| Parameter | Value |
|---|---|
| GTIN | 4046356554114 |
| Orderkey | 2320393 |
| (Signaling) | 15 Hz ... 150 Hz, 2.3g, 90 min. |
| Catalog page | Page 235 (C-6-2015) |
| Packing unit | 1 pc |
| Country of origin | CN (China) |
| Shock (Signaling) | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Voltage (Signaling) | 10 V (Test Level 3) |
| Comments (Signaling) | Criterion B |
| Custom tariff number | 85049091 |
| Screw thread (General) | M4 |
| UL approvals (Signaling) | UL/C-UL Recognized UL 60950-1 |
| Noise immunity (Signaling) | EN 61000-6-2:2005 |
| Stripping length (General) | 10 mm |
| Climatic class (Dimensions) | 3K3 (in acc. with EN 60721) |
| Connection method (General) | Screw connection |
| Depth (Key Commercial Data) | 125 mm |
| Frequency range (Signaling) | 0.15 MHz ... 80 MHz |
| Width (Key Commercial Data) | 64 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 130 mm |
| Contact discharge (Signaling) | 4 kV (Test Level 2) |
| Test field strength (Signaling) | 3 V/m |
| Degree of pollution (Dimensions) | 2 |
| Installation height (Dimensions) | 2000 m |
| Net weight (General output data) | 1.1 kg |
| Degree of protection (Dimensions) | IP20 |
| Low Voltage Directive (Signaling) | Conformance with LV directive 2006/95/EC |
| POWER BOOST (IBoost) (Input data) | |
| Standards/regulations (Signaling) | EN 61000-6-3 |
| Vibration (operation) (Signaling) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| Input voltage (Ambient conditions) | 24 V DC |
| IQ technology (General output data) | no |
| Memory medium (General output data) | Electrolytic capacitor |
| Nominal output voltage (Input data) | 24 V DC |
| Weight per Piece (excluding packing) | 1,100.000 g |
| Output name (Connection data, output) | Power Good signal output active (high = buffer module charged) |
| Screw thread (Connection data, input) | M4 |
| Standard - Safe isolation (Signaling) | DIN VDE 0106-101 |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 25; |
| Protection class (General output data) | III |
| Screw thread (Connection data, output) | M4 |
| Mounting position (General output data) | horizontal DIN rail NS 35, EN 60715 |
| Input voltage range (Ambient conditions) | 18 V DC ... 30 V DC |
| Nominal output current (IN) (Input data) | 40 A |
| Output voltage (Connection data, output) | + 24 V |
| Standard - Electrical safety (Signaling) | EN 60950-1/VDE 0805 (SELV) |
| Status display (Connection data, output) | LED "Power Good", green |
| Electromagnetic compatibility (Signaling) | Conformance with EMC Directive 2014/30/EU |
| Stripping length (Connection data, input) | 10 mm |
| Conductor cross section AWG max. (General) | 6 |
| Conductor cross section AWG min. (General) | 8 |
| Connection method (Connection data, input) | Screw connection |
| Assembly instructions (General output data) | alignable: horizontally 0 mm, vertically 50 mm |
| Selective Fuse Breaking (ISFB) (Input data) | |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 80 °C |
| Conductor cross section solid max. (General) | 16 mm² |
| Conductor cross section solid min. (General) | 0.5 mm² |
| Connection in acc. with standard (Signaling) | CUL |
| Fixed connect threshold (Ambient conditions) | < 20 V DC (< 22 V; < 24 V; < 26 V) |
| Output description (Connection data, output) | Power Good |
| Standard - Safety of transformers (Signaling) | EN 61558-2-17 |
| Conductor cross section flexible max. (General) | 16 mm² |
| Conductor cross section flexible min. (General) | 0.5 mm² |
| Current consumption (idle) (Ambient conditions) | 0.1 A (No-load) |
| Tightening torque max (Connection data, output) | 0.6 Nm |
| Variable connect threshold (Ambient conditions) | (UIN- 1 V)/0.1 s |
| MTBF (IEC 61709, SN 29500) (General output data) | > 902000 h (40 °C) |
| Note on status display (Connection data, output) | Buffer module is loaded: LED ON |
| Tightening torque, min (Connection data, output) | 0.5 Nm |
| Continuous load current (Connection data, output) | 20 mA |
| Standard – Safety extra-low voltage (Signaling) | EN 60950-1 (SELV) and EN 60204 (PELV) |
| Current consumption (maximum) (Ambient conditions) | 45 A (Conduction current) |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Efficiency (Output data (24 V DC battery operation)) | > 99 % (Mains operation, with charged energy storage) |
| Depth with alternative assembly (Key Commercial Data) | 67 mm |
| Width with alternative assembly (Key Commercial Data) | 122 mm |
| Height with alternative assembly (Key Commercial Data) | 130 mm |
| Conductor cross section AWG max. (Connection data, input) | 6 |
| Conductor cross section AWG min. (Connection data, input) | 8 |
| Conductor cross section AWG max. (Connection data, output) | 12 |
| Conductor cross section AWG min. (Connection data, output) | 24 |
| Conductor cross section solid max. (Connection data, input) | 16 mm² |
| Conductor cross section solid min. (Connection data, input) | 0.5 mm² |
| Current consumption (charging process) (Ambient conditions) | 0.7 A (charging process) |
| Max. permissible relative humidity (operation) (Dimensions) | ≤ 95 % (at 25 °C, non-condensing) |
| Conductor cross section solid max. (Connection data, output) | 4 mm² |
| Conductor cross section solid min. (Connection data, output) | 0.2 mm² |
| POWER BOOST (IBoost) (Output data (24 V DC mains operation)) | |
| Conductor cross section flexible max. (Connection data, input) | 16 mm² |
| Conductor cross section flexible min. (Connection data, input) | 0.5 mm² |
| Nominal output voltage (Output data (24 V DC mains operation)) | 24 V DC |
| Conductor cross section flexible max. (Connection data, output) | 2.5 mm² |
| Conductor cross section flexible min. (Connection data, output) | 0.2 mm² |
| Output voltage range (depends on the input voltage) (Input data) | 18 V DC ... 30.5 V DC |
| Nominal output current (IN) (Output data (24 V DC mains operation)) | 40 A |
| Selective Fuse Breaking (ISFB) (Output data (24 V DC mains operation)) | |
| Output voltage range (depends on the input voltage) (Output data (24 V DC mains operation)) | 19.2 V DC ... 27.6 V DC |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations (Signaling) | EN 50178/VDE 0160 (PELV) |
Technical specifications and performance data
Installation and operation guide