| Parameter | Value |
|---|---|
| 150 mm² / 15 kg | |
| Color | gray (RAL 7042) |
| Width | 31 mm |
| Height | 116.4 mm |
| Result | Test passed |
| Spectrum | Service life test category 1, class B, body mounted |
| ASD level | 0.964 (m/s²)²/Hz |
| Frequency | f1= 5 Hz to f2= 250 Hz |
| Potentials | 1 |
| Pulse shape | Half-sine |
| Acceleration | 0.58g |
| Product type | High current terminal block |
| Mounting type | NS 35/15 |
| Specification | DIN EN 50155 (VDE 0115-200):2018-05 |
| Number of rows | 1 |
| Shock duration | 30 ms |
| Nominal current | 309 A |
| Nominal voltage | 1000 V |
| Open side panel | No |
| Test directions | X-, Y- and Z-axis |
| Article revision | 06 |
| Stripping length | 40 mm |
| Time of exposure | 10 s |
| Cross section AWG | 250 kcmil ... 350 kcmil (converted acc. to IEC) |
| Depth on NS 35/15 | 116.5 mm |
| Temperature cycles | 192 |
| Degree of pollution | 3 |
| Insulating material | PA |
| Number of positions | 1 |
| Rated surge voltage | 8 kV |
| Test force setpoint | 15 N |
| Maximum load current | 309 A (with 185 mm² conductor cross section) |
| Overvoltage category | III |
| Nominal cross section | 150 mm² |
| Number of connections | 2 |
| Test duration per axis | 5 h |
| DIN rail/fixing support | NS 35/15 |
| Insulating material group | I |
| Internal cylindrical gage | B14 |
| Conductor cross section rigid | 95 mm² ... 185 mm² |
| Ambient temperature (assembly) | -5 °C ... 70 °C |
| Conductor cross section/weight | 95 mm²/14 kg |
| Number of shocks per direction | 3 |
| Ambient temperature (actuation) | -5 °C ... 70 °C |
| Ambient temperature (operation) | -60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) |
| Number of connections per level | 2 |
| Conductor cross section flexible | 95 mm² ... 185 mm² |
| Connection in acc. with standard | IEC 60947-7-1 |
| Permissible humidity (operation) | 20 % ... 90 % |
| Requirement temperature-rise test | Increase in temperature ≤ 45 K |
| Short-time withstand current 150 mm² | 18 kA |
| Flammability rating according to UL 94 | V0 |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
| Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, no longer than 24 h, -60°C to +70°C) |
| Conductor cross section, flexible [AWG] | 250 kcmil ... 350 kcmil (converted acc. to IEC) |
| Permissible humidity (storage/transport) | 30 % ... 70 % |
| Cross-section with insertion bridge, rigid | 95 mm² ... 150 mm² |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| Cross-section with insertion bridge, flexible | 95 mm² ... 150 mm² |
| Static insulating material application in cold | -60 °C |
| Maximum power dissipation for nominal condition | 9.55 W |
| Calorimetric heat release NFPA 130 (ASTM E 1354) | 27,5 MJ/kg |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Flexible conductor cross section (ferrule with plastic sleeve) | 95 mm² ... 150 mm² |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Conductor cross-section flexible (ferrule without plastic sleeve) | 95 mm² ... 150 mm² |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
| Cross-section with insertion bridge, flexible, with ferrule with plastic sleeve | 95 mm² ... 120 mm² |
| Cross-section with insertion bridge, flexible, with ferrule without plastic sleeve | 95 mm² ... 120 mm² |
Technical specifications and performance data
Installation and operation guide