm |
| Typical response time | < 1 s |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| Connection in parallel | yes, for redundancy and increased capacity |
| Input voltage range AC | 85 V AC ... 264 V AC (Derating < 100 V DC: 2.5%/V) |
| Input voltage range DC | 90 V DC ... 350 V DC (Derating < 110 V DC: 2.5%/V) |
| Maximum inrush current | ≤ 20 mA (short-circuit-proof) |
| Nominal output voltage | 24 V DC ±1 % |
| Note on status display | UOUT< 0.9 x UN: LED flashing |
| Tightening torque, min | 0.5 Nm |
| Continuous load current | ≤ 20 mA |
| Active current limitation | Approx. IBOOST= 45 A (for short-circuit) |
| Maximum switching voltage | ≤ 24 V |
| Nominal power consumption | 1051 W |
| Operating voltage display | Green LED |
| Standard - Safe isolation | DIN VDE 0100-410 |
| MTBF (IEC 61709, SN 29500) | > 500000 h |
| Permissible DC backup fuse | DC: Connect a suitable fuse upstream |
| Feedback voltage resistance | 35 V DC |
| Nominal input voltage range | 110 V AC ... 240 V AC |
| Nominal output current (IN) | 40 A (-25 °C ... 60 °C) |
| Standard - Equipment safety | GS (tested safety) |
| Power loss nominal load max. | 80 W |
| Standard - Electrical safety | EN 62368-1 |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Inrush current integral (I2t) | < 3.2 A2s |
| Insulation voltage input / PE | 3 kV AC (type test) |
| Insulation voltage output / PE | 500 V DC (routine test) |
| Voltage type of supply voltage | AC/DC |
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
| Insulation voltage input/output | 3 kV AC (type test) |
| Conductor cross section AWG max. | 10 |
| Conductor cross section AWG min. | 24 |
| Installation distance right/left | 0 mm / 0 mm |
| Installation distance top/bottom | 50 mm / 50 mm |
| Maximum no-load power dissipation | 28 W |
| Conductor cross section, rigid max. | 6 mm² |
| Conductor cross section, rigid min. | 0.2 mm² |
| EMC requirements for noise emission | EN 61000-6-3 |
| EMC requirements for noise immunity | EN 61000-6-1 |
| Peak switching voltages nominal load | < 50 mVPP(20 MHz) |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Standard – Safety extra-low voltage | EN 62368-1 (SELV) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Recommended breaker for input protection | 16 A ... 20 A (Characteristics B, C, D, K) |
| Setting range of the output voltage (USet) | 22.5 V DC ... 28.5 V DC (> 24 V DC, constant capacity restricted) |
| Max. permissible relative humidity (operation) | 95 % (at 25 °C, non-condensing) |
| Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
| Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
| Protection against overvoltage at the output (OVP) | ≤ 35 V DC |
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
| Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 62368-1 |
Technical specifications and performance data
Installation and operation guide