| Parameter | Value |
|---|---|
| GTIN | 4017918959715 |
| Orderkey | 2866242 |
| (Signaling) | UL/C-UL Recognized UL 60950-1 |
| Catalog page | Page 587 (IF-2009) |
| Packing unit | 1 pc |
| (Output data) | 4 kV (type test) |
| Country of origin | CN (China) |
| Custom tariff number | 85371091 |
| (Ambient conditions) | 9 min. (40 A) |
| Screw thread (General) | M4 |
| Efficiency (Output data) | > 98 % |
| Net weight (Output data) | 0.9 kg |
| UL approvals (Signaling) | UL/C-UL listed UL 508 |
| Output power (Input data) | 960 W |
| Noise emission (Signaling) | EN 55011 (EN 55022) |
| Noise immunity (Signaling) | EN 61000-6-2:2005 |
| Stripping length (General) | 10 mm |
| Connection method (General) | Screw connection |
| Depth (Key Commercial Data) | 125 mm |
| Memory medium (Output data) | external, battery 3.4 Ah/7.2 Ah/12 Ah |
| Width (Key Commercial Data) | 66 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 130 mm |
| Protection class (Output data) | II (in closed control cabinet) |
| Input fuse (Ambient conditions) | 50 A (slow-blow, internal) |
| Mounting position (Output data) | horizontal DIN rail NS 35, EN 60715 |
| Connection in series (Input data) | yes |
| Degree of protection (Dimensions) | IP20 |
| Low Voltage Directive (Signaling) | Conformance with LV directive 2006/95/EC |
| Shipbuilding approval (Signaling) | DNV GL (EMC A), ABS |
| Buffer period (Ambient conditions) | 5 min. (40 A) |
| Degree of protection (Output data) | IP20 |
| Assembly instructions (Output data) | alignable: horizontally 0 mm, vertically 50 mm |
| Connection in parallel (Input data) | Yes, for increasing the buffer period |
| Nominal output voltage (Input data) | 24 V DC (Normal operation: Uin- 0.5 V DC, buffer mode: 27.9 to 19.2 V DC) |
| Weight per Piece (excluding packing) | 900.000 g |
| Output name (Connection data, output) | floating |
| Screw thread (Connection data, input) | M4 |
| Standard - Safe isolation (Signaling) | DIN VDE 0100-410 |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 25; |
| Screw thread (Connection data, output) | M3 |
| Operating voltage display (Output data) | Green LED |
| Current consumption (Ambient conditions) | approx. 0.1 A |
| Input voltage range (Ambient conditions) | 22.5 V DC ... 30 V DC |
| MTBF (IEC 61709, SN 29500) (Output data) | > 500000 h |
| Nominal output current (IN) (Input data) | 40 A |
| Standard - Electrical safety (Signaling) | EN 60950-1/VDE 0805 (SELV) |
| Status display (Connection data, output) | Yellow LED |
| Electromagnetic compatibility (Signaling) | Conformance with EMC Directive 2014/30/EU |
| Stripping length (Connection data, input) | 10 mm |
| Conductor cross section AWG max. (General) | 6 |
| Conductor cross section AWG min. (General) | 20 |
| Connection method (Connection data, input) | Screw connection |
| Nominal input voltage (Ambient conditions) | 24 V DC |
| Type of signaling (Connection data, output) | LED, relay contact |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 70 °C |
| Conductor cross section solid max. (General) | 16 mm² |
| Conductor cross section solid min. (General) | 0.5 mm² |
| Connection in acc. with standard (Signaling) | CUL |
| Output description (Connection data, output) | Battery Mode |
| Insulation voltage input/output (Output data) | 2 kV (routine test) |
| Standard - Safety of transformers (Signaling) | EN 61558-2-17 |
| Conductor cross section flexible max. (General) | 10 mm² |
| Conductor cross section flexible min. (General) | 0.5 mm² |
| Current consumption (idle) (Ambient conditions) | approx. 0.1 A |
| Tightening torque max (Connection data, output) | 0.6 Nm |
| Note on status display (Connection data, output) | Battery mode: LED permanently lit |
| Tightening torque, min (Connection data, output) | 0.5 Nm |
| Continuous load current (Connection data, output) | ≤ 1 A |
| Current consumption (maximum) (Ambient conditions) | 42.5 A (max.) |
| Maximum switching voltage (Connection data, output) | ≤ 30 V AC/DC |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Depth with alternative assembly (Key Commercial Data) | 69 mm |
| Width with alternative assembly (Key Commercial Data) | 122 mm |
| Height with alternative assembly (Key Commercial Data) | 130 mm |
| Conductor cross section AWG max. (Connection data, input) | 6 |
| Conductor cross section AWG min. (Connection data, input) | 20 |
| Conductor cross section AWG max. (Connection data, output) | 12 |
| Conductor cross section AWG min. (Connection data, output) | 24 |
| Conductor cross section solid max. (Connection data, input) | 16 mm² |
| Conductor cross section solid min. (Connection data, input) | 0.5 mm² |
| Current consumption (charging process) (Ambient conditions) | 2.5 A (charging process) |
| Max. permissible relative humidity (operation) (Dimensions) | 95 % (at 25 °C, non-condensing) |
| Conductor cross section solid max. (Connection data, output) | 4 mm² |
| Conductor cross section solid min. (Connection data, output) | 0.2 mm² |
| Conductor cross section flexible max. (Connection data, input) | 10 mm² |
| Conductor cross section flexible min. (Connection data, input) | 0.5 mm² |
| Conductor cross section flexible max. (Connection data, output) | 2.5 mm² |
| Conductor cross section flexible min. (Connection data, output) | 0.2 mm² |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations (Signaling) | EN 50178/VDE 0160 (PELV) |
Technical specifications and performance data
Installation and operation guide