| Parameter | Value |
|---|---|
| GTIN | 4017918929534 |
| Orderkey | 2938963 |
| Catalog page | Page 596 (IF-2009) |
| Packing unit | 1 pc |
| Country of origin | CN (China) |
| Custom tariff number | 85049091 |
| (Ambient conditions) | 1x 48 A (16 mm² at 60°C) |
| Screw thread (General) | M4 |
| Efficiency (Output data) | > 97 % |
| Net weight (Output data) | 0.7 kg |
| (Connection data, output) | KEMA 03 ATEX 1197X |
| Stripping length (General) | 10 mm |
| Connection method (General) | Screw connection |
| Depth (Key Commercial Data) | 102 mm |
| Width (Key Commercial Data) | 62 mm |
| Height (Key Commercial Data) | 84 mm |
| ATEX (Connection data, output) | II 3G Ex nA IIC T4 Gc |
| Protection class (Output data) | II (in closed control cabinet) |
| Mounting position (Output data) | horizontal and vertical DIN rail NS 35, EN 60715 |
| Degree of pollution (Dimensions) | 2 |
| Connection in series (Input data) | No |
| Degree of protection (Dimensions) | IP20 |
| Degree of protection (Output data) | IP20 |
| Assembly instructions (Output data) | alignable: horizontal 20 mm, vertical 50 mm |
| Nominal output voltage (Input data) | 24 V DC |
| Weight per Piece (excluding packing) | 600.000 g |
| Screw thread (Connection data, input) | M4 |
| UL approvals (Connection data, output) | UL/C-UL listed UL 508 |
| Input voltage range (Ambient conditions) | 0 V DC ... 30 V DC |
| MTBF (IEC 61709, SN 29500) (Output data) | 28571428 h (40 °C) |
| Noise emission (Connection data, output) | EN 55011 |
| Noise immunity (Connection data, output) | EN 61000-6-2:2005 |
| Nominal output current (IN) (Input data) | 40 A |
| Power loss nominal load max. (Input data) | 20 W |
| Stripping length (Connection data, input) | 10 mm |
| Conductor cross section AWG max. (General) | 6 |
| Conductor cross section AWG min. (General) | 20 |
| Connection method (Connection data, input) | Screw connection |
| Maximum input current (Ambient conditions) | 2x 19 A (6 mm² at 40°C) |
| Nominal input current (Ambient conditions) | 2x 20 A |
| Nominal input voltage (Ambient conditions) | 24 V DC |
| Insulation voltage input / PE (Output data) | 1 kV |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 70 °C (> 60 °C derating, -25 ... 60°C) |
| Conductor cross section solid max. (General) | 16 mm² |
| Conductor cross section solid min. (General) | 0.5 mm² |
| Insulation voltage output / PE (Output data) | 1 kV |
| Conductor cross section flexible max. (General) | 10 mm² |
| Conductor cross section flexible min. (General) | 0.5 mm² |
| Shipbuilding approval (Connection data, output) | DNV GL (EMC A), ABS |
| Standards/regulations (Connection data, output) | EN 60079-0 |
| Nominal input voltage range (Ambient conditions) | 24 V DC |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Standard - Electrical safety (Connection data, output) | EN 60950-1/VDE 0805 (SELV) |
| Electromagnetic compatibility (Connection data, output) | Conformance with EMC Directive 2014/30/EU |
| Conductor cross section AWG max. (Connection data, input) | 6 |
| Conductor cross section AWG min. (Connection data, input) | 20 |
| Connection in acc. with standard (Connection data, output) | CUL |
| Conductor cross section solid max. (Connection data, input) | 16 mm² |
| Conductor cross section solid min. (Connection data, input) | 0.5 mm² |
| Max. permissible relative humidity (operation) (Dimensions) | ≤ 95 % (at 25 °C, non-condensing) |
| Conductor cross section flexible max. (Connection data, input) | 10 mm² |
| Conductor cross section flexible min. (Connection data, input) | 0.5 mm² |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations (Connection data, output) | EN 50178/VDE 0160 (PELV) |
Technical specifications and performance data
Installation and operation guide