| Parameter | Value |
|---|---|
| • WARNING: Only electrically qualified personnel may install and operate the product. They must observe the following safety notes. The qualified personnel must be familiar with the basics of electrical engineering. They must be able to recognize and prevent danger. The relevant symbol on the packaging indicates that only personnel familiar with electrical engineering are allowed to install and operate the product. | |
| Color | black |
| Width | 26.3 mm |
| Height | 26.3 mm |
| Length | 41.5 mm |
| Cable type | S03 |
| Safety note | • WARNING: Commission properly functioning products only. The products must be regularly inspected for damage. Decommission defective products immediately. Replace damaged products. Repairs are not possible. |
| Cable length | 300 mm |
| Halogen-free | yes |
| Product type | Panel feed-through |
| Seal material | EPDM |
| Product family | SUNCLIX |
| Cable structure | 84 x 0.30 mm Ø litz wires, tin-plated, 1x bunched |
| Contact surface | Silver Ag |
| Insertion force | 45 N ±10 N |
| Article revision | 10 |
| Contact material | Cu |
| Flame resistance | no |
| Housing material | PPE |
| Protection class | II |
| Withdrawal force | 250 N ±50 N (when locked) |
| Resistance to oil | no |
| Tightening torque | 1.8 Nm ±0.1 Nm |
| Contact resistance | 0.45 mΩ |
| Cable cross section | 6 mm² |
| Cable seal material | Elastosil LR 3065/50 |
| Degree of pollution | 2 |
| Dimensional drawing | |
| Insulating material | mPPE |
| Number of positions | 1 |
| Test voltage, cable | ≥ 8 kV AC (Spark test online (standard designation)) |
| Cable pull-out force | > 80 N |
| Rated voltage (III/2) | 1000 V |
| Single wire, material | Cu |
| External sheath, color | red, similar to RAL 3000 |
| Nominal voltage, cable | 1.8 kV DC (max U (conductor / conductor, ungrounded system)) |
| Outer sheath, material | PE-X |
| External cable diameter | 5.40 mm ±0.15 mm |
| Contact carrier material | PPE |
| Contact surface material | Ag |
| Rated current (6.0 mm²) | 40 A |
| Color of the housing part | black |
| Insulating material group | III |
| Single wire, cross section | 6 mm² |
| Insertion/withdrawal cycles | 100 |
| Rated surge voltage (III/2) | 12 kV |
| Ambient temperature (assembly) | -25 °C ... 50 °C |
| Ambient temperature (operation) | -40 °C ... 85 °C |
| Degree of protection (not plugged in) | IP20 |
| Degree of protection (when plugged in) | IP66 / IP68 (2 m / 24 h) |
| Flammability rating according to UL 94 | V0 |
| Smallest bending radius, fixed installation | 27 mm (5x Ø) |
| Smallest bending radius, movable installation | 54 mm (10x Ø) |
| Structure of individual litz in acc. with VDE 0295 / smallest wire diameter | 84x0.3 |
Technical specifications and performance data