| Parameter | Value |
|---|---|
| 500 V DC | |
| Color | green (RAL 6021) |
| Width | 24 mm |
| Coding | no |
| Height | 24 mm |
| Length | 62.2 mm |
| Diameter | 24 mm |
| Product type | Cable connector |
| Assembly note | If the conductor is reconnected, it must be cut off above the last contact point. QUICKON components may only be operated when under no load. |
| Impact strength | IK06 |
| Material Contact | Copper alloy |
| Material Housing | PA |
| Position marking | 1, 2, 3 |
| Tightening torque | 2.5 Nm |
| Contact resistance | ≤ 5 mΩ |
| Nominal current IN | 17.5 A |
| Nominal voltage UN | 500 V AC |
| Degree of pollution | 3 |
| Dimensional drawing | |
| Number of positions | 3 |
| Degree of protection | IP65 |
| Overvoltage category | III |
| rated voltage (II/2) | 630 V |
| Number of connections | 3 |
| Rated voltage (III/3) | 250 V |
| Wrench size Union nut | 24 mm |
| rated voltage (III/2) | 320 V |
| External cable diameter | 7 mm ... 9 mm |
| Material Contact surface | Sn |
| Material wire insulation | PVC / PE |
| Rated surge voltage (II/2) | 6 kV |
| Rated surge voltage (III/2) | 6 kV |
| Rated surge voltage (III/3) | 6 kV |
| Tightening torque Union nut | 2.5 Nm |
| Wrench size Contact carrier | 24 mm |
| Ambient temperature (operation) | -25 °C ... 80 °C |
| Number of connections per position | 1 |
| Wire diameter including insulation | >= 3 mm |
| Temperature when conductor connected | -5 °C ... 50 °C |
| Flammability rating according to UL 94 | V0 |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Frequency of connections between conductors of the same cross section | max. 10 (if the conductor is connected more than once, seal and cap may need to be replaced.) |
| Structure of individual litz in acc. with VDE 0295 / smallest wire diameter | VDE 0295 class 1 to 6/min. 0.15 mm |
Technical specifications and performance data
Installation and operation guide